Output – Profibus/Profinet
LQT40F has a Profibus or Profinet output for fast serial communication. Three different set of
”P
rocess Data Set Mapping
””
are availble. Each mapping has a unique GSD-file. The files are availble
from Tillquist homepage.
4.1
Process Data Set Mapping
A: Basic
–
Is the same mapping as old LQT60F
B: High Resolution F
Parameters
Data
Set
Parameter
Range
Bus value
Type
Byte
Note
A
B
Bus Inc Num
-
-
0-65535
Unsigned Word
1-2
-
X
X
Data Inc Num
-
-
0-65535
Unsigned Word
3-4
-
X
X
I_RMS
0-12
A
0-65535
Unsigned Word
5-6
(I1+I2+I3)/3
X
X
U_RMS
0-300
V
0-65535
Unsigned Word
7-8
(U1+U2+U3)/3
X
X
P_RMS
±10800
W
±10800000 Signed Double Word
9-12
P=P1+P2+P3
X
X
Q_RMS
±10800
var
±10800000 Signed Double Word
13-16
Q=Q1+Q2+Q3
X
X
F
0-300
Hz
0-65535
Unsigned Word
17-18
-
X
X
F_HIRES
0-300
Hz
0-300000
Unsigned Double Word
19-22
-
X
A: Basic
Bus Increment Number increase with every new message.
B: Basic + High Resolution F
Data Increment Number
increase with every new measured
C: Extended
Parameters
Data
Set
Parameter
Range
Bus value
Type
Byte
Note
C
Bus Inc Num
-
-
0-65535
Unsigned Word
1-2
-
X
Data Inc Num
-
-
0-65535
Unsigned Word
3-4
-
X
I_RMS
0-12
A
0-12000
Unsigned Double Word
5-8
(I1+I2+I3)/3
X
U_RMS
0-300
V
0-300000
Unsigned Double Word
9-12
(U1+U2+U3)/3
X
P_RMS
±10800
W
±10800000 Signed Double Word
13-16
P=P1+P2+P3
X
Q_RMS
±10800
var
±10800000 Signed Double Word
17-20
Q=Q1+Q2+Q3
X
F
0-300
Hz
0-300000
Unsigned Double Word
21-24
-
X
I1
0-12
A
0-12000
Unsigned Double Word
25-28
-
X
I2
0-12
A
0-12000
Unsigned Double Word
29-32
-
X
I3
0-12
A
0-12000
Unsigned Double Word
33-36
-
X
U1
0-300
V
0-300000
Unsigned Double Word
37-40
-
X
U2
0-300
V
0-300000
Unsigned Double Word
41-44
-
X
U3
0-300
V
0-300000
Unsigned Double Word
45-48
-
X
U12
0-520
V
0-520000
Unsigned Double Word
49-52
-
X
U23
0-520
V
0-520000
Unsigned Double Word
53-56
-
X
U31
0-520
V
0-520000
Unsigned Double Word
57-60
-
X
P1
±3600
W
±3600000
Signed Double Word
61-64
-
X
P2
±3600
W
±3600000
Signed Double Word
65-68
-
X
P3
±3600
W
±3600000
Signed Double Word
69-72
-
X
Q1
±3600
var
±3600000
Signed Double Word
73-76
-
X
Q2
±3600
var
±3600000
Signed Double Word
77-80
-
X
Q3
±3600
var
±3600000
Signed Double Word
81-84
-
X
LF
±1
±1000
Signed Double Word
85-88
-
X
PA
±180
°
±180000
Signed Double Word
89-92
-
X
C: Extended
Bus Increment Number increase with every new message.
Data Increment Number
increase with every new measured
4.2
Profibus
The address of the Profibus DP is set via the software ConfigLQT.