1. General Information
These instructions should be read carefully and retained for further reference
and maintenance.
2. Safety
• Before installation or maintenance, ensure the mains supply to the
thermostat is switched off and the circuit supply fuses are removed or the
circuit breaker turned off.
• It is recommended that a qualified electrician is consulted or used for the
installation of this thermostat and install in accordance with the current
IEE wiring and Building Regulations.
• Check that the total load on the circuit including when this thermostat is
fitted does not exceed the rating of the circuit cable, fuse or circuit breaker.
• To clean use a clean dry cloth only. Do not use any liquid cleaners.
3. Technical Specifications
• 230V AC 50 Hz
• This time switch is of Class ll Construction and must not be earthed
• Switch Rating:
6(2)A
• Switch Type:
Single pole, single throw (SPST)
• Connection Type:
3 wire
• Installation Type:
Surface mount with wall plate
• Micro Disconnection:
Type 1.B control action
• Operating Temperature Range: 0°C to +40°C
• Set Temperature Range:
M5°C (frost setting)
to m30°C
• Temperature Swing Adjuster: +/- 0.5°C or 1.0°C set by DIP switch
• PID Adjustment:
ON or OFF set by DIP switch