MEASURES, LOGIC STATES AND COUNTERS
51
NC020 - Manual - 05 - 2022
5 M E A S U R E S , L O G I C S T A T E S A N D C O U N T E R S
—
Measures
• RMS value of fundamental component of phase currents (
I
L1
,
I
L2
,
I
L3
)
• RMS value for phase currents
(
I
L1 RMS
,
I
L2 RMS
,
I
L3 RMS
)
• RMS value neutral current
(
I
N
)
• Displacement angle of neutral current
(
I
N PHI
)
• Displacement angle of calibrated neutral current
(
I
N PHI calib
)
• Fundamental component of calibrated neutral current (
I
N MOD calib
)
• Capacitor calculated peak voltages
(
V
1
,
V
2
,
V
3
)
• RMS value of fundamental component of calculated residual current (
I
EC
)
• Discharge timer
T
D
—
Circuit breaker
The CB and Trip Circuit Supervision states are provided
• Position
Open - Closed - Unknown
and the binary inputs state:
• IN1-52b
On/Off
• IN2-52a
On/Off
—
Counters
For every protective element and control function several counters are available; the partial coun-
ters can be cleared by the user.
Every partial counter is reset to zero when ten thousand count is passed.
All partial counters can be cleared by means a single command; for this purpose the
Reset coun-
ters
command must be issued available inside the
Reset
menu.
• Start I> element
On/Off
• Start I>> element
On/Off
• Start I>>> element
On/Off
• Start IE> element
On/Off
• Start IE>> element
On/Off
• Start IN>AL element
On/Off
• Start IN> element
On/Off
• Start IN>> element
On/Off
• Start U> element
On/Off
• Start U>> element
On/Off
• Start U>>> element
On/Off
• Start I<< element
On/Off
• Trip > element
On/Off
• Trip I>> element
On/Off
• Trip I>>> element
On/Off
• Trip IE> element
On/Off
• Trip IE>> element
On/Off
• Trip IN>AL element
On/Off
• Trip IN> element
On/Off
• Trip IN>> element
On/Off
• Trip U> element
On/Off
• Trip U>> element
On/Off
• Trip U>>> element
On/Off
• Trip I<< element
On/Off
—
Fault recording - SFR
Recording
[1]
is triggered by:
• Relay activation (OFF-ON)
• Element start or trip
Twenty faults are recorded into a circular FIFO (First In, First Out) buffer.
[2]
Following information are stored in every record (
Read \ Faults \ Info
menu):
• Fault counter (Faults stored)
[3]
F-number
• Fault cause
F-cause
• Date and time (S-Millisecond
• Phase currents (fundamental)
F-IL1 RMS, F-IL2 RMS, F-IL3 RMS
• Phase currents (RMS)
F-IL1, F-IL2, F-IL3
• Calculated residual current
F-IEC
• Compensated neutral current
F-INC
• Voltages
F-V1, F-V2, F-V3
• Date and time
F-Year
• Date and time
F-Month
• ...
The fault log may be erased by means of the command inside the
Read \ Faults \ Reset
menu
.
Note 1 Data concerning the twenty events are stored into non volatile memory; they are held in spite of power down
Note 2 Fault 0 is the newest event, while the Fault 19 is the oldest event
Note 3 Counter is updated at any new record; it may be cleared by means ThyVisor