IS---0797

IS---274FT(1)

January 2010

Page 1 of 4

Operating Instructions

274FT(1)

Feed--Thru/Grounding Device

CONTENTS: Feed--thru body complete with mounting hardware, Lubricant, Operating Instructions.

The feed thru provides interconnected apparatus interfaces for Elastimold 25kV class (15.2kV phase--to--ground and 26.3kV

phase--to--phase) loadbreak connections and can be used for the following functions:

A.

A junction point.

B.

A grounding point.

To use the feed--thru as a junction point, follow steps 1 to 5 and 6A and 7A.
To use the feed--thru as a grounding point, follow steps 1 to 5 and 6B to 9B.
A yellow band provides indication of full elbow seating and also provides vents for improved switching performance. This

product is identified by a yellow ID washer attached to the eyebolt.

DANGER

All apparatus must be de--energized during installation

or removal of part(s) except for test point caps and

indicators that can be installed and operated

energized.
After installation loadbreak products can be operated

energized per operating instructions. All deadbreak

connectors must be de--energized before operating.
All apparatus must be installed and operated in

accordance with individual user, local, and national

work rules. These instructions do not attempt to

provide for every possible contingency.
Do not touch or move energized products.

“Loadbreak connectors must be operated with a full

insulated “hotstick” type live--line tool.” Consult the

company’s safe work practices for the required

live--line tool length.

Excess distortion of the assembled product may result

in its failure.
Inspect parts for damage, rating and compatibility with

mating parts.
This product should be installed only by competent

personnel trained in good safety practices involving

high voltage electrical equipment. These instructions

are not intended as a substitute for adequate training or

experience in such safety practices.
Failure to follow these instructions will result in

damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping

cover(s), remove this shipping cover(s) and replace

with the appropriate HV insulated cap(s) or

connector(s) before submerging or energizing the

circuit.

FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.

IMPORTANT

1. Check contents of package to ensure they are complete

and undamaged.

2. Check all components to ensure proper fit with cable

and/or mating products.

3. Read entire installation instructions before starting.

4. Have all required tools at hand and maintain cleanliness

throughout the procedure.

STEP 1

Grounding-- Insert ground lead into the grounding lug

provided on the mounting hardware and tighten lug. Ground

lead should be No. 14 copper wire or equivalent. Connect

the opposite end of the lead to ground, leaving enough slack

to operate with a hotstick.

IS---0797

IS---274FT(1)

January 2010

Printed in U.S.A.

8155 T&B Boulevard, Memphis, Tennessee 38125

(800) 888--0211 Fax: (800) 888--0690

Ground Lug

No. 14 Copper Wire

To Ground

Yellow Seating Indicator

and Vent Ring

Yellow ID Washer