2X Ø 28

108

47.1

41.6

Ø 28

47.1

41.6

2X Ø 28

40

47.1

41.6

3X Ø 28

40

47.1

68

41.6

41.6

104.5

50.6

2X Ø 35

41.6

50.6

Ø 35

41.6

41.6

52.3

52.3

52.3

50.6

50.6

3X Ø 35

2X Ø 35

*all dimensions in mm

Enclosure Drilling Guide for .75" Conduit

Single Core

Dual Core

Single Core

Dual Core

Enclosure Drilling Guide for 1" Conduit

Содержание TS4-F

Страница 1: ...cting the TS4 R F output cables in series If disconnecting TS4 R F disconnect the TS4 R F output cables from the string before disconnecting the input cables from the PV module RSS transmitter must be...

Страница 2: ...ing on RSS Transmitter Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements RSS Transmitter Installation N N L L RSS Transmitter 1 2 3 RSS Core in...

Страница 3: ...TS4 F before powering on RSS Transmitter RSS Transmitter Wiring N N L L RSS Transmitter Homerun Only or through RSS Core AC Wires for Power Supply Max number of strings per RSS Core 10 Max string leng...

Страница 4: ...ivate keep alive signal and energize PV array Note Install TS4 F before powering on RSS Transmitter RSS Transmitter Grounding Warning nonmetallic enclosure does not provide bonding between conduit con...

Страница 5: ...de for placement Mount RSS Transmitter and power supply on DIN rail Connect DC leads from power supply 1 to transmitter 2 Connect RSS Core 3 and 4 to transmitter 3 4 1 2 N N L L 1 DIN Rail PSU 2 RSS T...

Страница 6: ...t wires to AC side of power supply Note Install TS4 F before powering on RSS Transmitter Homerun Homerun AC Wires for Power Supply Only or through RSS Core Max number of strings per RSS Core 10 Max st...

Страница 7: ...wires to DIN rail Ground all conduit connections Turn on AC power to Transmitter power supply to activate keep alive signal Note Install TS4 F before powering on RSS Transmitter Warning nonmetallic en...

Страница 8: ...6 3X 28 40 47 1 68 41 6 41 6 104 5 50 6 2X 35 41 6 50 6 35 41 6 41 6 52 3 52 3 52 3 50 6 50 6 3X 35 2X 35 all dimensions in mm Enclosure Drilling Guide for 75 Conduit Single Core Dual Core Single Core...

Страница 9: ...o Homeruns through RSS Core must be the same polarity all positive or all negative RSS Transmitter Power LED should be lit and Signal LED should be blinking during operation Verify that RSS Core wirin...