APPENDIX
203
NA20 - Manual - 04 - 2022
74CT Enable
74CT Enable
OFF | ON
74CT Threshold
S<
0.10 ... 0.95 step = 0.01
74CT Overcurrent threshold
State
OFF | ON
Pickup value
In
0.10 ... 1.00 step = 0.01
S< Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
S< Logical block
S<BLK1
OFF | ON
S< Trip relays
S<TR-K
K1 | K2 | K3 | K4 | K5 | K6 |
S< Trip LEDs
S<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Remote tripping
Remote tripping relays
RemTrip-K
K1 | K2 | K3 | K4 | K5 | K6 |
Remote tripping LEDs
RemTrip-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Pilot wire diagnostic
BLOUT1 Diagnostic pulses period
PulseBLOUT1
OFF | 100ms | 1s | 5s | 10s | 60s | 120s
BLIN1 Diagnostic pulses control time interval
PulseBLIN1
OFF | 100ms | 1s | 5s | 10s | 60s | 120s
Not received pulses at BLIN signalling relays
PulseBLIN-K
K1 | K2 | K3 | K4 | K5 | K6 |
Not received pulses at BLIN signalling LEDs
PulseBLIN-L
START | TRIP | L1 | L2 | L3 | L4 | L5 |
Demand measures
Fixed demand period
tFIX
min
1 ... 60 step = 1
Rolling demand period
tROL
min
1 ... 60 step = 1
Number of cycles for rolling on demand
N.ROL
1 ... 24 step = 1
TimeZone
Time Zone
(UTC+0) - Greenwich Dublin Edinburgh Lisbon
London | (UTC+1) - Amsterdam Berlin Bern Rome
Stockholm Vienna | (UTC+2) - Athens Bucharest
Cairo Instanbul | (UTC+3) - Addis Abeba Baghdad
Moscow Nairobi S.Petersburg | (UTC+4) - Baku
Dubai Mauritius Samara Tbilisi | (UTC+5) - Karachi
Maldives Tashkent Yekaterinburg | (UTC+6)
- Almaty Dhaka Omsk | (UTC-1) - Azores CapoVerde
| (UTC-2) - Mid Atlantic | (UTC-3) - Brasilia Bueno-
sAires Georgetown Greenland | (UTC-4) - Atlantic-
Time LaPaz Manuas Santiago | (UTC-5) - Eastern-
Time (US Canada) Indiana | (UTC-6) - CentralTime
(US Canada) CentralAmerica
Daylight saving time
Disable | Europe | Russia | Jordan | Syria | Egypt
Oscillography
Readings
State
Initialization | Upload from serial flash | Reset
| Wait | Store to serial flash | Start recording |
Acquire | Trigger | Stopped | Fail | Off
Serial flash state
OFF | Upload from serial flash | Store to serial flash
| Reset serial flash
Serial flash overrun
OFF | ON
Records
0 ... 0 step = 0
Buffer storage
%
0 ... 0 step = 0
Trigger Setup
Pre-trigger time
s
0.05 ... 1.00 step = 0.01
Post-trigger time
s
0.05 ... 60.00 step = 0.05
Element pickup trigger
ON | OFF
Trigger from outputs
K1 | K2 | K3 | K4 | K5 | K6 |
Binary input trigger
ON | OFF
Содержание NA20