DIP switches on the air curtain Ecopower PCB (see Fig 18) provide
the following optional features, as explained below:
Fan heat interlock
Disable fan run-on
Thermostat master (for master/slave installations)
Weather compensation heat control (Summer/Winter)
Door switch control
Feature
DIP setting
Default
Notes
Fan heat interlock
Allows fan speed to govern heat
output on electric heated units.
DIP 1
ON
Heat output is
governed by fan
speed.
This feature is only used with
electric heated air curtains to
limit very high air
temperatures
Disable fan run-on
The 2 minute fan run-on after
switch off is enabled or disabled
on electric heated air curtains.
DIP 2
OFF
Fan run-on at
medium speed
enabled.
Must only be used for water
heated or ambient air
curtains. Each air curtain must
have DIP2 set to ON for no
fan run-on.
Thermostat master
For master/slave installations.
Only the air sensor in the
thermostat master air curtain is
used to measure air temperature.
DIP 3
OFF
Air curtains in
master/slave
systems all act
independently.
Air sensor thermistors in all
slave air curtains will be
ignored.
We
ather compensation
control or Door switch control
Simple weather compensation
control to save heating energy.
or
Door switch control.
DIP 4
OFF
IN1 Weather
compensation
ON
IN1 Door switch
See Section 9.1 Remote
Switch Contacts IN0 and
IN1 for details
Weather compensation
control is the same as
Summer/Winter control
11 System Configuration
.
11.1 Optional features
WARNING:
Isolate and disconnect air curtain from the power source before making any changes.
ON
1
2
3
4
ON
1
2
3
4
ON
1
2
3
4
NOTE:
A range of advanced factory fitted and plug-in control options are available from Thermoscreens to
enhance the performance of the Ecopower PCB controller inside the air curtain. These include
advanced weather compensation control using a heating curve, outlet air temperature control,
ECObus
®
Modbus BMS control, modulating heater outputs and EEPROMs for non-standard control
strategies. Visit the Thermoscreens website for details.
NOTE:
Black rectangle is moveable head of DIP switch.
ON
1
2
3
4
Set DIP 3 to ON in the air curtain
that will be the master unit.
Stops some units blowing
cold air and others blowing
warm air in master/slave
systems on larger doorways.
If low or medium fan speed is
selected, a lower heat output
results. High heat operates only on
high fan speed.
Set DIP1 to OFF if unit is
water heated or ambient.