Please read the following 

instructions carefully in order to 
make sure that the heater is used 
properly and does not cause mal-
function.

1. Purpose

Hiton HP 30, HP 45, HP 80, HP 130 
and HP 250 heaters are designed for 
heating small and medium-size ro-
oms and surfaces in buildings without 
central heating and water system. 
Heat in form of hot air is transported 
to the room either directly by the head 
or by means of flues.
Heaters may be used in rooms where 
other oil or gas heaters functioning in 
ON-OFF mode are operating. Decision 
about which heater should be used is 
made by the user.

2. Construction of the heater

Heaters consist of the following units: 
heat exchanger made of stainless 
steel, radial fan, control panel with 
security thermostat, outlet decom-
pression head with side dampers and 
external casing painted with powder 
coating. On the inside of the casing 
are sheet zinc screens with deflectors 
which provide additional isolation 
against heat emission on the heater 
panels.

It is recommended to use 

burners which are approved by the 
producer. If a different burner is 
used the product may not comply 
with safety requirements of the 
European Directives.

Fig. 1 

Heater construction

3. Storage conditions

Oil heater should be stored in the 
following conditions:

Temperature

-20 - +85°C

Relative humidity

5-85%

Pressure 

800-
1200hPa

Lack of dust/ pollu-
tion 

V

Environment free of 
chemical pollutants

V

                                                                                                                                                      
                                   

4. Conditions for use

Oil heater should be operated in the 
following conditions:

Temperature

0-30°C

Relative humidity

5-85%

Environmental impact 
protection

IP20

Appropriate ventilation of 
the heated area

V

5. Safety measures and gene-

ral recommendations

Heater should be installed, placed 
and used in accordance with binding 
regulations. Rules that should be 
adhered to when operating the heater 
are as follows:
• recommendations included in this 

instruction should be meticulously 
followed

• heater may not be installed in pla-

ces where there is a risk of fire or 
explosion

• combustible materials should be 

placed away from the heater (mini-
mum 3 meters)

• there should be appropriate ven-

tilation in room(s) heated with oil 
heater to assure good functioning of 
the burner

• burner should be placed close to a 

flue or a flue pass and appropriate 
power distribution board. Burner 
should be protected against chil-
dren and animals.

Burner should be powered off after 
use.
Do not exceed maximum heating 
performance.
Assure appropriate air circulation in 
both sucking in and blowing out the 
air.

6. Installation

Installation and activation of the 

heater should be carried out by an 
authorised/certified fitter nomina-
ted by the seller

•  When installing the heater, all local 

regulations are to be complied with, 
including regulations referring to 
national and European norms.

•  Place the heater on level, concrete 

surface.

• Level the heater.
• The heater should be placed away 

from combustible materials.

• The heater must be connected to 

exhaust fumes channel according 
with binding norms, including the 
following recommendations:

•  Combustion outlet flue should 

be as short as possible facing 
upwards.

•  It should not have any sharp 

curves or bends and its diameter 
should under no circumstances 
be reduced compared to the size 
of the vent cap.

•  Each heater should be connected 

to a separate combustion flue.

•  Draught may not be lower than 

the minimum draught required 
as per technical specifications.

•  Flue has to be at least 1 meter 

long.

•  Burner should be fitted to the he-

ater by means of attached screws.

•  Attached insulating gasket should 

be placed between the burner and 
the heater.

•  Burner should be fitted to the fuel 

tank according to the ‘Burner In-
struction of Use’.

•  Installation powering the heater 

must be grounded and equipped 
with electro-magnetic thermal 
release. -1,5 mm2 diameter po-
wer cable must be connected to 
switchboard equipped with breaker 
switch. -Thermostat or digital timer 
should be connected to heater con-
trol panel.

7. Description of use  

and operation

Switching on

Mode switch located on the control 
panel should be set at HEATING or 
COOLING. In the COOLING position, 
the fan is immediately switched on. 
Setting threshold temperature or 

ENG

Содержание HP 130

Страница 1: ...0 HP 45 HP 80 HP 130 HP 180 i HP 250 INSTRUCTION FOR USE AND MAINTENANCE OIL HEATERS HP 30 HP 45 HP 80 HP 130 HP 180 i HP 250 BEDIENUNGS UND WARTUNGSANLEITUNG Heiz l Lufterhitzer HP 30 HP 45 HP 80 HP...

Страница 2: ...onditions for use 5 Safety measures and general recom mendations 6 Installation 7 Description of use and operation 8 Control panel 9 Failures and remedies 10 Technical specification 11 Manufacturer EC...

Страница 3: ...HITON heat your home not the planet 3...

Страница 4: ...4...

Страница 5: ...HITON heat your home not the planet 5 0 N 1 2 3 4 5 6 7 L L L 1 2 3 1 2 3 4 5 M 3 FUSE 250V 16A T 1 L1 3 L2 5 L3 A1 95 96 97 98 A2 2 T1 4 T2 6 T3 L P1...

Страница 6: ...czenia termostat LIMIT 90 C kontrolka awarii wentylatora sygnalizacja zasilania elektrycznego prze cznik GRZANIE CH ODZENIE gniazdo bezpiecznikowe regulator temperatury progowej Oznaczenia os ona wylo...

Страница 7: ...ylatora przegrzanie p yta czo owa zawora termostat zewn trzny opcja palnik termostat wentylatora termostat bezp stycznik wy cznik termiczny Oznaczenia kolor w przewod w to zielony br zowy szary czarny...

Страница 8: ...ej instrukcji nie wolno instalowa nagrzewnicy w miejscach zagro onych niebez piecze stwem po aru lub eksplozji materia y palne powinny znajdowa si w bezpiecznej odleg o ci od nagrzewnicy min 3 metry w...

Страница 9: ...progow przy kt rej b dzie za cza si wentylator Zbyt niska temperatura za czania mo e spowodowa samoczynne wygaszanie paleniska Zaleca si aby temperatur progow ustawi w zakresie 30 45 C Nastawy doko nu...

Страница 10: ...b przytkane otwory w perforowanych cianach Wentylator nie uruchamia si lub urucha mia si z op nieniem 1 Brak zasilania elektrycznego 2 Uszkodzony termostat 3 Spalona lub przerwane uzwojenie silnika el...

Страница 11: ......

Страница 12: ...er Side CH cover Terms Fuse base Threshold temperature regulator LIMIT thermostat 90 C Fan failure indicator light Electric power signal Switch HEATING CO OLING Terms Outlet CH cover Deflector Deflect...

Страница 13: ...ure of the fan overheating front plate latch External thermostat option burner Thermostatof the fan Safety thermostat contactor thermal switch Cables colour markings Yellow green brown grey black blue...

Страница 14: ...xplosion combustible materials should be placed away from the heater mini mum 3 meters there should be appropriate ven tilation in room s heated with oil heater to assure good functioning of the burne...

Страница 15: ...ers should be checked To do this it is recommended to turn on the heater and see if the fan starts to work after about 1 3 minutes following the activation of the burner If the heater operates for abo...

Страница 16: ......

Страница 17: ...t Grenztemperaturregler Thermostat LIMIT 90 C Kontrollleuchte f r Ventilato r Fehler Signalisierungslampe Net zversorgung Wahlschalter K HLEN HEIZEN Sicherungssteckplatz Vezeichnungs Schutzblech Abluf...

Страница 18: ...entilator fehler berhitzen Vorderbedienungspaneel Magnetanker Au enthermostat Brenner Ventilator thermostat Sicherheitstermostat Sch tz Thermoschalter Kabel Farbmarkierungen Yellow green braun grau sc...

Страница 19: ...en Be triebsanleitung sind streng einzu halten Der Erhitzer darf nicht auf den Stel len montiert werden die der Explo sions oder Brandgefahr ausgesetzt sind Brennbare Stoffe sollen in einem sicheren A...

Страница 20: ...Aufleuchten der sich am vorderen Bedienungspaneel des Steuerger ts befindlichen Kontroll leuchte St rung Ventilator signa lisiert Neustart des Lufterhitzers ist nur dann m glich nachdem die St rungsu...

Страница 21: ...lager geklemmt 1 Sicherungen berpr fen 2 Elektrische Kontakte berpr fen 3 Thermostat berpr fen und falls erforderlich einstellen oder auswechseln 4 Ventilatormotor auswechseln Ventilator wird in Vibra...

Страница 22: ......

Страница 23: ...24 LIMIT 90 1 2 RU...

Страница 24: ...HITON heat your home not the planet 25 3 400 50 RU...

Страница 25: ...26 RU 1 HITON HP 30 45 80 130 250 ON OFF 2 1 3 20 85 C 5 85 800 1200hPa V V 4 0 30 C 5 85 IP20 V 5 3 6 1...

Страница 26: ...HITON heat your home not the planet 27 RU 1 5 2 7 30 45 80 130 250 90 9 1 30 45 1 3 20 35 40 LIMIT 90 0...

Страница 27: ...28 RU 9 1 2 1 2 LIMIT 1 1 2 3 1 1 RM 5 2 1 1 1 2 3 4 5 1 2 3 4 1 2 1 2 1 1 1 31 41 43 30 a 8 2...

Страница 28: ......

Отзывы: