OPTIONS 

  

 

WATERSIDE ECONOMISER 

 
A waterside economizer can be used where the unit’s entering water temperature is between 45 and 
55° F. The economizer coil will act as the first stage of cooling if the water is cold enough. If the 
economizer is unable to maintain the zone or supply air temperature set point, one stage of DX 
cooling will also come on to meet the required set point. (Refer to sequence of operation for more 
details) The waterside economizer is internal to the unit. All economizer control valves, piping 
between the economizer and the condensers, and all the wiring is factory installed. All piping and 
control valves are located within the unit enclosure. 
The waterside economizer will take advantage of cooling tower water to pre-cool the entering air to 
aid in mechanical cooling process, or if the water temperature is low enough, the waterside 
economizer will provide total cooling.

 

 

3-WAY DIVERTING VALVE (ECONOMIZER VALVE) 

 
The 3-way diverting valve is used when a unit is equipped with a waterside economizer coil. The 
threaded ball valve is designed to provide 2-position control of hot or cold water systems. This 
valve comes combined with an electronic actuator that stops automatically when the motor reaches 
its end position. The actuator is mounted directly to the valve-operating shaft with a universal v-
bolt clamp assembly. Control of the valve is on/off. The direction of the rotation is reversible. The 
3-way diverting valve diverts water directly to the economizer coil upon a signal from the entering 
water thermostat. The water then goes to the condensers and out the unit. If the economizer 
function is not enabled the 3-way diverting valve will then direct the water directly to the 
condensers.  

 

 

ECONOMIZER CONTROL 

 
The economizer mode is activated when water temperature is lower than water set point and that 
the discharge air is under the 68°F set point on economizer mode (adjustable).  
 
 
 
 
 
 
 
 
 
 
 
 

Содержание KHP-720

Страница 1: ...t on its side may damage internal parts and displace oil from the compressor s crankcase STORAGE If job site storage is necessary place the unit in a clean warm dry area Follow instructions under Hand...

Страница 2: ...pumps must be properly grounded as per instructions on the unit wiring diagram LOCATION OF SUPPLY RETURN CONNECTIONS CONDENSATE DRAINAGE Vertical Units Ensure that the plastic drain tube is connected...

Страница 3: ...wrench on the hexagonal surface to tighten connections Never use a wrench on the hose or sleeve that crimps the fitting into the hose Do not over tighten connections Turn in the mating threads by hand...

Страница 4: ...mperature Avoid false heat or cold sources from sunlight open doors or window drafts supply air outlets fireplaces ovens etc NOTE Electronic thermostat must be use to operate this unit HIGH LOW PRESSU...

Страница 5: ...ERIODIC MAINTENANCE 1 Air filters should be inspected monthly If filters are dirty or air flow is blocked replace filters 2 The coils should also be inspected monthly for excess moisture or icing If t...

Страница 6: ...the belts you must lower the nuts under the tilt base and then lower the top nuts until the proper tension is reached Raise lower nuts to re tighten tilt base To relieve tension in the belts start by...

Страница 7: ...that control the flow of liquid refrigerant entering the direct expansion DX evaporator by maintaining a constant superheat of the refrigerant vapor at the outlet of the evaporator KHP only NOTE This...

Страница 8: ...de economizer will provide total cooling 3 WAY DIVERTING VALVE ECONOMIZER VALVE The 3 way diverting valve is used when a unit is equipped with a waterside economizer coil The threaded ball valve is de...

Страница 9: ...9...

Страница 10: ...10...

Отзывы: