Synergy Controller Technical Manual, Revision H
Page 159
14.1.3 Logging Commands
The logging system can be setup from the touch screen as described in the previous Logging Setup section
of this application note. In addition, the logging system can also be setup and adjusted remotely, or with
command file (.CFG), or a Bar Code Macro file. The command syntax for the Logging system is as follows:
Command
Function
Example
CLEARHIST
Clear’s the History Log File
= clearhist 1
COPYHISTTOFTP 1
Copies the log database to the file “history.txt” in the
Controller’s FTP directory.
= copyhisttoftp 1
File: history.txt
COPYHISTTOFTP 3
“name”
Copies the log database to the file “name.txt” in the
Controller’s FTP directory.
= copyhisttoftp 3 “test”
File: test.txt
COPYHISTTOFTP 7
“name”
Copies the log database to the file “name_MM-DD-
YYYY.txt” in the Controller’s FTP directory.
= copyhisttoftp 7 “test”
File: test_07-09-2009.txt
COPYHISTTOFTP 15
“name”
Copies the log to the file in the controller’s FTP
directory:
“name_MM-DD-YYYY_HH.MM.SS.txt
= copyhisttoftp 7 “test”
File: test_07-09-
2009_02.20.05.txt
LOGGING_ENABLED
Enables/Disables Interval logging
= LOGGING_ENABLED
1
LOGGING_INTERVAL
Sets the Logging Interval in seconds
= LOGGING_INTERVAL
1
LOG_FILE_SIZE
Sets the Log file size in M Bytes.
= LOG_FILE_SIZE 1.4
LOG_WHILE_OFF
Controls whether the controller continues to log when
the chamber is off
= LOG_WHILE_OFF 0
LOG_CHn_ACT
Controls whether the controller logs the Channel n
Actual (Process Variable)
= LOG_CH1_ACT 1
LOG_CHn_SP
Controls whether the controller logs the Channel n
Setpoint
= LOG_CH1_SP 1
LOG_DEVALMS_CHn
Controls whether the controller logs the Channel n
Deviation Alarms
= LOG_DEVALMS_CH1
1
LOG_CHn_HEAT
Controls whether the controller logs the Channel n
Heat output
= LOG_CH1_HEAT 1
LOG_CHn_COOL
Controls whether the controller logs the Channel n Cool
output
= LOG_CH1_COOL 1
LOG_CH1_HEAT_PB
Controls whether the controller logs the Channel n
Heat Proportional Band constant
= LOG_CH1_HEAT_PB
1
LOG_CH1_COOL_PB
Controls whether the controller logs the Channel n Cool
Proportional Band constant.
= LOG_CH1_COOL_PB
1
LOG_LOW_n
Controls whether the controller logs the nth Low Res
Analog Input.
= LOG_MACHINE1 0
LOG_UUTn
Controls whether the controller logs the nth UUT
Module.
= LOG_UUT1 0
LOG_HIGH_n
Controls whether the controller logs the nth High
Resolution Analog Input.
= LOG_HIGH_1 0
LOG_TCn
Controls whether the controller logs the nth
Thermocouple Input.
= LOG_TC1 1
LOG_TCnCJ
Controls whether the controller logs the nth
Thermocouple Cold Junction sensor.
= LOG_TC1CJ 0
LOG_OUTPUTS
Controls whether the controller logs the Outputs
= LOG_OUTPUTS 1
LOG_DIO_n
Controls whether the controller logs Digital Input n
= LOG_OUTPUTS
Содержание Synergy Compact
Страница 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Страница 71: ...Synergy Controller Technical Manual Revision H Page 71...
Страница 106: ...Synergy Controller Technical Manual Revision H Page 106...
Страница 123: ...Synergy Controller Technical Manual Revision H Page 123...
Страница 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Страница 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Страница 188: ...Synergy Controller Technical Manual Revision H Page 188...
Страница 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Страница 294: ...Synergy Controller Technical Manual Revision H Page 294...
Страница 312: ...Synergy Controller Technical Manual Revision H Page 312...
Страница 345: ...Synergy Controller Technical Manual Revision H Page 345...
Страница 346: ...Synergy Controller Technical Manual Revision H Page 346...