DFT-6300 Battery Load Bank Instruction Manual
15
3.3 Cell-Data-Case connection
12V Cell-Data-Case wiring mode
(with independent power cable) as follows:
The power cord connection method of each case: the power supply negative (P-) is connected to the same position
as the Case line 0. The power supply is positive (P+) in the same position as the Case line 2 or 3. It is
recommended to connect the power cable first and then the voltage monitoring cable.
The first Case: Line 0 is connected to the 1st battery negative (total negative), Line 1 is connected to the 1st
battery positive, and Line 2 is connected to the 2nd battery positive... Line 12 section 12 battery cathode;
The second case: Line 0 is connected to the 13th battery negative (total negative), Line 1 is connected to the 13th
battery positive, and Line 2 is connected to the 14th battery positive... Line 12 section 24 battery positive pole;
The wiring harness of the 2V Cell-Data-Case
does not have a separate power cord. The wiring is as follows:
The first Case: Line 0 is connected to the 1st battery negative (total negative), Line 1 is connected to the 1st
battery positive, and Line 2 is connected to the 2nd battery positive... Line 12 section 12 battery cathode;