25
9. Technical data
Nominal voltage range: SPB 1000L-UB: 50 ... 1000 V AC/DC
Nominal frequency range:
DC/15 ... 2000 Hz
Measurement range:
SPB 1000L-UB: 24 ... 1000 V AC/DC
± 2,5 % + 5 D (> 50 V)
Input resistance
SPB 1000L-UB:
direct: 300-350
kΩ bei 1000 V
switched:
4 ... 7 kΩ
Ri
ELV
:
335 kΩ bei 50V
Ri
ELV
switched: 12 kΩ bei 50 V
Current peak value I
s
:
direct:
< 3,5 mA
swiched:
< 300 mA
(35 mA at 230 V - RCD-
resolution)
On-time:
at max nominal voltage
TRon 120 s
RToff max 240 s (recovery time)
Display:
high-impedance
direct reading:
red LED for voltage
green LED for self-test
LCD, backlit
pressed button
low-resistive:
additional display symbol for
connected load
Phase: capacitive,
tests possible with gloves
LCD „POL“ for phase unipolar
Polarity:
LCD voltage type - / ~
Continuity:
0 - 500 kΩ (rdY)
Power supply:
Voltage tests from the mains,
phase and self-tests from integrated
Longlife-Li-battery
> 10 years operating time for
normal daily use
Overvoltage category:
CAT IV 1000 V
Surge voltage strength: >12 kV (1,2/50 µs)
Test voltage:
6 kV
Operating temperatures: -15 ... + 45°
Casing:
unbreakable silicone rubber,
display cover made of
impact resistant polycarbonate
Protection category:
IP 65,
impact resistant polycarbonate
environments
Connecting line:
PUR sheathed cable, 1000 V, 1 m
Standards:
IEC 61243-3:2014 + Cor.: 2015
EN 61243-3:2014
DIN-EN 61243-3:2015-08
EMV requirements:
DIN-EN 61326
Dimensions/Weigth:
274 x 75 x 47 mm (Anzeigeteil)
385 g