2

 

Instructions 

2.1

 

Mounting 

The transducer is mounted on a 35mm DIN rail on a wall or device cabinet for suitable 
protection. The enclosure shall not be accessible without tools. 
 

2.2

 

Installation 

The  installation  is  to  be  made  by  competent  personnel  and  in  accordance  with 
applicable  regulations.  Before  installation  please  check  that  the  transducer  has  the 
correct type and complies with the installation needs. The connection to the transducer 
is  done  through  the  terminals  that  are  designed  for  a  maximum  of  6  mm²  cable  in 
accordance with connection diagram. An external switch shall be used so that the unit 
can  be  deenergized  during  disassembly.  It  shall  be  appropriately  positioned,  easy  to 
reach  and  marked  as  a  switch  for  the  transducer.  The  measuring  circuits  from  the 
current  transformers  must  be  short-circuited  before  disconnection.  The  unit  must  be 
protected against possible overcurrent by automatic circuit breaker.  

2.3

 

Operation 

The transducer is intended for operation at an altitude not exceeding 2000m and in an 
environment that is not considered as wet location. 

2.4

 

 Warning! 

Connection must comply with current regulations for systems with rated voltage up to 
1000 V. 
 
Before  switching on or off and  if the housing is removed, all voltages to the  appliance 
must be switched off. 

2.5

 

Maintenance 

The  transducer  requires  no  maintenance.  Any  repairs  shall  be  performed  by  trained 
personnel or the appliance shall be returned to the supplier for repair. 
 
Function and safety are only guaranteed if the instructions in this manual are followed. 
 
 
 
 
 
 
 
 
 

Содержание LQT400

Страница 1: ...Manual LQT400 Rev EN2020 11 04 USER MANUAL LQT400 HUGO TILLQUIST AB Box 1120 SE 164 22 KISTA Sweden Tel 46 8 594 632 00 info tillquist com www tillquist com...

Страница 2: ...i transducer with 2 analog outputs that can be configured to measure any electrical quantity All areas for AC current and voltage True RMS are covered by one single unit Our free transducer configurat...

Страница 3: ...s 3 2 7 Symbols on the appliance 3 2 8 Installation of ConfigLQT 3 3 Configuration 4 3 1 Connection to computer 4 3 1 1 Monitored parameters 5 3 2 Input settings 5 3 2 1 System connection 6 3 3 Analog...

Страница 4: ...x In continuously 10 x In 15 s 40 x In 1 s Consumption 0 05 VA phase AUX Supply Universal current 24 2W 253VDC 3W 5 80 4VA 253VAC 5VA 50 60 Hz 5 Outputs Analog Quantity 2 pcs Range 20 mA Load max 750...

Страница 5: ...positioned easy to reach and marked as a switch for the transducer The measuring circuits from the current transformers must be short circuited before disconnection The unit must be protected against...

Страница 6: ...uations 2 8 Installation of ConfigLQT The installation kit consists of the configuration software and a driver for the USB connection to LQT400 NET Framework version 4 0 is a software from Microsoft u...

Страница 7: ...ection is established Various basic parameters of the transducer as well as the measured values are displayed on the screen when the transducer is connected to a measuring object The measured values c...

Страница 8: ...se angle F Frequency 3 2 Input settings Read configuration Read present settings from LQT400 to ConfigLQT Apply configuration Save data to LQT400 Configuration using choose which values will be shown...

Страница 9: ...mmetrical load 01 1 phase 1 system 02 3 phase 1 system 3 phase symmetrical load 03 3 phase 1 system 3 phase symmetrical load 04 3 phase 1 system 3 phase symmetrical load 05 3 phase 1 system 3 phase sy...

Страница 10: ...d X X PI1U23 QI1U23 I1 U23 3 04 3 wires 3 phase symmetrical load X X PI1U31 QI1U32 I1 U31 3 05 3 wires 3 phase symmetrical load X X X X X X X I1 P1 3 Q1 3 S1 3 09 3 wires 3 phase asymmetrical load X X...

Страница 11: ...alues are to be written in the first space any breakpoints afterwards and the end value at last Under Output Value the corresponding values of the output signal are indicated Click Apply configuration...

Страница 12: ...OS 3 P3 S3 L3 QF Reactive power factor Q S System QF1 Reactive power factor SIN 1 Q1 S1 L1 QF2 Reactive power factor SIN 2 Q2 S2 L2 QF3 Reactive power factor SIN 3 Q3 S3 L3 LF LF factor sign Q 1 PF Sy...

Страница 13: ...condary Analog out 0 0 5 20 P Measuring total power IN 50 MW OUT 20 mA Primary Analog out 50000 20 50000 20 Q Measuring total power IN 28 MVar OUT 20 mA Primary Analog out 28000 20 28000 20 U12 Measur...

Страница 14: ...nloaded to other transducers 3 4 1 Save a configuration to a file 1 Select File menu and click Save as 2 Write a file name and choose a desired folder 3 Click Save 3 4 2 Open a configuration from a sa...

Страница 15: ...able 1 Start ConfigLQT 2 Select Firmware Upgrade from Transducer menu 3 Choose the file with the new firmware and Upgrade 4 When the upgrade is done the auxiliary voltage must be disconnected so that...

Отзывы: