Installation

•  Locate the charger in a suitable dry area in the vehicle or caravan. 

•  Secure the charger using the mounting tabs on the unit.

•  Connect the input terminal on the rear of the charger using suitable cable  
 

to the main starting battery of the vehicle (see specification table on  

 

next page), it is recommended to place a circuit breaker (30A minimum,  

 

not supplied) in the main positive lead as close as possible to the starting  

 battery.

•  Connect the auxiliary battery to the output terminal of the charger, ensure  
 

the correct size cable is used to prevent any voltage drop (see specification  

 

table on next page).

•  It is recommended to place a circuit breaker (30A minimum, not supplied) in  
 

the auxiliary positive lead as close as possible to the auxiliary battery.

•  Secure the negative wire to the common negative terminal and secure to a  
 

metal (unmoving) part of the vehicle, it is preferable to connect this directly  

 

to the negative terminal of both batteries.

•   The TDR02020 will work with even the newest computer controlled 

alternators, for installation into vehicles with variable voltage alternators, 
negative must be connected to vehicle chassis. 

•  If connecting a solar panel connect the positive from the panel to the  
 

solar input terminal and the negative of the panel to the negative terminal.

•  There is no need for an external regulator the DC-DC has a built in  
 

MPPT solar regulator.

•  Check all connections are tight.

Once correctly installed the TDR02020 is a simple set and forget dual battery 
solution.

Start the vehicle and let it idle, the charger will recognise that there is charge being 
applied to the main starting battery. Once the main starting battery has reached 
13.1V the charger will automatically begin to charge.

The charger will continue to operate even after the vehicle has been switched off, 
however once the main start battery falls below a loaded voltage of 12.2V the 
charger will automatically shut down.  

The TDR02020 will prioritise the vehicle input over the solar input so while the 
battery voltage is above 12.2V it will continue to charge, however once the main 
battery has reached a loaded voltage of 12.2V and the charger switches off it will 
look for a solar input. 

If the solar input is above 13V then the green LED on the display will illuminate to 
indicate that the TDR02020 is now using the solar input to charge the auxiliary 
battery.

Once the solar input goes under 12V the charger will turn off completely.

INSTALLATION

Содержание TDR02020

Страница 1: ...is specialty 12 Volt battery charger is a sophisticated multi stage charger utilising fully automatic computerised control designed to charge most 12 Volt Gel Lead Acid and Calcium batteries It is rec...

Страница 2: ...s 4 Important Safety Warnings 5 Installation 6 Specifications 7 Integrated LED Diagram 8 Wiring Diagram 9 8 Stage Charging Mode 10 Solar Charging Mode 11 Warranty Terms Conditions Copyright 2017 GPC A...

Страница 3: ...nd minimises temperature equating to longer battery life Unit will automatically change charge rate mapping for GEL AGM and standard Lead Acid Internal charger temperature monitoring and power output...

Страница 4: ...battery charger is not intended for outdoor operation Do not expose it to moisture or extreme weather conditions 8 If skin or clothing comes in contact with battery acid flush the affected area immed...

Страница 5: ...vehicle chassis If connecting a solar panel connect the positive from the panel to the solar input terminal and the negative of the panel to the negative terminal There is no need for an external reg...

Страница 6: ...ses over 17V the Thunder DC DC will shut off reset will be needed MIN AND MAXIMUM CHARGING VOLTAGES 13 1V 15 2V stops charging when alternator or vehicle battery below 12 2V SOLAR INPUT VOLTAGE RANGE...

Страница 7: ...e of charge and indicator lights These functions include Solar green LED Reverse polarity orange LED including alarm Faulty battery red LED NOTE The percentage display shows the stage at what the DC D...

Страница 8: ...mmended Not Supplied As your auxiliary battery charges its state of charge is reflected by the Thunder logo illuminating in 10 increments A percentage charge is also shown in green This percentage cha...

Страница 9: ...ter one minute If voltage is over 12 6V the Thunder DC DC goes to stage 6 Note If battery is determined to be faulty the Thunder DC DC will stop charge 6 Stage 6 Boost Stage Voltage up to max of 15 2V...

Страница 10: ...switches to stage 2 2 Stage 2 Overpressure Pulse Charging When the battery voltage is lower than 14 5V charger pulses for one sec on and one sec off This will occur for two hours or until 14 5V averag...

Страница 11: ...ir or replace the unit This warranty does not apply to failure or damage to a Thunder product caused by incorrect or faulty fitment accidental or intentional damage failure of other products incorrect...

Страница 12: ...12 GPC Asia Pacific Pty Ltd ABN 97 097 993 283 51 57 Qantas Drive Brisbane Airport QLD 4007 AUSTRALIA thunderauto com au thunderauto co nz...

Отзывы: