APPENDIX
178
NA20 - Manual - 04 - 2022
IN3 matching
Reset LEDs | Set profile | Fault trigger | Block2 IPh/
IE | Block2 IPh | Block2 IE | Block1 | TCS1 | TCS2 |
Trip ProtExt | Reset counters | Reset CB Monitor |
52a | 52b | Open CB | Close CB | Preset DTheta |
Remote trip | Reset on demand measures | None
Binary input IN4
IN4
Logic
Active-ON | Active-OFF
IN4 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN4 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN4 matching
Reset LEDs | Set profile | Fault trigger | Block2 IPh/
IE | Block2 IPh | Block2 IE | Block1 | TCS1 | TCS2 |
Trip ProtExt | Reset counters | Reset CB Monitor |
52a | 52b | Open CB | Close CB | Preset DTheta |
Remote trip | Reset on demand measures | None
Binary input IN5
IN5
Logic
Active-ON | Active-OFF
IN5 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN5 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN5 matching
Reset LEDs | Set profile | Fault trigger | Block2 IPh/
IE | Block2 IPh | Block2 IE | Block1 | TCS1 | TCS2 |
Trip ProtExt | Reset counters | Reset CB Monitor |
52a | 52b | Open CB | Close CB | Preset DTheta |
Remote trip | Reset on demand measures | None
Binary input IN6
Relays
K1
Logic
De-energized | Energized
Operation MODE
No-latched | Pulse | Latched
Minimum pulse width
ms
0 ... 500 step = 5
K2
Logic
De-energized | Energized
Operation MODE
No-latched | Pulse | Latched
Minimum pulse width
ms
0 ... 500 step = 5
K3
Logic
De-energized | Energized
Operation MODE
No-latched | Pulse | Latched
Minimum pulse width
ms
0 ... 500 step = 5
K4
Logic
De-energized | Energized
Operation MODE
No-latched | Pulse | Latched
Minimum pulse width
ms
0 ... 500 step = 5
K5
LEDs
START
Type
No-latched | Latched
TRIP
Type
No-latched | Latched
L1