9
under remote control. Choose “Disable” or “Open First” or “Close First”, and connect wires according to required
ways. Factory setting: Disable.
4.3.8 Calibrate 4mA For ACC.: if 4mA control current sent by user is different from calibration value of the
actuator, user can use this item to re-calibrate. After choosing this item, on the right side there is control current
value which is collected by actuator; at this time, user could send lower current signal, and press “Ok” to save the
collected current value when current is stable.
4.3.9Calibrate 20mA For ACC.: if 20mA control current sent by user is different from calibration value of the
actuator, user can use this item to re-calibrate. After choosing this item, on the right side there is control current
value which is collected by actuator; At this time, user could send higher current signal, and press “Ok” to save the
collected current value when current is stable.
4.3.10Brake Time: Setup range: 0-50ms. Factory setting: 0ms.
4.3.11Stop Moving Time Before Brake: Before “Brake Time”, stop for a while. Setup range: 150-250ms. Factory
setting: 150ms.
4.3.12 Two-Speed Timer Control:in order to save from water hammer effect or reduce the rate of pressure –change
in the pipe, it is required that reducing the speed during valve closing and opening. While choosing two-speed timer
control, it requires the actuator to do two speed action. If user chooses “Disable”, the actuator will do continuous
action; if user chooses “Enable”, it goes to the next menu(a-h).
a. Open Direction Start Position: in valve open direction, actuator sets up the start position of “Two-Speed Timer
Control” in the range of 0%~100%.
b. Open Direction End Position: in valve open direction, actuator sets up the end position of “Two-Speed Timer
Control” in the range of 0%~100%.
c. Open Direction Pulsate Journey: while actuator functions “Two-Speed Timer Control”, the limit value in each
intermittent operation period shall be in the range of 2%~100%.
d. Open Direction Stoppage Time: while actuator applies “Two-Speed Timer Control” in the open direction, the
time value in each intermittent operation period shall be in the range of 1-255s.
e. Close Direction Start Position: in valve close direction, actuator sets up the start position of “Two-Speed Timer
Control” in the range of 0%~100%.
f. Close Direction End Position: in valve close direction, actuator sets up the end position of “Two-Speed Timer
Control” in the range of 0%~100%.
g. Close Direction Pulsate Journey: while actuator applies “Two-Speed Timer Control” in closing direction, the
limit value in each intermittent period shall be in the range of 2%~100%.
h. Close Direction Stoppage Time: while actuator applies “Two-Speed Timer Control” in closing direction, the
time value in each intermittent period shall be in the range of 1~255s.
4.3.13
Senior Password Change: after choosing this item, on the right side there will be the previous setting
password which should be in the range of 0
~
255 and press “Ok” to save. Factory setting: 25.
4.3.14 Basic Password Inquires: After choosing this item, on the right side there will be the basic password.
4.3.15Feedback Password Inquires: After choosing this item, on the right side there will be password inquiry.
4.3.16Set The Default Value: this is used before factory delivery.
4.4Signal Inquires
4.4.1 Position of the Selector Knob: after choosing this item, on the right side there will be the position of “Status
Position of the Selector Knob
Stop / Local / Remote
Position Of The Operator Knob
None / Open / Close
Remote Open Signal Appear
No / Yes
Remote Close Signal Appear
No / Yes
Remote keep Signal Appear
No / Yes
Remote Auto Signal Appear
No / Yes
Remote ESD Signal Appear
No / Yes
Position Control Current
XXmA
Signal Inquires
Enter?