Concrete
1/8"
Finished Floor
Floor Box
FIGURE 1
Cut top of Floor Box or Floor
box Extension (not shown) off
1/8" below finished floor
FIGURE 2
Data Cables
1" Conduit
3/4" Conduits
"Through"
Data Cable
FIGURE 3A
FIGURE 3B
Assemble Divider
(Do Not Glue)
Divider
Assembly
68P-EXT-DIV
(Optional,
Sold Separately)
FIGURE 4
Mark edges
of Divider at top of Floor Box
Marked edge
See Figure 4
Cut
Measure 1/2" then cut Divider
at next molded score line
Use a Razor Knife
(Utility Knife) to score
long groove on side of
divider or divider
extension (not shown).
Bend back and forth
to remove cut portion.
FIGURE 5
Installation Instructions for 68P Dual Voltage Kit
Catalog Numbers
68P-DV-KIT-BRS & 68P-DV-KIT-AL
WARNING
BE SURE POWER IS OFF!
PRODUCT DESCRIPTION
•
The 68P-DV-KIT is a floor box cover and divider kit to be used in the
Thomas & Betts 68P nonmetallic round floor box. It is designed to
accommodate one standard duplex or GFCI style receptacle and
four data/communication jacks. The standard configuration is for
keystone jacks. Other data plates are available for other jack
configurations.
•
The Kit includes the cover, face plate with data plates, mounting ring
and dual voltage divider. It does not include the receptacle or
data/communication jacks.
•
The cover is solid metal construction and features a snap-shut lid.
INSTALLATION INSTRUCTIONS
1)
Verify that 68P round floor box or 68P-EXT floor box extension has
been prepared for installing the 68P-DV-KIT. The top surface of the
floor box or 6” extension will need to be cut 1/8" below finished
floor height as shown in Figure 1(below). Finished floor may be
carpet, wood, vinyl or ceramic tile.
2)
Pull data cable up through opening in box. Pass "through" cable
to other side of box and through conduit opening(s), see Figure 2.
NOTE:
Data cable may enter the box from either the two 1"
conduit openings (as shown), or it may enter through the four 3/4”
conduit openings.
The 68P-DV-KIT will work with either conduit
The 68P-DV-KIT will work with either conduit
arrangement.
arrangement.
3)
Assemble divider halves, see Figure 3A. Do not glue! Lower divider
assembly into 68P floor box so that data cables exit the floor box
on outer sides of the divider assembly. Verify the divider ramp
covers any data cable that runs through the box. Make sure
divider assembly is resting on the bottom of the 68P floor box,
see Figure 4.
NOTE:
When using the 68P-EXT floor box extension, the
68P-DVD-EXT Voltage Divider Extension (not included) is required.
Snap (do not glue) the divider extensions onto top of the Divider
Assembly provided, see Figure 3B.
4)
Make a mark on the divider sides where they meet the top of the
cut floor box, see Figure 4.
5)
Remove the divider halves or divider extensions from the floor
box. Make a second mark at 1/2” below or the next molded score
line on the divider or divider extensions. Score (cut) the divider or
divider extensions at the second mark and remove the cut portion,
see Figure 5.
NOTE:
When reinserted in the floor box, the top of the divider
assembly should be 1/2” to 9/16” from the top of the 68P floor
box, see Figure 7.
TA02485 C Page 1 of 2