19
8.
Remove the plug from the Manifold Pressure Test Point and install a manometer. Check for
gas leak on the connection.
9.
Turn ON the isolation gas valve, and open two (2) burners and set at “High Flame”.
10.
Check the pressure reading in the manometer. The manometer pressure reading should be
according to the pressure of the gas type used. Refer also to the Gas Specification Table on
page 5 of this manual for the Manifold Pressure for the specific gas type.
11.
Turn ON the pilot and main burners and check the flame for any abnormalities.
12.
Adjust the burner’s air shutter, as necessary, to eliminate yellow flame and lifting of flames,
and other burner flame abnormalities.
13.
Refit the pilot covers, radiants, cast grates, front panel cover, and knobs.
14.
After converting the unit, ensure to post the new label with the appropriate gas type used.
Fill-up the Gas Conversion Label and attach it to the unit beside the rating label.
15.
Before leaving the premises, ensure to check the functions of the following:
a.
Pilot burner ignition
b.
Pilot burner flame. It should stay lit.
c.
Main burners, “HIGH” flame and “LOW” flame.
d.
Check for gas leaks on the connections.
CAUTION!
To avoid property damage, personal injury or death, all gas joints and connections disturbed
during servicing or gas conversion must be check for gas leaks. Check with a soap and water
solution (bubble test) or any gas leak detecting solution. Do not use naked flame to check for
gas leaks.
Manifold Pressure
Test Point