It is prohibited to use any other device as part of grounding electric circuit
•
The area of the conduction between grounding wire and device’s frame should be no less
than 25mm
2
.
2.2.4 Frame Grounding
All the machine frames should be connected with protective copper strip. The grounding wire should
be as short as possible and avoid circling. The area of the conduction between grounding wire and
grounding strip should be no less than 25mm
2
.
2.2.5 Device Grounding
Connecting the device’s grounding rod to frame’s grounding pole with copper wire.
2.3 Wire’s Connection
•
Connecting Power Cord
•
User can insert one end into power supply socket, while insert the other end to AC power.
•
Connecting Grounding Wire
•
When the device solely connects to protective ground, it should not share the same ground
with other devices. If the device shares grounding, the resistance should be smaller than
1Ω.
Caution:
Before connecting power cord to Universal Satellite and ATSC IRD, user should set the
power switch to “OFF”
.
2.4 Signal Cable Connection
The signal connections include the connection of input signal cable and the connection of output
signal cable. The details are as follows: