2
Order Separately . . .
PETK Power and End Termination Kits (per cable)
PETK-1D
for BSX, RSX, VSX
PETK-2D
for KSX, HTSX
PETK-3D
for HPT, FP
Tools Required . . .
E4X-1
INSTALLATION PROCEDURES
The following installation procedures are suggested guidelines
for the installation of termination and connection systems.
Receiving, Storing and Handling . . .
1. Inspect materials for possible damage incurred during
shipping.
2. Report any damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper
type and quantity has been received.
4. Store in dry location prior to installation.
Kit Contents . . .
Item
Quantity
Description
1
1
E4X-1 Kit Assembly
2
1
Junction Box Cover
3
2
Stainless Steel Pipe Band
4
1
Thermostat Sensor
2
4
3
1
Installation Precautions . . .
• To minimize the potential for arcing and fi re caused by product
damage or improper installation use ground-fault protection.
The National Electrical Code (NEC) and Canadian Electrical
Code (CEC) require ground-fault protection of equipment for
each branch circuit supplying electric heat tracing.
• Installation must comply with Thermon requirements and
be installed in accordance with the NEC, CEC, or any other
applicable national and local codes.
• Component approvals and performance ratings are based on
the use of Thermon specifi ed parts only.
• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before
and during installation.
• Individuals installing these products are responsible for
complying with all applicable safety and health guidelines.
Proper personal protective equipment, or PPE, should be
utilized during installation. Contact Thermon if you have
any additional questions.
Item
Quantity
Description
1
1
RTV Tube
2
1
Power Connection Boot
3
1
End Cap
4
1
Tape Strip Tefl on 6" (PETK-3D only)
5
1
End Termination Caution Label
6
1
GRW-G Grommet (PETK-3D only) (Not used with
E4X-1)
1
2
6
4
3
5
WARNING:
Disconnect Circuit Before R
emoving Cover
E4X Thermostat
E4X-35235 30A/250 V
ac, 25A/277 Vac, 15A/480 V
ac
E4X-1-SR 30A/250 V
ac, 25A/277 Vac, 15A/480 V
ac
E4X-1-ZN 30A/250 V
ac, 25A/277 Vac, 15A/480 V
ac
for use in NEMA 4X Ordinar
y Locations
P
N
2
7
085-0
7
07