13.1 Verify system operation
To commission the system, verify the following conditions are met
:
All fans are working.
Fans operate at Low, Medium and High speeds.
There is no excessive mechanical noise coming from the fans.
When heating is selected, the air stream from the discharge grille warms up across the whole
length of the air curtain.
When set to manual with fans set to high speed, heating increases as higher heat is selected.
Warm air reaches across the doorway with door open or closed.
Ecopower Remote Control operates correctly in both manual and auto modes.
13.2 Instruct customer and hand over
Before leaving site, hand over the installation to the customer/end user or their representative.
Explain
that any person operating the air curtain must be given supervision and instruction by the person
responsible for their safety, concerning the safe use of the unit and to understand any hazards involved.
Children and those with reduced physical, sensory or mental capabilities should not operate the
air curtain.
Recommend
that the doorway should be closed whenever possible but that during times of high
pedestrian use it will become an ‘open doorway’. The air curtain then serves an essential purpose by
saving energy and providing comfort to occupants.
Explain
that the inlet grilles must be cleaned regularly and the unit serviced at schedule intervals
– see Section 16: Service & Maintenance.
Complete the following once commissioning is completed:
Installer signature
Customer signature
Installer name
Customer name
Installer company
Customer company
Date
Date
13 Commissioning the System
.
14 Sign Off
.
NOTE:
Leave these instructions with the customer/end user or their representative!!
NOTE:
To restrict heat output for standard C2-1000E and C2-1500E air curtains, disconnect second stage
heating by removing push-on terminals K1, K4 and K7 from Ecopower PCB. To convert three phase
electric heated models to single phase please visit the Thermoscreens wwebsite.