This guidance includes the description, operation principle, instructions on installation,
configuration and operation of fire alarm control panel (further
–
FACP) Tiras PRIME 8L.
In order to avoid possible errors during operation and possible damage to the
equipment, before the installation, configuration and operation of FACP, please read this
document and also the user manual, which are provided with the control panel.
This document does not specify the installation rules for fire alarm systems.
The following abbreviations are used in this document:
FACP
–
fire alarm control panel;
FARS
–
fire alarm receiving station;
PC
–
personal computer;
ATS
–
alarm transmission system;
SC
–
short circuit;
PS
–
power supply;
IM
–
Installation Manual for FACP (
1 Purpose
FACP is designed to:
•
Control the state of fire alarm detectors;
•
Control the sounders;
•
Control the external devices;
•
Control the state of external devices;
FACP is the basis of fire alarm system, which can be added to:
•
Expansion module, for increasing the number of zones
–
M-Z (f).
Installed on the
FACP board;
•
Relay module
for 4 relays
M-OUT4R
.
Installed on the FACP board;
The example of connection of modules to FACP is provided in
appendix A
.
2 General information
•
8 zones
(can be expanded to 20 zones, using M-Z(f) module);
•
Up to
32 detectors
in each zone;
•
Dependence
in zones
(Verification);
•
2
controlled
outputs for sounders
;
•
Outputs to
fire alarm
and
fault warning
routing equipment;
•
2 programmable relay outputs
;
•
Controllable
power outputs - 24V
;
•
LCD display
wit highlight;
•
Day-Night
mode to control the activation of outputs;
•
Programming of
scripts
for outputs and inputs operation;
•
Configuration with
PC and Android-device (via USB);
•
Intelligent
charging device with battery capacity control;
•
Non-volatile clock
and event log
–
up to 1000 events;
•
Alternative power supply
–
2 batteries with a capacity of 7 Ah;
•
Intelligent
charging device with battery capacity control;
•
Powerful switching PS
–
24V/2A;