TIANJIN BAILI ERTONG MACHINERY IMT Series Скачать руководство пользователя страница 14

12 

Part III Additional Instruction for IMT-04

4Ex Explosion-proof product 

1. Summary 

IMT-04

4Ex explosion-proof intelligent product is produced on the basis of GB3836.1

General Requirement 

for the Equipment Used in Explosive Environment, Part I

and GB3836.2 

The Equipment Protected by 

Explosion-proof Enclosure “d” Used in Explosive Environment, Part II

. Meanwhile, this series have been tested, 

experimented and finally verified by the national verified explosion-proof organization and get Conformity 
Certificate of Explosion-Proof. 

IMT-04

4Ex is explosion-proof product

and explosion-proof grade: Ex         d II B        T4   Gb.

 

 

2. Notice for maintenance and usage 

2.1 Power must be cut off when actuator’s any cover is open. (Please see the warning plate: “Forbid to open the box 
cover when the power is on.”) 
2.2 Don’t hit the openness window. 
2.3 Keep the nameplate and warning plate being fixed on actuator and the words on them should be recognized. 
2.4 Don’t open the electric box cover outdoors in rainy day or windy day. 
2.5 The product’s explosion-proof cover cannot be knocked or scratched during maintenance or debugging. (Please 
refer to the attached diagram.) 
2.6 Apply anti-rust painting 204-1 after debugging or maintenance and before assembling. 
2.7 Please notify the company to change the broken explosion-proof elements. The products cannot be powered on 
until it is renewed with qualified element. 
2.8 Fasten the screws on the explosion-proof electric case and spring washer shall be kept well. After strong 
vibration, please make regular check to make sure whether it is reliable.   
2.9 O-ring shall be kept well, and if it is damaged or lost, please connect with the manufacturer to purchase a new 
one. 
2.10 The external grounding should be reliable. 

3. Wire outlet on wiring box 

There are three plugs on the wiring box. User shall screw out plug first and use appropriate outlet device which 

can be connected with matched thread.( This outlet device shall comply with GB3836.1<General Requirement for 
the Equipment Used in Explosive Environment, Part I>and GB3836.2 <The Equipment Protected by 
Explosion-proof Enclosure “d” Used in Explosive Environment, Part II>). Pay attention to enclosure protection to 
ensure its protection grade. Outlet device is offered by user.    Keep the unused outlet hole in factory setting.     

4. Wiring sequence 

4.1 Open “wiring box” and screw out plug. 
4.2 Choose appropriate outlet device according to the dimensions of cable and outlet thread. 
4.3 Screw in cable outlet device and seal it well to make sure its original protection grade. 
4.4 Use specialized electric tool to connect “lug plate” with cable’s cores. 
4.5 According to electric schematic diagram, connect each core with corresponding terminals. Lug plate shall be 
turned up. 
4.6 After making sure that wiring connecting on the terminal is right and reliable, please check whether the cable’s 
position is right. 
4.7 Close “wiring box case” and firmly screw its screws. 

Till now, wiring is finished. Adjust according to Part I in this operation manual. 

4. Others: after the entire actuator’s wiring job is finished, user can adjust the product according 
to Part I and Part II in this operation manual. 

 

    

Содержание IMT Series

Страница 1: ...sing this product SM 20 IMT Series Intelligent Multi turn Electric Valve Actuator IMT Explosion proof Series Intelligent Multi turn Electric Valve Actuator Operation Manual Tianjin Baili Ertong Machinery Co Ltd Former Tianjin No 2 General Machinery Plant ...

Страница 2: ... Local control 2 Operation instruction for actuator 3 Adjustment for electric actuator 4 Function of electric acutuator and parameter setup 5 Alarm information 6 Referenced control wire connection 7 Referenced circuit diagram Part III Additional Instruction for IMT 04 4Ex Explosion proof product 12 1 Summary 2 Notice for maintenance and usage 3 Wire outlet on wiring box 4 Wiring sequence 5 Other ...

Страница 3: ...pair Thus it owns a practical output rotation speed range 3 3 Output shaft driving hollow shaft it is the power output component of electric actuator Both jaw type and valve stem nut type can be provided The internal thread is usually processed by user The type of the output shaft is decided by user when ordering 3 4 Manual electric switching handwheel it is used to switch manual operation between...

Страница 4: ...em thread is left and the output shaft will rotate counterclockwise Gradually pull down actuator as valve stem meshes with stem nut actuator flange begins to touch valve s connection surface Screw bolt into the flange thread hole and keep the bolt firmly To keep stem nut firmly setting in output shaft user could use cutting tools to damage the meshing fringe between the upper part of output shaft ...

Страница 5: ...nding bolt is on actuator s main case Keep external grounding safe and sound 7 Notice 7 1 Forbid to hit local switch button and position indicator window glass 7 2 Fasten valve cover on the top of actuator or wire plug remove them for maintenance in case foreign material goes into 7 3 Forbid to open case or mount in hazardous weather outdoors 7 4 Cut off power supply before opening case cover 7 5 ...

Страница 6: ...ey Status button turns from Stop Local hereinafter referred to as OK key Esc Status button turns from Stop Remote hereinafter referred to as Esc key 2 3 3 Keys for operation button Down key operation button close valve hereinafter referred to as Down key key operation button open valve hereinafter referred to as key 2 4 LCD display The actuator is equipped with Lattice line image type LCD The dist...

Страница 7: ...sition Note 1 User can set up fully closed position first and then fully open position and vice versa Setup methods are the same 2 Encoder value 0 and 65535 respectively are the minimum value and maximum value The two overlaps While setting up open close limit it can go through this overlapped position But it shall make sure that the value in the whole limit shall be in the range of absolute encod...

Страница 8: ...s and press Ok If password is 0 directly go into the next menu otherwise user needs to input Basic password to go into next menu 4 1 1 Accept Valve close open Limit Put cursor here manually or electrically make the valve to be at fully closed fully open position Press Ok to save this position as fully closed fully open position This setup record will not be changed after factory reset 4 1 2 Deadba...

Страница 9: ...all alarm relay that is the contact MONI showed in the electric schematic diagram If CPU Error ROM Error RAM Error A D Error Lost Phase Lost Analog OP CL SIG ON MOT Over Thermal display and set up parameters this contact will close if off contact is needed please notify when making an order Besides press Ok to go into OUT6 sub menu to choose if that alarm includes Over Torque At Remote Factory set...

Страница 10: ...the range of 0 3kB 0 6kB 1 2kB 2 4kB 4 8kB 9 6kB 19 2kB 38 4kB press Ok to save d Parity Only applied for Modbus Setup for parity bit in the data which comes from Field Bus s control circuit Odd Even None can be chosen choose Ok to save e Bus ESD Action Only applied for Modbus the action which is made since electric actuator accepts BUS Control signal Choosing Disable then Bus ESD cannot be used C...

Страница 11: ...in the range of 0 100 c Open Direction Pulsate Journey while actuator functions Two Speed Timer Control the limit value in each intermittent operation period shall be in the range of 2 100 d Open Direction Stoppage Time while actuator applies Two Speed Timer Control in the open direction the time value in each intermittent operation period shall be in the range of 1 255s e Close Direction Start Po...

Страница 12: ...act Fully Open Closure Two Wire Control Disable Out2 S2 Contact Fully Closed Closure Two Speed Timer Control Disable Out3 S3 Contact Over Torque Open Closure Brake Time 0mS Out4 S4 Contact Over Torque Close Closure The Basic Feedback Password 0 Out5 R Contact Red knob at remote Closure Advanced Password 25 OUT6 MONI Contact Failure Alarm including over torque excluding remote 5 Alarm information R...

Страница 13: ... orders Connecting wires according to product attached wiring diagram 6 2 Analog in remote control 4 20mA While under the control of 4 20mA analog control short circuit 16 and 17 If it is under the control of switching value and analog control it needs to add a change over switch on 15 16 17 Maintain open close stop SO SC and SS are provided by user Inching open close SO and SC are provided by use...

Страница 14: ... kept well After strong vibration please make regular check to make sure whether it is reliable 2 9 O ring shall be kept well and if it is damaged or lost please connect with the manufacturer to purchase a new one 2 10 The external grounding should be reliable 3 Wire outlet on wiring box There are three plugs on the wiring box User shall screw out plug first and use appropriate outlet device which...

Страница 15: ...Explosion proof components table No Item Quantity No Item Quantity No Item Quantity 1 Body case 1 6 Torque switch box 1 11 Openness window 1 2 Input shaft 1 7 Torque switch shaft 1 12 Wiring box 1 3 Gear frame cover 1 8 Box cover 1 13 Wiring box s case 1 4 Explosion proof screw 4 9 Compressing ring 1 14 Terminal board 1 5 Torque switch box cover 1 10 O ring 1 ...

Страница 16: ...ection function in the above conditions 2 At the end of operation replace the cover When fastening the clamp nuts at wire inlet and outlet make sure that no adverse elements such as severe damp water and dust etc that could weaken protective performance left in the inner space 3 In the course of mounting covers make sure that rubber seal rings are not damaged and fasteners are securely screwed dow...

Отзывы: