IS---0797
IS---274FT(1)
January 2010
Page 1 of 4
Operating Instructions
274FT(1)
Feed--Thru/Grounding Device
CONTENTS: Feed--thru body complete with mounting hardware, Lubricant, Operating Instructions.
The feed thru provides interconnected apparatus interfaces for Elastimold 25kV class (15.2kV phase--to--ground and 26.3kV
phase--to--phase) loadbreak connections and can be used for the following functions:
A.
A junction point.
B.
A grounding point.
To use the feed--thru as a junction point, follow steps 1 to 5 and 6A and 7A.
To use the feed--thru as a grounding point, follow steps 1 to 5 and 6B to 9B.
A yellow band provides indication of full elbow seating and also provides vents for improved switching performance. This
product is identified by a yellow ID washer attached to the eyebolt.
DANGER
All apparatus must be de--energized during installation
or removal of part(s) except for test point caps and
indicators that can be installed and operated
energized.
After installation loadbreak products can be operated
energized per operating instructions. All deadbreak
connectors must be de--energized before operating.
All apparatus must be installed and operated in
accordance with individual user, local, and national
work rules. These instructions do not attempt to
provide for every possible contingency.
Do not touch or move energized products.
“Loadbreak connectors must be operated with a full
insulated “hotstick” type live--line tool.” Consult the
company’s safe work practices for the required
live--line tool length.
Excess distortion of the assembled product may result
in its failure.
Inspect parts for damage, rating and compatibility with
mating parts.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in
damage to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace
with the appropriate HV insulated cap(s) or
connector(s) before submerging or energizing the
circuit.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
STEP 1
Grounding-- Insert ground lead into the grounding lug
provided on the mounting hardware and tighten lug. Ground
lead should be No. 14 copper wire or equivalent. Connect
the opposite end of the lead to ground, leaving enough slack
to operate with a hotstick.
IS---0797
IS---274FT(1)
January 2010
Printed in U.S.A.
8155 T&B Boulevard, Memphis, Tennessee 38125
(800) 888--0211 Fax: (800) 888--0690
Ground Lug
No. 14 Copper Wire
To Ground
Yellow Seating Indicator
and Vent Ring
Yellow ID Washer