background image

The 68P-DV-KIT will work with either conduit 

arrangement.

FIGURE 6

Mounting Ring

Grounding Lug

FIGURE 7

Mounting Ring

"THROUGH" power wires

Top of Divider 1/2" below 
top surface of Floor Box.

Install Duplex 
to power 
wires

FIGURE 8

Face Plate

Trim Clean  
with Utlily Knife

Duplex Cover

FIGURE 9

Secure (4) screws through faceplate, 
cover and into mounting ring.

Faceplate

Duplex Cover
(Discard if using GFI)

Apply Caulk or Sealant 
under Flange on Wood 
or Tile Floors

Connect Data Cable to 
Data Jacks

Data Plates

(See NOTE Below)

Cover Assembly

Snap Keystone Data Jacks 
in bottom of Faceplate

*NOTE:

 Keystone Data Plates come standard on the            

68P-DV-KIT. Other style Data Plates are available from T&B and 
and can be ordered separately.

6)

  Re-insert divider assembly into floor box. Pull power wires 

up through center of floor box. Pull non-used or (through) 
wires over ramp and into conduit openings on opposite side 
of box. Install duplex receptacle device onto mounting ring 
per device instructions and make electrical connections in 
accordance with national and local electrical codes. A 
grounding lug is provided on the underside of mounting 
ring. Terminate grounding wire to grounding lug when 
required by device installation instructions or national or 
local codes (see Figure 6 and 7).

7)

 

Verify divider assembly is aligned with conduit direction. 
The divider assembly can be rotated a few degrees in either 
direction to align with conduit openings. Align mounting ring 
vertical walls with divider vertical walls and push (install) 
mounting ring onto top of the floor box (see Figure 7).

8)

 

On wood or tile floors, apply caulk or sealant to the 
underside of carpet flange to block water entry (see Figure 9).

9)

 

Place cover assembly onto top of mounting ring. Pull data 
cable up through side openings and install to data jacks per 
manufacturer’s instructions (see Figure 9).

10)

 

Trim duplex cover from face plate using utility knife. Place 
duplex cover on top of duplex receptacle before installing 
face plate (see Figures 8 and 9).

11)

 

Snap keystone jacks into data plates (see Figure 9). 

12)

 

Assemble faceplate onto cover using four No. 8 x 3/4" long 
flat head screws (see Figure 9).

© 2008 Thomas & Betts. All Rights Reserved.

TA02485  C    page 2 of 2

WARRANTY:

 Thomas & Betts sells this product with the 

understanding that the user will perform all necessary tests to 
determine the suitability of this product for the user's intended 
application.  Thomas & Betts warrants that this product will be free 
from defects in materials and workmanship for a period of two (2) 
years following the date of purchase. Upon prompt notification of any 
warranted defect, Thomas & Betts will, at its option, repair or replace 
the defective product or refund the purchase price.  Proof of 
purchase is required. Misuse or unauthorized modification of the 
product voids all warranties.

Limitations and Exclusions:

  THE ABOVE WARRANTY IS THE 

SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN 
LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED, 
INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF 
MERCHANTABILITY OR FITNESS FOR A PARTICULAR 
PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY 
FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST 
OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER 
NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR 
ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL 
DAMAGES.

Thomas & Betts Corporation

Memphis, Tennessee

www.tnb.com

Отзывы: