9
lights code
green
the charging station is energized.
green
the charging station is energized.
the total load exceeds 80%. if the loads
exceed 80% for a predetermined period,
the charging station will be de-energized.
Yellow
the charging station is not energized.
the total loads exceed 80%. the resump-
tion time will start when the total load is
lower than 80%.
Yellow
the charging station is not energized.
the total load is lower than 80% and the
recovery time is in progress. each flash
mean two (2) minutes before the resump-
tion of power to the charging station. (ex:
3 flashes = 6 minutes before power to the
charging station). during that period, if
the total load exceeds 80%, the recovery
time will restart from the beginning.
red
malfunction:
1) check all connections and voltage.
2) check the dip switch configuration
settings.
3) check if the current transformers (ct)
are properly connected and interlocked.
4) check if the connection for the current
transformers are properly connected to
the pcb electronics.
5) if the problem persists, send pictures
of the installation at [email protected]
and then call 1 (833) 717-1355.
off
no power. check the power source.
Charging station power supply
1. put the circuit breaker in the on position.
2. check if the electric vehicle supply equipment (eVse) is powered:
eVse powered: go to the next step.
eVse not energized: check the charging station connections.
step 7: seCure and re-enerGize
secure
1. turn off the power on the dcc.
2. put the cover back.
re-energize
1. supply electrical power to the dcc.
step 8: identiFiCation
1. identify the branch circuit breaker.
2. register all configuration settings of the charging station in the
space provided on the cover.
application
electric vehicle recovery time
following a power cut to the electric vehicle supply equipment (eVse),
a 15 minutes’ delay is initiated to monitor the total consumption of the
electrical system. power to the vehicle will then be restored if the total
load consumption is lower than 80% of the main circuit breaker rating.
electric vehicle charging time
it is recommended to schedule the charging vehicle program during
hours of low electrical consumption to minimize interruptions to the
electric charging station.
maintenance
do not use any cleaning solvents to clean the dcc.