10
40.020.945 - rev. 04 - 2011
ITA/ITAS-US
English
5. Check the ventilation surface area: for
each 3500 BTU a surface of 270 ft
2
is
needed.
6. Check the connection of the room
thermostat.
Do not remove the cap when you do not
use a room thermostat.
Remove the cap to connect a room
thermostat.
7. Install the flue (4 ft and a raincover).
8. Make sure the On/Off switch is in the
0 position.
9. Check the supply voltage: see the
identification plate.
10. Put the plug in the socket.
11. Press the reset switch.
3.3
Power up
1. Press the On/Off switch to switch on the
heater.
2. Set the room thermostat.
The heater supplies warm air after
approximately 10 seconds.
4
OPERATION
4.1
During operation
4.2
Power down
1. Switch off the heater.
The magnet valve closes and stops the
fuel supply.
2. Disconnect the electric power.
Caution
Do not switch on the heater when the
tank is empty!
Caution
The fuel system de-aerates through
the nozzle. Close down may occur
several times when starting with an
empty filter. To rectify: press the reset
switch.
Hot
Do not touch the flue with rain cover,
nor the air outlet! The flue with rain
cover and the air outlet become hot
during operation!
Caution
After you switch off the heater, the
fan still rotates. The fan cools the
heater to avoid damage caused by
overheating. The fan stops
automatically.
Do not remove the plug from the
socket until the heater fully stops!