background image

 

7

units only) 

 
Each refrigeration circuit consists of an adjustable direct acting water regulating valve. The valve is 
a pressure actuated modulating valve that is suitable for either closed or open systems. This valve is 
primarily used to regulate the flow of water or glycol to the water-cooled condenser in each 
refrigerant circuit. By regulating the flow to the condensers the refrigerant circuit maintains 
constant head pressure.  
 
CONDENSER 
The condensers are of the coaxial 
type and capable of operating @ 
300 psi waterside and 600 psi 
refrigerant side. These condensers 
require no maintenance. 
If the condenser is of the tube and 
shell type, a manufacture’s catalog 
for maintenance and service is 
supplied at the end of manual. 
 
 
 

THERMOSTATIC EXPANSION 
VALVES 

 
This unit is equipped with thermostatic expansion valves (TEV) that control the flow of liquid 
refrigerant entering the direct expansion (DX) evaporator by maintaining a constant superheat of 
the refrigerant vapor at the outlet of the evaporator. 

 
(KHP only) 
NOTE: This unit is equipped with 2 thermal expansion valves per circuit. One is controlling 
the flow to the evaporator in cooling mode and one is controlling the flow to the condenser 
(evaporator in heating mode). This unit does not come with bi-flow expansion valves. 
 

 

FILTER-DRIERS 

 

This unit is equipped with two reversible heat pump filter driers per refrigerant circuit. The filter-
driers operate in either flow direction of the refrigerant circuit. The filter-driers consist of one core 
in a shell with two check valves at either end. These check valves control the flow, so filtration 
occurs on the outside of the core, regardless of the flow direction. The filter-driers do not release 
the dirt collected in one mode when the flow direction reverses. The filter-driers are installed in the 
reversing liquid line of each circuit. 
 

 

Содержание KHP-720

Страница 1: ...t on its side may damage internal parts and displace oil from the compressor s crankcase STORAGE If job site storage is necessary place the unit in a clean warm dry area Follow instructions under Hand...

Страница 2: ...pumps must be properly grounded as per instructions on the unit wiring diagram LOCATION OF SUPPLY RETURN CONNECTIONS CONDENSATE DRAINAGE Vertical Units Ensure that the plastic drain tube is connected...

Страница 3: ...wrench on the hexagonal surface to tighten connections Never use a wrench on the hose or sleeve that crimps the fitting into the hose Do not over tighten connections Turn in the mating threads by hand...

Страница 4: ...mperature Avoid false heat or cold sources from sunlight open doors or window drafts supply air outlets fireplaces ovens etc NOTE Electronic thermostat must be use to operate this unit HIGH LOW PRESSU...

Страница 5: ...ERIODIC MAINTENANCE 1 Air filters should be inspected monthly If filters are dirty or air flow is blocked replace filters 2 The coils should also be inspected monthly for excess moisture or icing If t...

Страница 6: ...the belts you must lower the nuts under the tilt base and then lower the top nuts until the proper tension is reached Raise lower nuts to re tighten tilt base To relieve tension in the belts start by...

Страница 7: ...that control the flow of liquid refrigerant entering the direct expansion DX evaporator by maintaining a constant superheat of the refrigerant vapor at the outlet of the evaporator KHP only NOTE This...

Страница 8: ...de economizer will provide total cooling 3 WAY DIVERTING VALVE ECONOMIZER VALVE The 3 way diverting valve is used when a unit is equipped with a waterside economizer coil The threaded ball valve is de...

Страница 9: ...9...

Страница 10: ...10...

Отзывы: