background image

PDFM362 / PDFM361 can also be 
controlled by the infrared remote 
controller IR-10. As well as allowing 
remote setting of times and light level 
the IR-10 also enables continuous 
operation for 8 hours in ON or OFF 
modes as well as continuously in 
detection mode controlled by or 
independent of light level.

The IR-10 is invaluable during 
commissioning enabling changes to 
be made without resorting to ladders.

Further to this the IR-10 can download 
stored settings from one sensor to additional sensors in the 
same area.

3.3.2 (cont). The protection covers have teeth (see Fig. 8-A) giving a 
degree of cable clamping if power and load are connected by individual 
wires (0.8 -1.8mm dia.).

If connection is by cable (9 - 11mm dia.) then use of a coarse rat-tailed 
file to open out as many of the holes as necessary using the markings 
on the inside of the  protection cover as an approximate guide 
(see Fig. 8-B).

Referring it to the appropriate wiring diagram insert the wires into the 
correct screw terminals and tighten fully. Then plug the sensor lead into 
SENSOR A socket only.

Use the coarse rat-tailed file to open a single hole (smaller than that 
above) in the remaining protection cover to take the sensor cable with a 
degree of strain relief. Secure down the protection covers.

3.3.3 Feed the wires/cables followed by the power unit through the 
65mm dia. ceiling hole (see Fig. 9).

4.1.1 TIME control adjustment

These are delay times between the sensor being triggered and the 
controller switching off assuming no further detections are made.

If there are additional detections the time delay applies from the latest 
detection.

PDFM362:

TIME 1: Adjustable from 5sec to 20min (lighting). (Extendable to 30min 
and 60min when in use with the IR-10 remote controller).

TIME 2: Adjustable from 10sec to 60min (HVAC).

PDFM361:

TIME: Adjustable from 5sec to 20min (lighting). (Extendable to 30min 
and 60min when in use with the IR-10 remote controller).

4.1.2 LUX control adjustment

The LUX level below which the sensor will operate is adjustable from 
10 LUX (operation only after dusk) to 2000 LUX (operation at any light 
level).

4.1.3 METER control adjustment

This control sets the diameter of detection coverage at floor level. 
Assuming a ceiling height of 2.5m at the + end of the scale the 
coverage diameter will be 7m, at the - end of the scale the coverage 
diameter will be 1m.

The affect of METER control at other ceiling heights is shown in section 3.1.

4.2 Test Mode

4.2.1 Sensor warm up

The detector will take a minimum of 60 seconds to warm up when the 
power is connected to it for the first time or if the power is being 
re-connected after being turned off.

During this period load I and the sensor LED will both be on. After the 
warm up is finished the sensor will revert to operation according to the 
settings of the controls on the sensor body.

4.2.2 LED function

There is a red LED (see Fig. 12) built into the sensor and visable through 
the PIR lens that shows the status of the loads and enables testing to be 
carried out without the loads 
being connected.

If the IR-10 remote controller
is in use the LED will flash to 
give confirmation of the 
commands and adjustments 
made by the IR-10.

3.3.4 Force the spring clips back until they can feed into the ceiling hole 
(see Fig. 10-A) and then push  the sensor upwards into place so that its 
flange fits tightly against the ceiling (see Fig. 10-B).

Fig. 8-A

Fig. 8-B

Fig. 9

Fig. 10-A

Fig. 10-B

4

 Test and Operation

5

 Troubleshooting

6

 Optional Remote Control - IR-10

4.1 Time, LUX and Meter Controls

Following marked values (excepting TEST and       ) are approximate, 
the values are continuously adjustable over the control range 
(see Fig.11-A & Fig.11-B).

Fig. 11-A (PDFM362 control dials)

Fig. 11-B (PDFM361 control dials)

4.2.3 Adjusting sensor head

The sensor head can be tilted by as much as 30º off axis as shown 
in Fig. 13A. This can be achieved by using a flat blade screwdriver 
as shown in Fig. 13B.

Fig. 13C shows the tilt angle markings on the sensor body. The tilt 
angle is read off against the edge of the mounting flange.

Fig. 13D shows the detection coverage for various tilt angles. The 
tilt angle can be used in conjunction with rotation of the sensor 
head within the flange up to 350º to give the required coverage 
in any direction. The markings on the sensor mounting flange (see 
Fig. 13E) giving 30º per division provide a useful way of adjusting 
angular position.

When the PDFM362 / PDFM361 is not working as expected go 
through the troubleshooting guide below.

4.2.4 Walk test

Turn supply on and wait at least 60 seconds for the system to 
settle down.

Turn Time 1 control to the Test position. This means that the sensor 
LED and load I will turn on for 2 seconds after triggering and then 
be off for 3 seconds after which the sensor can be re-triggered. 
The triggering is independent of light level.

The installer should move around in the detection area to establish 
that it is all covered. If necessary the tilt and rotation of the sensor 
should be adjusted, after which the area should be walk tested 
again to confirm coverage is as required.

To confirm that load 2 (HVAC) is operating correctly for a 
PDFM362, carry out the following:- 

Turn LUX (light level) to its minimum value (10 lux) to stop load 
1 (lights) from turning on. Then turn TIME 2 (HVAC) to minimum 
value (10s) and carry out a limited walk test to confirm correct 
operation of load 2.

Fig. 12

Fig. 13A

Fig. 13B

Fig. 13C

Fig. 13D

Fig. 13E

 

Problem Possible 

Suggested 

 

 

  

Cause 

Solution

 

Problem Possible 

Suggested 

 

 

  

Cause 

Solution

Lighting or 
HVAC does not 
turn off.

LED does not 
turn on.

Nuisance
triggering.

Lights do not 
turn on.

1. Incorrect time setting.

2. Incorrect wiring.

1. Out of detection range.

2. Power supply not on.
3. ”TIME” knob setting 
isn’t on “Test”.
4. Incorrect wiring.

There are heat sources, 
HVAC vents/fans, highly 
reflective surfaces or
anything which may be 
swayed by air movement 
within the detection 
coverage.

1. Power is not turned on.
2. Incorrect control dial 
setting.

3. Incorrect wiring.

4. Faulty load.

1. Check that the correct 
delay time is set on either 
TIME 1 or TIME 2 control 
dial. Then determine if 
nuisance triggering is 
keeping the unit turned on.
2. Make sure supply and 
load wires are connected 
correctly.

1. Walk within the effective 
detection range.
2. Switch the power on.
3. Turn the control position
to “Test”.
4. Refer to wiring diagrams 
(Fig. 3 to Fig.5).

Avoid aiming the sensor 
toward any heat sources, 
such as air conditioners, 
electric fans, heaters or any 
highly reflective surfaces. 
Make sure there are no 
swaying objects within the 
detection coverage.

1. Switch on the power.
2. Check if control dials are 
set to the correct position, 
then supply the power to 
check if the LED will turn on.
3. Refer to wiring diagrams 
(Fig. 3 to Fig. 5)
4. Replace the faulty load.

3 Year Guarantee

In the unlikely event of this product becoming faulty due to defective 

material or manufacture within 3 years of the date of purchase, please 

return it to your supplier in the first year with proof of purchase and it will 

be replaced free of charge. For years 2 and 3 or any difficulty in the first year 

telephone the helpline on

 

020 8450 0515.

HELPLINE

020-8450-0515

or email [email protected]

For a product brochure please contact:

Timeguard Ltd.

020-8452-1112

or email [email protected]

A               Group company

67-058-277 (Iss. 2)

For assistance with the product please contact:-

Fig. 14

PDFM361_362_Instructions_2.indd   2

PDFM361_362_Instructions_2.indd   2

14/5/08   09:04:56

14/5/08   09:04:56

Содержание PDSM362

Страница 1: ...2000LUX Adjustment continuously adjustable Max Detection Coverage 360º cone shape from ceiling height of 2 5m giving 7m dia coverage at floor level for affect of ceiling height on coverage see section 3 1 1 Conforms To EC Directives All procedures indicated in this manual must be carried out by a professional installer METER Adjustment Adjustable continuously from giving maximum detection coverage...

Страница 2: ...2000LUX Adjustment continuously adjustable Max Detection Coverage 360º cone shape from ceiling height of 2 5m giving 7m dia coverage at floor level for affect of ceiling height on coverage see section 3 1 1 Conforms To EC Directives All procedures indicated in this manual must be carried out by a professional installer METER Adjustment Adjustable continuously from giving maximum detection coverage...

Страница 3: ...the control range see Fig 11 A Fig 11 B Fig 11 A PDFM362 control dials Fig 11 B PDFM361 control dials 4 2 3 Adjusting sensor head The sensor head can be tilted by as much as 30º off axis as shown in Fig 13A This can be achieved by using a flat blade screwdriver as shown in Fig 13B Fig 13C shows the tilt angle markings on the sensor body The tilt angle is read off against the edge of the mounting f...

Страница 4: ...the control range see Fig 11 A Fig 11 B Fig 11 A PDFM362 control dials Fig 11 B PDFM361 control dials 4 2 3 Adjusting sensor head The sensor head can be tilted by as much as 30º off axis as shown in Fig 13A This can be achieved by using a flat blade screwdriver as shown in Fig 13B Fig 13C shows the tilt angle markings on the sensor body The tilt angle is read off against the edge of the mounting f...

Отзывы: