FUNCTION CHARACTERISTICS
40
NC020 - Manual - 05 - 2022
Breaker failure (BF)
The elements (
I
>>,
I
>>>) can produce the Breaker Failure output if the
Trip I>>
and/or
Trip I>>>
outputs are set for
BF Enable.
The outputs are available inside the
Set \ Breaker failure
menu.
[1]
Cold load pickup
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Blocking
the
ICLP>>
and/or
ICLP>>>
param-
eters.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Changing
the
ICLP>>
and/or
ICLP>>
param-
eters, whereas the operating thresholds within the CLP may be adjusted inside the
Set \ 50/51 Funda-
mental \
I> Element, (I>> Element
)
\ I>> Definite (I>>> Definite)
or
I>> Inverse (I>>> Inverse)
menus.
For both operating modes the CLP Activation time parameters (
tCLP>>, tCLP>>>
) may be ad-
justed inside the
Set \ 50/51 Fundamental \
I>> Element, (I>>> Element
)
\ I>> Setpoint (I>>> Setpoint)
menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Fun_50-51-S2.ai
I
L1
I
L2
I
L3
t
I
>>
RES
T
0
RESET
t
I
>>
0
T
≥
1
≥
1
t
I
>>
def
t
I
>>
inv
t
I
>>
RES
Start I>>
Trip I>>
CB-State
ON
≡
Enable I>> overcurrent element
(Pickup within CLP)
(Pickup outside CLP)
&
T
0
t
CLP>>
ICLP>>Mode
I
CLP>>def
t
CLP>>
I
CLP>>inv
ON
≡
Enable
BF Enable
towards BF logic
I>> BF
&
Trip I>>
TR
IP
PIN
G
M
AT
RIX
(
LE
D+R
EL
AY
S)
I
>> Curve
0
T
A
B
C
A =“1”
A =“0 or OFF”
Output
t
CLP>>
I>> Enable
t
CLP>>
CB State
CB OPEN
CB CLOSED
CB OPEN
Output t
CLP
>>
t
0.1 s
HIGH THRESHOLD/
BLOCK
LOW THRESHOLD/
UNBLOCK
HIGH THRESHOLD/
BLOCK
A = ON - Change setting
B = OFF
C = ON - Element blocking
I>>TR-K
LED 1
I>>ST-L
I>>ST-K
I
>>
inv
I
L1
≥
I
>>
def
I
L1
≥
I
>>
inv
I
L1
≥
I
CLP
>>
(def/inv)
I
>>
def
Fundamental phase overcurrent (50/51) - I>> element logic diagram