27
5.3 Technical data EXM 25
Norm
EN 60079-0 and EN 60079-11 also
EN 61010-1 and 61010-031
EC type examination certificate
DMT 03 ATEX E 013
II 2G Ex ib T6/T4 Gb and
I M2 Ex ib I Mb
Nominal measurement ranges
usable in electricity networks group Ex I up to
1(2) kV, Ex IIB and Ex IIC up to 690 V
Direct current 1 kV with EXM 72010
red LED up to 12 V, LCD 3 1/2-digit:
1, 10, 100, 1000 V (1610 V),
± 1,5% + 3 digit, resolution 0,001 ... 1 V
Alternating voltage 1 kV
with EXM 72010
red LED up to 12 V, LCD 3 1/2-digit, TRMS;
10, 100, 1000 V (1160 V)
± 1,5% + 3 digit up to 0 ... 100 Hz
± 5% + 5 digit up to 101 ... 500 Hz
resolution 0,01 ... 1 V
Direct current 2 kV with EXM 72011
red LED up to 12 V, LCD 3 1/2-digit:
1, 10, 100, 2000 V,
± 2,5% + 5 digit, resolution 0,001 ... 1 V
Alternating voltage 2 kV
with EXM 72011
red LED up to 12 V, LCD 3 1/2-digit, TRMS;
10, 100, 2000 V
± 2,5% + 5 digit up to 0 ... 100 Hz
± 5% + 5 digit up to 101 ... 500 Hz
resolution 0,01 ... 1 V
Input resistance
with EXM 72010
2 MΩ distributed to 4 resistances,
moulded into DATA-HOLD test prods
Input resistance
with EXM 72011
4 MΩ distributed to 8 resistances,
moulded into DATA-HOLD test prods
Continuity/resistance
green LED LCD 3 1/2-digit
200, 2000 Ω
20, 200, 2000 kΩ, 2 MΩ, 20 MΩ ± 1 % + 5 digit,
resolution 0,1 Ω ... 10 kΩ
Current
AC/DC 1000 mA, 2 A ± 1 % + 2 digit,
resolution 1 ... 10 mA
Current with clamp
AC/DC 100, 1000 A, ± 1,5 % + 2/3 digit,
resolution 0,1 ... 1 A
Frequency
200, 2000 Hz ± 1 % + 2 digit, resolution 0,1 ... 1 Hz
10 kHz ± 3 % + 2 digit, resolution 0,01 kHz
Temperature with measurement accessory
-80 ... +150° C ± 1,5 % + 3 digit, resolution 0,1° C
-80 ... +600° C ± 1,5 % + 2 digit, resolution 1° C
Further functions
automatic selection of measurement range,
indication of function, self-test, automatic switch-off