lights code

green 

the charging station is energized.

green 

the charging station is energized.  

the total load exceeds 80%. if the loads 
exceed 80% for a predetermined period, 
the charging station will be de-energized.

Yellow 

the charging station is not energized. 

the total loads exceed 80%. the resump-
tion time will start when the total load is 
lower than 80%.

Yellow 

the charging station is not energized. 

the total load is lower than 80% and the 
recovery time is in progress. each flash 
mean two (2) minutes before the resump-
tion of power to the charging station. (ex: 
3 flashes = 6 minutes before power to the 
charging station). during that period, if 
the total load exceeds 80%, the recovery 
time will restart from the beginning.

red 

malfunction: 

1) check all connections and voltage. 
2) check the dip switch configuration 
settings. 
3) check if the current transformers (ct) 
are properly connected and interlocked. 
4) check if the connection for the current 
transformers are properly connected to 
the pcb electronics. 
5) if the problem persists, send pictures 
of the installation at [email protected]  
and then call 1 (833) 717-1355.

off 

no power. check the power source.

Charging station power supply

1. put the circuit breaker in the on position.
2. check if the electric vehicle supply equipment (eVse) is powered:

eVse powered: go to the next step.
eVse not energized: check the charging station connections.

step 7: seCure and re-enerGize

secure

1. turn off the power on the dcc.
2. put the cover back.

re-energize

1. supply electrical power to the dcc.

step 8: identiFiCation

1. identify the branch circuit breaker.
2. register all configuration settings of the charging station in the 

space provided on the cover.

application

electric vehicle recovery time

following a power cut to the electric vehicle supply equipment (eVse), 
a 15 minutes’ delay is initiated to monitor the total consumption of the 
electrical system. power to the vehicle will then be restored if the total 
load consumption is lower than 80% of the main circuit breaker rating.   

electric vehicle charging time 

it is recommended to schedule the charging vehicle program during 
hours of low electrical consumption to minimize interruptions to the 
electric charging station.

maintenance

do not use any cleaning solvents to clean the dcc.

Содержание DCC-10 series

Страница 1: ...igned by Design par Main power supply 240 208V Single Phase 60A 70A 80A 90A 100A 125A 150A 200A alimentation principale 240 208V Monophas 60A 70A 80A 90A 100A 125A 150A 200A approved market North Amer...

Страница 2: ...2...

Страница 3: ...ECTRIQUE and its licensors This installation manual cannot be modified reproduced or copied without a prior writ ten authorisation from THERMOLEC LTE E RECHARGE V HICULE LECTRIQUE and its licensors Ad...

Страница 4: ...e that the electric power source is adequate for the use of one or more DCC Do not use any cleaning solvents to clean the DCC Charge controller for electric vehicle Limited warranty 1 THERMOLEC LTE E...

Страница 5: ...ation through a 30A 40A 50A or 60A 240 208V AC circuit breaker L1 L2 and ground The DCC is equipped with a Square D cir cuit breaker QU0230 QU0240 QU0250 or QU0260 Trip Percentage TP The DCC Charge co...

Страница 6: ...installed incorrectly WARNING Ceiling installation The installation may be done in any direction DCC installation Step 1 Check the package contents 1 x Ceiling mounting support 1 INSTALLATION MANUAL...

Страница 7: ...FT4 SHIELD 4C FAS 18 or equivalent Step 5 A Dip switch programming for main power supply 1 Identify the set up section on the DCC 2 Set up the section as per the layout corresponding to the main powe...

Страница 8: ...and operating DRAWING NO DCC 10 SPLITTER BOX CONTROLLER TITLE DCC 10 SPLITTER BOX CONTROLLER BOITIER DE CONTROLE DCC 10 DATE 18 04 2018 V5 PER DCC ELECTRONIC CONTROLLER CONTROLEUR ELECTRONIQUE DCC PB...

Страница 9: ...ures of the installation at support dcc technology and then call 1 833 717 1355 OFF No power Check the power source Charging station power supply 1 Put the circuit breaker in the ON position 2 Check i...

Страница 10: ...des mati res propos de ce manuel 10 Information de s curit 10 Sp cifications 12 Caract ristiques 12 Exemple d installation 13 Installation du DCC 13 Utilisation 17 Maintenance 17 Code de lumi re 17 f...

Страница 11: ...staller le DCC Contr leur de charge pour v hicule lectrique proxi mit de mat riaux inflammables explo sifs ou combustibles produits chimiques et des vapeurs Ne pas installer le DCC Contr leur de charg...

Страница 12: ...justement programmable qui permet de prot ger une distribution lectrique en fonction de son disjoncteur principale Il permet de pr venir la surcharge d une distribution lectrique en coupant momentan m...

Страница 13: ...ps de reprise de 15 minutes exemple d installation Installation du DCC tape 1 V rifier le contenu de la bo te I Pour visionner notre vid o d installation visitez le www dcc technology fr VID O D INSTA...

Страница 14: ...ntation principale de l entr e lectrique 3 V rifier la polarit des CT 4 Raccorder les c bles des CT aux borniers l int rieur du DCC 10 pr vus cet effet tape 2 Pr paration l installation 1 Couper l ali...

Страница 15: ...g and operating DRAWING NO DCC 10 SPLITTER BOX CONTROLLER TITLE DCC 10 SPLITTER BOX CONTROLLER BOITIER DE CONTROLE DCC 10 DATE 18 04 2018 V5 PER DCC ELECTRONIC CONTROLLER CONTROLEUR ELECTRONIQUE DCC P...

Страница 16: ...uement annul e si le DCC est aliment sans que le transforma teur n ait t configur ad quatement ATTENTION Extension des fils des transformateurs de courant Les transformateurs de courant qui sont fourn...

Страница 17: ...ert La borne de recharge est aliment e en lectricit Vert La borne de recharge est aliment e en lectricit La charge totale exc de 80 Si la charge exc de 80 pendant la p riode pr d termin e l alimentati...

Отзывы: