SECOND SETPOINT (SP2) 

SECOND SETPOINT (SP2) Alarm Output 

Configure SP2 output to operate as an alarm from 

SP2.A 

in Level 2 and set the temperature alarm setting in 

SEt.2 

Level 1. The 

alarm will be triggered when the process temperature changes according to the options listed below. 

 
dV.hi  

Rises above the main setpoint by the value inserted at 

SEt.2

dV.Lo  

Falls below the main setpoint by the value inserted at 

SEt.2

Band 

Rises above or falls below the main setpoint by the value inserted at 

SEt.2

FS.hi 

Rises above the main setpoint by a 

SEt.2 

value that is greater than the setpoint. 

FS.Lo  

Falls below the main setpoint by a 

SEt.2 

value that is smaller than the setpoint. 

 
SUBSIDIARY SP2 MODE 

The following additional alarm functions can be added to the above alarm configurations using the features found in 

SP2.b 

in Level 2 

 
LtCh  

Once activated, the alarms will latch and can be manually reset when the alarm condition has been removed. 

Hold  

This prevents any alarm operation on power-up and is automatically disabled once the process reaches setpoint in 
order to allow normal alarm operation. 

Lt.ho  

Combines the effects of both 

LtCh 

&

 Hold 

and can be applied 

 
SECOND SETPOINT (SP2) Proportional control output 

Configure in 

Level 1 

using 

CyC.2 

to select proportional cycle time and 

bnd.2 

to adjust proportioning band.  

- For Heat/Cool operation see full operating manual. 
- In on/off mode, bnd.2 adjusts SP2 hysterisis. 
 

SP2 OUTPUT AND LED INDICATION STATES - IN ALARM CONDITION 

 

 

 
SP2 ALARM ANNUNCIATOR 

When an SP2 alarm mode is selected in SP2.A the alarm annunciator 

-AL- 

is displayed, alternating with the process temperature, 

during alarm condition. 

Notes: 

The alarm will be automatically reset when the temperature returns within the 

bnd.2 

setting in Level 1. 

The annunciator may be disabled by selecting function 

no.AL : on 

in level 4. 

 

SP2 in cool strategy 

See full operating manual (ADVANCED SETTINGS)

 

 

ERROR MESSAGES 

Display Flashes 

Fault Type 

Action 

inPt: FAiL

 

SENSOR FAULT  

Thermocouple burnout RTD/Pt100 open or short circuit 
or negative over-range.

 

Check sensor/wiring 
 

dAtA FAiL

 

NON-VOLATILE MEMORY ERROR 
 

De-power briefly.  
Replace unit if problem persists  

hAnd FAiL 

MANUAL POWER ERROR  

SP1 set to ON/OFF in 

CYC.t 

Select proportional mode 

tunE FAiL 

IMMEDIATE FAIL ON AUTOTUNE START 

Note: To reset and clear error press  

 

 

together briefly to cancel message.

 

1. If display setpoint=0 then enter setpoint 
2. If SP1 set to ON/OFF in 

CyC.t 

then 

select proportional mode 

FAIL LATER DURING AUTOTUNE CYCLE 

The thermal characteristics of the load exceed the 
autotune algorithm limits. The failure point is indicated by 
any display 0.0 in 

tech 

e.g. Ctb = 0.0 

1. Change conditions. eg. raise setpoint 
2. Try 

tunE : At.SP 

3. If the error message persists, call local 
CAL representative for advice.

 

FUNCTION LIST (LEVELS 1 TO 4) - 

LEVEL 1

 

Function Options 

[Factory settings] 

shown in brackets

 

Description 

Select Autotune 

tunE 

[oFF], on, ParK, At.Sp 

Used to switch the Autotune feature on and off, to select 

ParK 

or tune at setpoint. 

ParK 

temporarily turns the output(s) off. To use select 

ParK 

and exit program 

mode. To disable re-enter program at 

tunE 

and select 

oFF

SP1 Operating Parameters

 

bAnD 

0.1 to  *  C/°F 

[10ºC/18ºF]

 

SP1 proportional band/Gain or Hysteresis 
*

 25% sensor maximum Proportional control eliminates the cycling of on-off 

control. Heater power is reduced, by time proportioning action, across the 
proportional band. 

int.t 

oFF, 0.1 to 60 minutes 

[5.0]

 

SP1 integral time/reset  

Auto-corrects proportional control offset error

dEr.t 

oFF 1 - 200 seconds 

[25] 

 

SP1 derivate time/rate 

Suppresses overshoot and speeds response to 

disturbances

 

dAC 

0.5 - 5.0 x bAnd 

[1.5]

 

SP1 derivative approach control dAC  

Tunes warm-up characteristics, 

independent of normal operating conditions, by controlling when derivative action 
starts during warm-up (smaller dAC value = nearer setpoint). 

CyC.t 

A – –, on.oF, 0.1 - 81 sec 

[20]

 

SP1 proportional cycle-time 

(see section above) 

Determines the cycle rate of the output device for proportional control. Select 

on.oF 

for ON/OFF mode.

 

oFSt 

[0] to  *  °C/°F 

SP1 offset/manual reset  
*

 ±50% 

bAnd

. Applicable in proportional and ON/OFF mode with integral disable: 

Int.t : oFF

.

 

SP.LK [oFF] 

on 

Lock main setpoint  

Locks the setpoint preventing unauthorised adjustment.

 

Programmer Settings

 

SPrr 

[0] to 9995 deg/hour 

Sets the

 ramp rate 

SPrn 

on [oFF] hold 

Switches the ramp on or off, or hold at last ramp value

 

SoAK – – 

[oFF] 0 to 1440 min 

Sets the soak time 

SP2 Operating Parameters

 

SEt.2 

0 to  *  °C/°F 

[0]

 

Adjust SP2 setpoint

 

*

 Deviation Alarms 

DV.hi, DV.Lo, bAnd 

25% sensor maximum. 

*

 Full scale alarms 

FS.hi, FS.Lo 

sensor range f/s 

bnd.2 

0.1 -  *  °C/°F 

[2.0 °C/3.6°F]

 

Adjust SP2 hysteresis or proportional band/gain

 (see 

CyC.2 

setting) 

*

 25% of sensor full scale

 

CyC.2 

[on.oFF] 0.1–81 seconds 

Select SP2 ON/OFF or proportional cycle-time 

Select on.oFF for ON/OFF mode, or the cycle rate of SP2 output device for 
proportional mode. 

LEVEL 2 

Function Options 

[Factory settings] 

shown in brackets

 

Description

Manual Control Modes 

SPI.P 

0 to 100 % ‘read only’

Read SP1 output percentage power

hAnd 

[oFF] 1 to 100 % (not in 
ON/OFF) 

SP1 manual percentage power control 

For manual control should a sensor fail. 

Record typical 

SP1.P 

values beforehand.

 

PL.1 

100 to 0 % duty cycle 

[100]

 

Set SP1 power limit percentage 

Limits maximum SP1 heating power during 

warm-up and in proportional band. 

PL.2 

100 to 0 % duty cycle 

[100]

 

Set SP2 percentage power limit (cooling) 

SP2 Operating Modes

 

SP2.A 

[none] dV.hi dV.Lo bAnd 
FS.hi FS.Lo Cool 

Main SP2 operating mode
 

SP2.b 

[none] LtCh hoLd nLin 

Subsidiary SP2 mode: latch/sequence ,

Non-linear cool proportional band

Input Selection and Ranging 

dI.SP [1] 

0.1 

Select display resolution: for display of process temperature, setpoint, 

OFSt, 

Set.2, hi.SC, LoSC 

hi.SC 

sensor minimum [sensor 
maximum]

 

°C/°F 

Set full scale

 

Lo.SC 

[sensor minimum] sensor 
maximum °C/ºF 

Set scale minimum 

(default 0°C or 32°F) 

 

inPt 

 

[nonE] 

Select input sensor  

 

(See 

SENSOR SELECTION 

table) 

Unit 

[nonE] °C °F bAr Psi Ph rh 
SEt

 

Select °C/°F or process units

 

 

LEVEL 3 

Function Options 

[Factory settings] 

shown in brackets

 

Description

Output Configuration

 

Note: ‘

Read only’ after initial configuration. 

rSET ALL 

full reset to factory settings required to change 

SP1.d 

subsequently. 

SP1.d 

[nonE] rLY SSd rLY1 rLY2 
SSd1 

Select SP1 output device
Dual Relay 

and 

Dual SSd 

output options are factory set. 

SP2.d 

[nonE] SSd rLY rLY2 rLY1 
SSd2 

Read SP2 output device

(read only)

Dual Relay 

and 

Dual SSd 

output options are factory set. 

For SP1.d & SP2.d 
Note: 

(when in initial configuration only) Hold 

 

and  

 

or 

 

 for 10 seconds to move to or from output options shaded. 

burn 

                 SP1     /     SP2
[uP.SC]  

Upscale/Upscale 

dn.SC  

Downscale/Downscale 

1u.2d     

Upscale/Downscale 

1d.2u     

Downscale/Upscale 

Sensor burn-out/break protection
Caution: 

Settings affect fail safe state.

  

rEu.d 

             SP1      /      SP2
[1r.2d]   

Reverse    Direct 

1d.2d    

Direct         Direct 

1r.2r      

Reverse    Reverse 

1d.2r     

Direct        Reverse 

Select output modes: Direct/Reverse

Select 

Reverse 

on SP1 for heating and 

Direct 

for cooling applications. 

 
Caution: 

Settings affect fail safe state. 

 

rEu.L 

                SP1    /   SP2
[1n.2n]    

Normal   Normal 

1i.2n        

Invert     Normal 

1n.2i        

Normal   Invert 

1i.2i         

Invert      Invert 

Select SP1/2 LED indicator modes
 

SPAn 

[0.0] to ±25% sensor 
maximum 
 

Sensor span adjust

For recalibrating to align readings with another instrument e.g. External Meter, 
data logger. See Full Operating Manual (ADVANCED SETTINGS). 

ZEro 

[0.0] to ±25% sensor f/s 

Zero sensor error 

(see Sensor span adjust above). 

ChEK [oFF] 

on 

Select control accuracy monitor

rEAD  

[Var] hi Lo 

Read control accuracy monitor

tECh 

[Ct A] CT b Ct 1 Ct 2 Ct 3 Ct 
4 oS 1 uS oS 2 

Read Autotune tuning cycle data 

(see Operating Manual) 

 

UEr 

 

Software version number

rSET [nonE] 

ALL 

Resets all functions to factory settings 
Caution: 

This selection will lose all of the current settings.

 

FUNCTIONS MENU

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

LEVEL 4 

Access to level 4 is gained through 

UEr 

in level 3. Press and hold  

 

or 

 

 

 

for 10 seconds. 

Enter level 4 at 

Lock

, release 

 

or 

 

 

together. Display reads 

LoCK nonE 

 
Function

Options 

[Factory settings] 

shown in brackets

 

Description 

Security 

LoCK

[none] LEV.3 LEV.2 ALL 

Program security using Lock
LEV.3 

locks level 3 and 4 only- Technical Functions. 

LEV.2 

locks levels 2, 3 and 4 only - Configuration and technical Functions. 

ALL 

locks all functions 

LoCK ALL 

Function Options  

ProG

[Auto] StAY 

Program mode auto-exit switch.  

Auto-exit returns display to normal if 60 

seconds of key inactivity, select 

StAY 

to disable 

no.AL [oFF] 

on 

Disable SP2 alarm annunciator–AL

 Select on to disable -AL 

di.SS 

Dir, 1 to 32 [6] 

Display sensitivity  

dir 

= direct display of input 

= maximum, 

32 

= minimum sensitivity 

dEr.S 

0.1 to 1.0 [0.5] 

Derivative sensitivity 

 

SPECIFICATION 

Thermocouple 

9 types 

Standards:    

IPTS/68/DIN 43710 

CJC rejection:  

20:1 (0.05°/°C) typical 

External resistance:  

100

 maximum 

 

Resistance thermometer 

RTD-2/Pt100 2 wire

 

Standards:    

DIN 43760 (100

0°C/138.5

100°C Pt) 

Bulb current:   

0.2mA maximum

 

 

Linear process inputs 

mV range:    

0 to 50mV 

 

Applicable to all inputs SM = sensor maximum 

Calibration accuracy:  

±0.25%SM ±1°C 

Sampling frequency:  

input 10Hz, CJC 2 sec. 

Common mode rejection:   Negligible effect up to 140dB, 240V, 50-60Hz 
Series mode rejection:  

60dB, 50-60Hz 

Temperature coefficient:   150ppm/°C SM 
Reference conditions:  

22°C ±2°C, rated voltage after 15 minutes settling time. 

 

Output devices 

SSd/SSd1/SSd2:  

solid state relay driver: To switch a remote SSR 5Vdc +0/-15% 15mA non-isolated 

Miniature power relay:  

form A/SPST contacts (AgCdO) rLY and rLY1: 2A/250ac resistive load rLY2: 1A/250ac resistive load 

 

General 

Displays:  

 

Upper, 4 Digits, high brightness green LED. 10mm (0.4”) high. 

Lower,  

 

4 Digits, Orange LED. 9mm (0.35”) high (dual display version only) 

Digital range - 

-199 to 9999 

Hi-res mode - 

-199.9 to 999.9 

LED output indicators -  

flashing,  SP1 square, green; SP2 round, red 

Keypad:  

 

3 elastomeric buttons 

 

Environmental 

Humidity:  

 

Max 80% 

Altitude:  

 

up to 2000M 

Installation:    

Categories ll and lll 

Pollution:  

 

Degree ll 

Protection:    

NEMA 4X, lP66 

EMC emission:  

EN50081-1 FCC Rules 15 subpart J Class A 

EMC immunity:  

EN50082-2 

Ambient:  

 

0-50ºC (32-130°F) 

Mouldings:    

flame retardant polycarbonate 

Weight:  

 

1/32 DIN - 110g (3.9oz), 1/16 DIN  single display - 120g (4.2oz), 1/16 DIN dual display - 130g (4.6oz).

 

 
Approvals  

CE, UL (file number E81867), cUL, FM (3545)

 

 

Note

Applications where controller may be subjected to 110MHz –130MHz radiated RF (common in aeronautical environments) 

 

If using the 12-24V variant fitted with RS232/485 comms option, individual Ferrites (Wuerth Elektronik, Part 742 711 31, or similar) 
must be fitted to all incoming and outgoing cables, at the point of entry / exit to the controller. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

 
 
 

 

 

 
 

Range of Adjustment shown under description. If applicable, factory settings shown in 

bold

Note: 

The letter K appears in the instrument display as the character 

K

 