12  DIMS01-TH01 modulation electronics 

Description of setting elements: 

Jumper

 

JP1 

– gas type selection 

(natural gas / propane) – interconnection 2-3 = natural gas, 

interconnection 1-2 = propane 

Dip-switch

 (Boiler type and parameters changing switch) 

 

 

DS1-DHW 

DS2- ext. 

sensor 

DS3 - cascade 

DS4 

DS5 

DS6 

OFF 

tank 

without ext. 

sensor 

slave 

 

 

 

ON 

through-flow 

with ext. 

sensor 

master 

microswitch 

test 

 

 

 

Factory setting:DS1- according to the boiler type; DS2-OFF (mode 1.1), DS3-OFF;DS4-OFF, pump 
run-down 50% = 5 minutes; anticycling time 50% = 5 minutes; gas selection (JP1) depending on the 
order.

   

Description of operation: 

1.1

 

Mode: Heating up the system without weather compensated regulation 

Setting: Outside sensor not connected, service buttons DS2, DS3 – OFF. 

  

The  boiler  starts  working  when  the  room  thermostat  closes  (the  mode  switch  being  in  the  winter 

position).  The  pump  and  ignition  automatics  start  operating  too.  The  boiler  is  ignited  at  the  set  starting 
output. This is kept for 2 seconds after ignition (the feedback of the ignition automatics). Then the output 
is lowered to the minimum with slow linear rise (approximately 1 min.) up to the modulation point. The 
point value depends on the factory setting of the max. heating output.  The boiler output control at this 
moment is PID (proportionate/integral/derivative) while the temperature set on the control panel knob is 
maintained  (within  35  –  80 

o

C).  When  heating  the  system  with  a  lower  input  than  the  minimum  boiler 

output  is  the  outlet  heating  water  temperature  exceeds  the  set  temperature  by  5 

o

C.  At  this  moment  the 

boiler stops burning, but the pump is running and the re-ignition is restricted for some time (the factory 
setting is  0 – 10 minutes). All this means the boiler is highly flexible heat source from the point of the 
number of consequently controlled heating systems (e.g. zone regulation, thermostatic valves, etc.).  

When the room thermostat opens, the pump runs down in the set time (the factory setting is 0 – 10 

minutes). This function is used to cool down the exchanger, to drain heat from the combustion chamber 
and  to  balance  the  temperatures  of  different  heating  elements  (useful  mainly  for  horizontal  distribution 
systems) when room thermostats with PI link with short operating cycles (e.g. Honeywell CM707). 

1.2

 

Mode: Heating up the system with weather compensated regulation 

Setting: Outside sensor connected, service buttons

 

DS2 – ON, DS3 – OFF

.

 

The boiler operates on the same basis as above. The only difference is the temperature of the heating 

system  is  controlled  depending  on  the  outside  temperature  (measured  by  the  outside  sensor).  The 
calculation of the necessary temperature of the heating system is a function of the outside temperature and 
factor 

„K“ 

(weather compensation curve inclination). The factor is set by the service technician according 

to the nature of the place and the heating system. The user can set the demanded heat comfort with the 
heating water temperature knob on the control panel (the curve can be changed in the range of  

±

 15 °C of 

the heating water). 

The weather compensation curve is calculated for the standard heating system with radiators. 

Содержание Therm DUO 50 FT

Страница 1: ...Manual for installation and maintenance DUO 50 FT...

Страница 2: ...ents 7 Starting the boiler 7 Disconnecting the boiler 8 6 Regulations for control and maintenance 8 Use of the boiler 8 LCD display 9 Maintenance 10 7 Gas fitting SIT 845 SIGMA 10 8 Boiler hanging 11...

Страница 3: ...removable Above the exchangers there is an exhaust rectifier There is an eighteen armed water cooled low NOX gas burner in the lower part of the combustion chamber The burner is a product of POLIDORO...

Страница 4: ...rough which the combustion air will be supplied and another through which the flue gas will be exhausted 3 TECHNICAL SPECIFICATIONS units DUO 50 FT Flue natural gas Boiler category I2H Maximum heat in...

Страница 5: ...g must follow valid technical regulations Important No flammable objects can be placed within the safe distance from the boiler i e 50 mm and within the safe distance from the exhaust pipe and check g...

Страница 6: ...combustion air will be supplied and another through which the flue gas will be exhausted Given the wide range of possible solutions the exhaust components are not delivered as the standard boiler fix...

Страница 7: ...ilers and features of IU 02Q interface communication with programmable QAA 73 110 This kind of communication offers more programmable options and it displays the operational modes of the boiler room m...

Страница 8: ...for user s setting of water temperature in the heating system within 35 80o C the recommended range is 55 80o C If weather compensated regulation is used you can set the heating curve within 15 C from...

Страница 9: ...gain Failure or operational values exceeding indication The LCD display shows E and failure code for codes see the following chart failure code meaning E01 ignition failure E02 insufficient heating wa...

Страница 10: ...erm is signalled by top arrows in the display corners when it is a communication of a cascade IU04 10 and IU05Q it is signalled by bottom arrows Maintenance Regular maintenance is very important for r...

Страница 11: ...e manual Important The system for the setting of gas pressure range on modulator is protected by a plastic cover That is removed for gas pressure setting and after the setting it is necessary to put i...

Страница 12: ...es of heating water are done for Wilo 25 70 and Grundfos 15 60 pumps at the highest level of regulation We do not recommend lowering the pump output because of the boiler output and circulation featur...

Страница 13: ...Graphs for boiler output setting Graph for output settings of THERM DUO 50 FT natural gas nozzles 1mm 0 2 4 6 8 10 12 14 25 27 29 31 33 35 37 39 41 43 45 Boiler output kW Gas pressure mbar Starting o...

Страница 14: ...14 10 BOILER SETS 10 1 THERM DUO 50 FT set front view...

Страница 15: ...15 10 2 THERM DUO 50 FT set side and top view...

Страница 16: ...16 11 1 Wiring diagram of THERM DUO 50 FT connection...

Страница 17: ...e outlet heating water temperature exceeds the set temperature by 5 o C At this moment the boiler stops burning but the pump is running and the re ignition is restricted for some time the factory sett...

Страница 18: ...setting is to be set to a value a little higher than it is when a room thermostat is not used If the outside temperature sensor is not working the failure is signalled and the boiler works in the prev...

Страница 19: ...rts of the boiler 13 GUARANTEE AND LIABILITY FOR DEFECTS The manufacturer is not to be held liable for any mechanical damage of individual components caused by malpractice for defects caused by unprof...

Страница 20: ...sely to each other not further than 50 cm that they are exposed to the same climatic conditions C42 Separated connection to two pipelines within the same shaft The outlet of both shafts is either conc...

Страница 21: ...duction correspond with the requirements of valid norms and regulations The product packaging is to be handed in the paper disposal area the foil in the disposal containers for plastics The boiler par...

Страница 22: ...sic technical safety and hygienic requirements The product is certified by Engineering testing institute authorized person 202 THERM DUO 50 FT certificate for type testing according to EC guidelines f...

Отзывы: