background image

18

 

EN

 

  

 

 

 

TIMER FEATURE

 

In the TIMER feature you can set the timer points for operation of heat pump at various temperatures. The feature enables four time 

points daily for different settings of the water temperature or heat pump shut

-

down. The next timer point cannot be set one hour after 

the previous setting. The time setting step is 10 min. If the   symbol in field no. 

16

 is not visible, the TIMER feature is not available.

 

When setting the timer you must know the habits and take into account the duration of heating times. Senseless settings to which the 

system cannot respond will not achieve the set temperature points and will have a negative impact on the heat pump

s efficiency.

 

  

 

 

SELECTING THE TIMER MODE OF OPERATION

 

  

 

 

TIMER MODE FOR THE ENTIRE WEEK

 

  

 

 

 

 

4

17

 

While the feature is on, field no. 

4

 is illuminated.

 

 

 

Field no. 

17

 shows the number of days remaining until the end of the VACATION mode. If the 

display is in the saving mode, touch the display to see the number of remaining days.

 

 

 

After the set number of days has elapsed, the heat pump resumes the previously set mode of 

operation, and illumination of field no. 

4

 stops.

 

 

 

The "VACATION" feature can be switched off manually by pressing field no. 

4

 briefly (main 

display).

 

 

 

In case the heater is disabled (parameter 01:09) minimum temperature is maintained only 

by the heat pump operation. In case the source temperature is outside the range of 

operation of the heat pump, freeze protection will not work!

 

 

16

1.

 

Hold (for 3 s) field no. 

16

.

 

 

 

 

 

 

7

7

7

2.

 

Field no. 

7

 starts to flash.

 

3.

 

By pressing 

+

 or 

 select from among three timer options:

 

-

 timer mode for the entire week (in field no. 

7

 the numbers from 1 to 7 flash),

 

-

 timer mode of operation for the period between Monday and Friday and from Saturday to 

Sunday (in field no. 

7

 the numbers 1 to 5 flash ),

 

-

 timer mode of operation for each individual day (in field no. 

7

 number 1 flashes).

 

4.

 

Confirm the setting by pressing the   symbol.

 

 

17

5.

 

Field 

17

 starts to flash.

 

6.

 

By pressing 

+

 or 

 set the time of the first time point t1.

 

7.

 

Confirm the setting by pressing the   symbol.

 

Содержание TC100ZW

Страница 1: ...INSTRUCTIONS FOR USE EN TC 100 120 ZW R TCM 200 ZE6GW ...

Страница 2: ...2 ...

Страница 3: ...safety valve so the outlet opening should be set to atmospheric pressure The outlet of the safety valve should be installed facing downwards and in a non freezing area To ensure proper functioning of the safety valve the user should perform regular controls to remove limescale and make sure the safety valve is not blocked Do not install a stop valve between the heat pump and the safety valve becau...

Страница 4: ... not use the appliance in a manner not compliant with the instructions The appliance is not intended for industrial use and use in premises with corrosive and explosive substances The manufacturer shall not be responsible for injuries resulting from inappropriate installation and inappropriate use that is not in accordance with the instructions for assembly and use The instructions for use are a c...

Страница 5: ...f the heat pump mm FLOOR STANDING VERSION Fig 2b Connection and installation dimensions of the heat pump mm A B C D E F TC100ZW 1342 490 100 100 G 1 2 TC120ZW 1497 645 100 100 G 1 2 TC120ZWR 1497 645 100 100 G 1 2 G 3 4 A B E F G HV CV TV TCM200ZE6GW 25 130 880 1240 1835 G3 4 G3 4 G3 4 ...

Страница 6: ... source inlets Heat losses are greater in a room with cold air To prevent condensation it is recommended to insulate the pipes connected to the source If the temperature of the source is lower than 12 C or higher than 40 C the electric heater will activate to heat the domestic water The electric heater will also activate if the flow rate of the source is lower than 120 l h The heat pump will opera...

Страница 7: ... be dismounted from the wall for service interventions Make sure to take measures to prevent the transfer of noise and vibrations through walls where this would be disturbing bedrooms rooms intended for resting A radiator can be connected only to the TC ZWR model Fig 4a Minimum requirements for the installation of HP FLOOR STANDING VERSION Before setting up the appliance screw in the enclosed adju...

Страница 8: ...ve The outlet pipe which is mounted under the safety valve must be directed downwards in a place with a temperature above freezing If the installation does not allow draining of the water from the safety valve into the drains dripping can be avoided by installing an expansion vessel onto the heat pump inlet pipe The volume of the expansion vessel must be ca 3 of the hot water tank volume After con...

Страница 9: ...ETWORK Connecting the heat pump to the power supply network must take place in accordance with the standards for electric appliances To comply with the national installation regulations an all poles disconnect switch must be installed between the heat pump and the power supply network Fig 8 Electrical circuit diagram WALL MOUNTED VERSION Before connecting to the power supply network install a powe...

Страница 10: ... Features and displays depend on the models Fig 11 Control display 4 3 2 1 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 LEGEND 1 Indication overview of errors access to the user menu 2 Signalisation of the operation of the heater Signalisation of the reserve mode 3 Signalisation of the operation of the compressor 4 Activation and setting of the VACATION programme 5 Display of quantity of hot water 6...

Страница 11: ...gure 11 Pressing anywhere on the saving mode display shows the main display Setup of features of the heat pump is only possible on the main display 1 Some parameters and features are set up in the user menu You can enter the user menu by holding for 3 s the field no 1 for setting the parameters and features see next chapters Group of parameters Parameter Description 01 Anti legionella programme 01...

Страница 12: ...sabled and the source temperature is outside the range of operation of the heat pump water in the water tank will not be heated Parameter group starts to flash By pressing field or select the number of the group of parameters 01 Confirm the setting by pressing the symbol Parameter number starts to flash The current parameter value is displayed By pressing field or select the number of the paramete...

Страница 13: ...r set the hour Confirm the setting by pressing the symbol The minutes segment starts to flash By pressing or set the minutes Confirm the setting by pressing the symbol The day of the week starts to flash field no 7 By pressing or set the day of the week 1 Monday 7 Sunday Confirm the setting by pressing the symbol 7 The illuminated number in field no 7 shows the number of the day of the week 1 Mond...

Страница 14: ...mperature Factory setting of the temperature is 55 C Store the setting by pressing the symbol The set temperature should meet the actual needs Recommended temperature settings are between 45 and 55 C Higher temperatures are not recommended as they reduce the efficiency COP and extend the time of heating thereby increasing the number of operating hours 1 To enter the user menu hold for 3 s field no...

Страница 15: ...he setting by pressing the symbol Exit the user menu by pressing field no 1 moves you one step back or wait for the unit to exit the menu automatically after a while 1 To enter the user menu hold for 3 s field no 1 By pressing field no 1 again you can move one step back thus exiting the user menu The parameter group starts to flash By pressing or select the number of the parameter group 01 Confirm...

Страница 16: ...the setting by pressing the symbol The parameter number starts to flash By pressing or select the number of the parameter 01 Confirm the setting by pressing the symbol 1 Parameter value starts to flash By pressing or you can set the frequency number of days of start up of the anti legionella programme or turn off the anti legionella programme OFF Store the setting by pressing the symbol Exit the u...

Страница 17: ... The TURBO feature can be switched off manually by pressing field no 6 briefly main display In case the heater is disabled parameter 01 09 the TURBO feature is not enabled 6 Briefly press field no 6 12 Field no 12 starts to flash By pressing or set the temperature of the HOT feature Store the setting by pressing the symbol 6 While the feature is on field no 6 is illuminated When the set temperatur...

Страница 18: ...e saving mode touch the display to see the number of remaining days After the set number of days has elapsed the heat pump resumes the previously set mode of operation and illumination of field no 4 stops The VACATION feature can be switched off manually by pressing field no 4 briefly main display In case the heater is disabled parameter 01 09 minimum temperature is maintained only by the heat pum...

Страница 19: ...g or select whether you want to complete the setting or set the next time point t2 t3 t4 YES NO If you select NO the setting of the selected segment will be finished If you select YES set the other time points as per the above procedure from step 5 to 13 max 4 13 Confirm the setting by pressing the symbol 14 To set the next time interval Saturday Sunday repeat the steps 5 to 13 14 By pressing or s...

Страница 20: ...diator heating after a major consumption of hot water from the water tank e g after someone has taken a shower for 3 hours factory default parameter 01 10 The set features of heating domestic water always have priority before the radiator heating feature 11 Briefly press field no 11 Field no 12 starts to flash By pressing or set the time of operation of the radiator heating feature Up to 30 minute...

Страница 21: ...the radiator heating feature Shortly press field 11 Field 12 starts to flash By pressing field or set to OFF Confirm the setting by pressing the symbol 1 To enter the user menu hold for 3 s field no 1 By pressing field no 1 again you can move one step back thus exiting the user menu The parameter group starts to flash By pressing or select the number of the parameter group 01 Confirm the setting b...

Страница 22: ... to flash By pressing field or set the time of operation of the radiator heating feature Up to 30 minutes you can set the time in 5 min increments and above 30 minutes you can set the time in 10 minute increments After maximum time setting the word ON appears on the display indicating constant heating of the radiator until manual switch off Confirm the setting by pressing the symbol 11 During the ...

Страница 23: ...f the week in field no 7 number 1 flashes 7 Confirm the setting by pressing the symbol 17 8 Field no 17 starts to flash 9 By pressing or set the first time point t1 10 Confirm the setting by pressing the symbol 11 Field no 12 starts to flash 12 By pressing field or set the activation ON or deactivation OFF of radiator heating at the first time point 13 Confirm the setting by pressing the symbol 12...

Страница 24: ... of the radiator heating feature d EXTERNAL CONTROL OF THE RADIATOR HEATING FEATURE ECH FEATURE In this case the RADIATOR HEATING feature is controlled by external signal e g room thermostat manual activation deactivation with an external switch etc The set features of heating domestic water always have priority before the radiator heating feature 1 Connect external control via contact 2 2 Connect...

Страница 25: ...menu by pressing field no 1 moves you one step back or wait for the unit to exit the menu automatically after a while By pressing field or select contact 2 Confirm the setting by pressing the symbol Exit the user menu by pressing field no 1 moves you one step back or wait for the unit to exit the menu automatically after a while When the feature is enabled and contact 2 2 is made external signal f...

Страница 26: ...old for 3 s field no 1 By pressing field no 1 again you can move one step back thus exiting the user menu The parameter group starts to flash By pressing or select the number of the parameter group 01 Confirm the setting by pressing the symbol The parameter number starts to flash By pressing or select the number of the parameter 11 Confirm the setting by pressing the symbol Parameter value starts ...

Страница 27: ...g field or select contact 2 Confirm the setting by pressing the symbol By pressing or set the temperature that the heat pump must maintain when electric energy from the photovoltaic system is available contact 2 2 is connected The factory setting is 55 C Confirm the setting by pressing the symbol 1 By pressing or set the temperature that the heat pump must maintain when electric energy from the ph...

Страница 28: ...r wait for the unit to exit the menu automatically after a while By pressing field or select contact 2 Confirm the setting by pressing the symbol By pressing or set the temperature that the heat pump must maintain when the tariff is low contact 2 2 is connected The factory setting is 55 C Confirm the setting by pressing the symbol 1 By pressing or set the temperature that the heat pump must mainta...

Страница 29: ...eactivated by re entering the user menu where you set the feature to the OFF value 1 To enter the user menu hold 3 s field no 1 By pressing field no 1 again you can move by one step back on each step thus exiting the user menu Parameter group starts to flash By pressing or select parameter number 02 Confirm the setting by pressing the symbol Parameter number starts to flash By pressing or select p...

Страница 30: ...eater must be enabled parameter 01 09 Reserve mode of operation is a mode of operation using a heater used when an error is detected on the aggregate section In case of using the manual reserve mode of operation please contact the service provider When the feature is enabled and contact 2 2 is connected external start up the abbreviation ECHP is on The feature enables the heating of domestic water...

Страница 31: ...pressing field no 1 moves you one step back or wait for the unit to exit the menu automatically after a while When the manual reserve mode is switched on the symbol flashes on the display 4 Hold 4 s field no 4 12 In field no 12 the word LOC appears The main display is locked The symbol for power on off works normally The status of the heat pump is displayed as well active components features time ...

Страница 32: ...le water sensor error Temperature sensor fault Hot water volume display is disabled symbol flashing Call the authorised service The error message disappears automatically once the fault has been eliminated E05 Upper water sensor error Temperature sensor fault Hot water volume display is disabled symbol flashing Water heating switches off Call the authorised service The error message disappears aut...

Страница 33: ...eat source circulation pump fault Water heating by the heat pump system is switched off Electric heater is switched on Check the operation of the circulation pump Turn off the error message in the user menu Fault on the electromagnetic valve or closed stop valve on the heat source system if applicable Check the position and functioning of the valves if any on the heating source system Turn off the...

Страница 34: ...re is an error of the parameter see the table of errors If the display shows it means that the parameter has no errors 1 Confirm the selection of the parameter by pressing You can delete the parameter error by pressing the symbol You can exit the user menu by pressing field no 1 moves you one step back or wait for the unit to exit the menu automatically after a while ...

Страница 35: ...8 78 195 85 285 Anti corrosion protection of tank Enamelled MG Anode Insulation thickness mm 40 85 40 85 40 85 60 Degree of protection IP24 IP24 IP24 IP22 Max connected load W 2380 2380 2400 2400 Voltage 230 V 50 Hz Number and power of heating elements W 2 x 1000 Electricity protection A 16 Adjusted water temperature C 55 Maximum temperature HP el heater C 65 75 Legionella control programme C 70 T...

Страница 36: ...05 2020 826264 ...

Отзывы: