background image

DTB

27

DTB000\08
4-95

Testing through laboratory tests

The DTB relay being of the draw-out type, it can

be extracted from the counterbase without putting
the system out of service and then taken to a
laboratory for a thorough testing of the operation
thresholds and times of the various functions.

In the meantime however the system is left

unprotected unless an identical spare DTB relay is
available for substitution.

Note that extracting the relay from the counter-

base does not cause anomalies in the amperometric
circuits, owing to the automatic short circuit device
contained in the counterbase. The circuits
connected with the final contacts remain open,
and therefore the following cases occur:

- if the DTB relay is of the type with final relays

normally de-energized and its make contacts are
being used, there is no consequence whatsoever;

- if, on the contrary, the break contacts are

being used, intervention of the protection is
simulated;

- if the DTB relay is of the type with final relays

normally energized, the intervention  of the
protection is simulated.

For the exact test sequence, see the paragraph

Testing procedures.

Testing by current injection

If the electric panel is fitted with test sockets, it

is possible to feed them with the amperometric test
signals and check the state of the final contacts of
the DTB relay. When this procedure is used the
system remains unprotected for the length of the
test. The testing procedures are described in the
next paragraph.

Testing procedures

The testing procedures are the same both for

laboratory tests and tests carried out by means of
the test sockets on the controlgear.

A relay-testing equipment which can feed two

current signals with adjustable amplitude and phase
and can measure the operation times, or an equiva-
lent device, must be used; it is however possible to
carry out the tests with a single-phase signal
source, but in conditions differing from the actual
situation of the system.

The connection scheme indicated in fig.11 is of

use for the testing of all the protection functions,
except for the maximum residual current protection,
for which see under.

Verifica mediante prove in laboratorio

Essendo il relè DTB di tipo estraibile, è possibile

asportarlo dalla sua controbase senza per questo
mettere fuori servizio l'impianto e portarlo in labo-
ratorio per eseguire un controllo accurato delle
soglie e dei tempi d'intervento delle varie funzioni.

Nel frattempo tuttavia l'impianto rimane privo di

protezione, a meno che si disponga di un identico
relè DTB di riserva da sostituire a quello in prova.

L'estrazione del relè dalla sua controbase non

provoca alcuna anomalia nei circuiti amperometri-
ci, grazie al dispositivo di corto circuito automatico
contenuto nella controbase. Viceversa i circuiti
facenti capo ai contatti finali rimangono aperti, per
cui si presentano i seguenti casi:

- se il relè DTB è del tipo con relè finali normal-

mente diseccitati e ne sono impiegati i contatti di
lavoro, non si presenta alcuna conseguenza;

- se contrariamente si utilizzano i contatti di

riposo, viene simulato l'intervento della protezio-
ne;

- se il relè DTB è del tipo con relè finali normal-

mente eccitati, viene simulato l'intervento della
protezione.

Per le modalità di esecuzione delle prove di

verifica, si rimanda al successivo paragrafo Ese-
cuzione delle verifiche.

Verifica mediante iniezione di corrente

Se il quadro elettrico è provvisto di prese di

prova, è possibile applicare ad esse i segnali
amperometrici di prova e rilevare lo stato dei
contatti finali del relè DTB. Con questa procedura
tuttavia, l'impianto rimane privo di protezione per
tutto il tempo necessario all'esecuzione della pro-
va. Le modalità di esecuzione delle prove di veri-
fica sono riportate al paragrafo seguente.

Esecuzione delle verifiche

Le modalità di esecuzione delle verifiche sono

le stesse sia nel caso in cui si eseguano le prove
in laboratorio, sia nel caso in cui si eseguano le
prove dell'impianto mediante le prese di prova
previste nel quadro.

È necessario disporre di un'apparecchiatura

prova-relè (o della strumentazione equivalente) in
grado di fornire due segnali amperometrici regolabili
in ampiezza e fase e di misurare i tempi d'interven-
to; è possibile tuttavia eseguire le prove anche con
una sorgente di segnale monofase, ma in condi-
zioni difformi dalla effettiva situazione impiantistica.

Lo schema di collegamento riportato in fig. 11

serve per la verifica di tutte le funzioni di protezio-
ne, ad eccezione della protezione di massima
corrente residua, per la quale si veda più avanti.

Содержание DTB 49-50

Страница 1: ...DTB 1 DTB000 08 4 95 DTB Relè di protezione termica Thermal protection relay MANUALED ISTRUZIONE INSTRUCTIONMANUAL 49 50 ...

Страница 2: ...UNZIONA MENTO 3 PRINCIPIO DI FUNZIONAMENTO 4 INSTALLAZIONE 5 TARATURA 6 MESSA IN SERVIZIO 7 PROCEDURE DI PROVA 0 CONTENTS 1 DESCRIPTION 2 FUNCTION CHARACTERISTICS 3 FUNCTION PRINCIPLE 4 INSTALLATION 5 SETTING 6 COMMISSIONING 7 TESTING PROCEDURES 3 4 12 14 19 24 26 ...

Страница 3: ...se guenti dati di targa marchio di fabbrica tipo del relè campo d impiego della tensione ausiliaria corrente nominale frequenza nominale DESCRIPTION General The thermal protection relay type DTB as well as all the other types of the line DENOVA SYSTEM is composed by a withdrawable unit and a counterbase unit The last one performs the function of electrical connection and mechanical frame while all...

Страница 4: ... the corresponding symbols are explained below IN Relay input nominal current coincident with the secondary nominal current of the CT s IB Base current it represents the nominal current of the protected machine referred to the the nominal current of the CT s IP Current drawn by the machine before the overload condition with reference to the hot operation curves of the thermal function ΘB Base over...

Страница 5: ...the operation of the following protection functions 49 thermal protection 50 overcurrent protection Caratteristiche generali d intervento Le caratteristiche d intervento del relè DTB sono rappresentate in modo qualitativo nel diagramma di fig 1 Esso rappresenta l intervento delle se guenti funzioni di protezione 49 protezione termica 50 protezione di massima corrente ...

Страница 6: ... funzione termica per sua natura tiene realmente conto del riscaldamento della macchina anche in occasione di correnti variabili nel tempo e non equilibrate Operation characteristics of the thermal function The thermal function reproduces the heating of the protected machine caused by the currents flowing in the windings then it is a dependent time function The operation characteristics presented ...

Страница 7: ...ione ter mica corrispondenti a diversi stati termici prece denti valore della costante termica τ pari a 2 min Operation characteristics of the thermal function corresponding to different previous thermal condi tions value of the thermal constant τ equal to 2 min ...

Страница 8: ...ne ter mica corrispondenti a diversi stati termici prece denti valore della costante termica τ pari a 5 min Operation characteristics of the thermal function corresponding to different previous thermal condi tions value of the thermal constant τ equal to 5 min ...

Страница 9: ...one ter mica corrispondenti a diversi stati termici prece denti valore della costante termica τ pari a 10 min Operation characteristics of the thermal function corresponding to different previous thermal condi tions value of the thermal constant τ equal to 10 min ...

Страница 10: ...e ter mica corrispondenti a diversi stati termici prece denti valore della costante termica τ pari a 20 min Operation characteristics of the thermal function corresponding to different previous thermal condi tions value of the thermal constant τ equal to 20 min ...

Страница 11: ...one ter mica corrispondenti a diversi stati termici prece denti valore della costante termica τ pari a 40 min Operation characteristics of the thermal function corresponding to different previous thermal condi tions value of the thermal constant τ equal to 40 min ...

Страница 12: ... della macchina pro tetta mediante la predisposizione della costante termica di riscaldamento τ Tale valore deve esse re dichiarato dal costruttore della macchina È inoltre possibile mediante l interruttore ON OFF escludere o azzerare l immagine termica ciò risul ta utile durante le operazioni di verifica e di messa in esercizio FUNCTION PRINCIPLE The DTB thermal protection carries out its various...

Страница 13: ...continuità delle bobine dei relè finali Il rilevamento di un anomalia è evidenziato dallo spegnimento del LED verde di presenza tensione e può essere telesegnalato mediante un apposito relè finale comandato dal circuito di controllo diagnostico Overcurrent protection I 50 This protection operates instantaneously against the serious damages caused by severe thermal and mechanical stress due to shor...

Страница 14: ...gombro in profondità indicato a disegno deve essere opportunamente maggiorato della quantità occorrente per il passaggio dei cablaggi INSTALLATION Mechanical mounting The DTB relay is available in various case styles depending on the required mounting Flush mounting The fixed counterbase fitted with special fastening brackets is mounted on the front of electric controlgear previously drilled as in...

Страница 15: ...n opportuna tolleran za tra i diversi apparecchi e di una appropriata distanza in senso verticale per il passaggio dei cablaggi Projecting mounting The fixed counterbase is fastened with screws onto the panel as indicated in fig 9 In case of side by side mounting of several relays the minimun fixing distance is determined by the dimensions of the terminal board indicated in the overall dimensions ...

Страница 16: ...L ingombro in profondità indicato a disegno deve essere opportunamente maggiorato della quantità occorrente per il passaggio dei cablaggi Rack mounting The relay is fitted in a 19 rack supplied by us whose dimensions are indicated in fig 10 The DAV type rack is designed to house a number of DENOVA series relays corresponding to a total of 10 base modules The DTB relay has a width corresponding to ...

Страница 17: ...ro e si diseccita al mancare della tensione ausiliaria o comunque in caso di guasto dei circuiti interni della protezione se il relè prescelto è del tipo a sicurezza positiva i relè finali si mantengono normalmente in Electric connections When making the electric connections refer to the connection diagram on the side of the relay It must be noted that the DTB relay can be supplied in different ve...

Страница 18: ...posta in corrispondenza della maniglia superiore La calotta frontale può essere sigillata in modo da evitare manomissioni delle tarature o attivazio ne del ciclo di prova mediante il pulsante TEST da parte di persone non autorizzate Inoltre se non si asporta preventivamente la calotta frontale non è possibile svitare le viti di bloccaggio ed estrarre il relè di protezione dalla sua controbase quan...

Страница 19: ...base IB dati corrente nominale della macchina INM 170 A corrente nominale dei trasformatori di corrente INTP INTS 200 A 5 A corrente nominale DTB IN 5 A taratura IB INM INTP IN 170 A 200 A IN 0 85 IN 0 84 IN 0 5 Σ 0 04 0 1 0 2 IN SETTING The front settings must be made accurately to achieve optimal functioning of the DTB type thermal protection relay The following characteristics of the protected ...

Страница 20: ...tante termica si ottiene quindi moltiplicando il valore relativo alla carat teristca del DTB presa in considerazione per il rapporto tra il tempo massimo di sovraccarico e il tempo d intervento rilevato sulla caratteristica del DTB Thermal protection Θ Θ Θ Θ Θ 49 The operation threshold of the thermal protection has a fixed value 1 1IB corresponding to an over temperature of 1 2 ΘΒ that is 1 2 tim...

Страница 21: ...itched to ON during normal running Esempio dati corrente di sovraccarico IMS 850 A tempo massimo di permanenza in sovraccari co tMS 9 s taratura IB già definito al paragrafo preceden te 0 84 IN calcolo corrente di base primaria IB 0 84 200A 168 A corrente di sovraccarico espressa in rapporto alla corrente di base IMS 850A 168A IB 5 06 IB la curva d intervento relativa alla costante termica τ 2 min...

Страница 22: ... primaria IB 0 84 200 A 168 A sovratemperatura di allarme ΘAL IAL IB 2 180A 168A 2 ΘB 1 15 ΘB taratura ΘAL 1 15 ΘB 0 8 Σ 0 05 0 1 0 2 ΘB The ΘA thermal alarm function has an operation threshold quantified in terms of the Θ overtempe rature and is referred to the ΘB overtemperature corresponding to the absorption of the base current IB It can therefore be set at a value lower than the Θ operation t...

Страница 23: ...po di risposta dei circuiti è inferiore a 0 04 s Esempio dati corrente d intervento desiderata I 7 IB taratura I 2 Σ 5 IB Overcurrent protection I 50 This protection function does not feature inten tional delay circuits and its operation time corre sponding to the response time of the circuits is therefore lower than 0 04 s An example data desired operation current I 7 IB setting I 2 Σ 5 IB ...

Страница 24: ...di corrente errata impostazione della taratura Più in dettaglio alcune ulteriori possibili cause d intervento delle singole funzioni di protezione sono descritte nel seguito COMMISSIONING After the installation has been completed and the adjustment of the settings carried out according to the instructions given in the preceding chapters the start up can be proceeded on As the auxiliary voltage is ...

Страница 25: ...ntl function can be caused by wrong adjustment of setting IB wrong adjustment of setting I Intervento protezione termica Θ Θ Θ Θ Θ 49 L intervento della funzione termica può essere dovuta a errato collegamento dei circuiti amperometrici per cui il relè rileva una componente di sequenza inversa non realmente presente errata impostazione della taratura IB errata impostazione della taratura τ eventua...

Страница 26: ...verifica risulta automaticamente estesa a tutta la catena di protezione Ciò però comporta l arresto del processo produttivo interessato a meno che il segnale di sgancio dell interruttore sia bloccato temporaneamente mediante apposito dispositivo esterno al relè di protezione DTB TESTING PROCEDURES The DTB thermal protection relay as all protection relays operates only under exceptional circumstanc...

Страница 27: ...relè DTB di tipo estraibile è possibile asportarlo dalla sua controbase senza per questo mettere fuori servizio l impianto e portarlo in labo ratorio per eseguire un controllo accurato delle soglie e dei tempi d intervento delle varie funzioni Nel frattempo tuttavia l impianto rimane privo di protezione a meno che si disponga di un identico relè DTB di riserva da sostituire a quello in prova L est...

Страница 28: ...ry supply test This test must be carried out by feeding an auxiliary voltage of the same kind alternate or continuous available in the controlgear with two different values corresponding to the minimum and the maximum of the tolerance range Follow this procedure when applying the auxiliary voltage it must be instantly observed that the green LED marked ON and the first LED of the thermal image ind...

Отзывы: