30
30
In
st
al
la
tio
n
5.
Conductor Sizing
5.1 Using the following table to aid in the selection of the appropriate size conductors between the heater and
service.
Table 1 – Conductor Sizing
V
ol
ta
ge
Ph
as
e
C
u
rre
n
t
Cir
cui
t
B
re
ake
r
1
Wire Size
#10
#8
#6
#4
#2
Maximum Distance
2,3
m
ft
m
ft
m
ft
m
ft
m
ft
240
1
7.5
20
213
698
339
1110
538
1764
855
2806
1360
4462
208
3
7.3
15
320
1048
508
1668
808
2650
1285
4215
2043
6702
440
3
3.6
15
1430
4691
2275
7646
3616
11861
5750
18863
9144
29993
575
3
3
15
2442
8011
3886
12748
6176
20257
9821
32214
15616
51222
1
As per Canadian Electrical Code, Part 1.
2
Assumed voltage drop of 5%.
3
Allowable voltage drop to be determined by local authority.
6.
Local Safety Grounding
6.1 The service ground electrically grounds the
heater. If a local safety ground is required, drive
in at least one ground rod and connect it with a
suitably sized stranded copper conductor, of at
least #8 AWG, to one of the leveling leg bolts.
7.
Signal and Communications Connections
7.1
Use the 1/2” conduit knockout, or punch a
suitable size hole for the signal cable.
7.2 All signal and communications connections
are made to the 1/4” AAR control and indicate
terminal block. The terminals are labeled A1 to
A12.
Table 1 – Terminals
Terminals
Label
Description
A1 - A2
REMOTE START
A contact closure across these
terminals starts the heater when
the heater is in REMOTE RTC mode.
A3 - A4
RUN
Dry contact closes to provide a run
indication.
A5 - A6
ALARM
Dry contact closes to provide
alarm indication.
A7 - A8
FORCE OFF
Default is closed. If FORCE OFF
function is desired, remove
shorting link and replace with
customer supplied relay contact.
Open contact disables heater.
A9 - A10
TANK VALVE
These terminals are intended
to operate a 120Vac gas supply
solenoid shut off valve. They
energize when the motor contact
closes.
A11
RS-485 (+)
Communications, RS-485 positive
terminal.
A12
RS-485 (-)
Communications, RS-485 negative
terminal.
Содержание HELLFIRE 400
Страница 26: ...26 26 Installation Figure 2 140 Clearance Figure 3 155 Clearance...
Страница 27: ...27 27 Installation Figure 4 Clearance Turned 90 Degrees...
Страница 39: ...39 39 THERMON HEATING SYSTEMS INC Heater Specifications...
Страница 40: ...40 40 THERMON HEATING SYSTEMS INC Heater Specifications...
Страница 41: ...41 41 CCI THERMAL TECHNOLOGIES INC Heater Specifications...
Страница 42: ...42 42 THERMON HEATING SYSTEMS INC Heater Specifications...
Страница 54: ...54 54 NOTES...
Страница 55: ...55 55 NOTES...