IMAC 4000 OIL US

Fault

Nr.

Cause

Solution

Who

The convector 

heater is starting 

up, but no flame is 

forming.

20

The fuel pump has too much

vacuum.

Clean or replace the main filter.

User

Check the suction line for

blockage.

Check the vacuum using a

vacuum gauge.

Dealer

21

The nozzle is blocked or

damaged.

Replace the nozzle.

Dealer

22

The electrodes are worn or the

settings are incorrect.

Clean or replace the electrodes. Dealer

23

The magnet valve or valves will

not open.

Check the electric connection.

You should hear a “click” when

the convector

User

Clean or replace the magnet

valve(s).

Dealer

24

The photocell is dirty or

defective.

Check and clean the glass.

Clean the photocell.

Clean the forcer plate.

User

Test the photocell and replace if

necessary.

Dealer

25

The air-inlet valve of the burner 

is not correctly set.

Check the air-inlet valve.

Measure the CO2 content and

the amount of soot.

Dealer

26

The settings of the nozzle 

holder and/or the forcer plate 

are incorrect or dirty.

Correct the settings of the

nozzle holder and the forcer

plate.

Clean the nozzle and the forcer

plate.

Dealer

27

Exhaust opening or flue

connection is in poor condition.

Connect the convector heater 

to a flue that is in good 

condition.

Correct the connections.

User

28

The ignition transformer is

defective.

Test the insulation in relation to

the burner.

Replace the ignition transformer

if necessary.

Dealer

The burner is

starting up poorly

(stutters).

29

There is insufficient fresh-air

supply.

Open a door or window.

Use an outside-air suction

device for the burner.

User

30

There are problems in the 

burner room or heat exchanger.

Clean, repair or replace the

burner room and heat

exchanger, if necessary.

Dealer

The convector

heater burns

intermittently.

31

The burner thermostat has not

been set correctly.

Set the burner thermostat

according to the manufacturer’s

specifications.

Dealer

The burner is

producing soot.

32

The air inlet has not been

correctly set.

Set the air inlet.

Dealer

Содержание IMAC 4000 OIL US

Страница 1: ...IMAC 4000 OIL US USER MANUAL...

Страница 2: ...2 40 020 950 rev 01 2019 IMAC 4000 US A B C D E F G H I J K O P Q R 1 2 3 4...

Страница 3: ...3 40 020 950 rev 01 2019 IMAC 4000 US 6 5 7...

Страница 4: ...4 40 020 950 rev 01 2019 IMAC 4000 US Language English 5...

Страница 5: ...nty regulations Environment Note The convector heater is made of various metals and synthetic materials The heater also contains electronic parts which must be treated as electronic waste Please conta...

Страница 6: ...ignited by the spark between the electrodes The light of the flame that is created will activate the photocell This photocell checks whether a good combustion is brought about In case of poor or no c...

Страница 7: ...ches stinging eyes Dizziness disorientation Difficulty breathing feels of being suffocated Proper ventilation air exchange OSHA 29 CFR 1926 57 to support combustion and maintain acceptable air quality...

Страница 8: ...nimum distance is 1 m 5 Ensure that the heated air is allowed to flow freely The minimum distance between the outlet and any obstacle is 5 m 6 Check the ventilation surface per kW a surface area of 25...

Страница 9: ...ly before carrying out any maintenance 5 3 V belts Fig 7 Impression V belt tension 13 mm 32 2 N 1 Remove the upper and lower side panels A 2 Lower the motor B by turning the adjusting nuts C 3 Remove...

Страница 10: ...ect the air flow Reset the convector heater User 9 The combination thermostat is defective Replace the combination thermostat Dealer 10 The frequency controller is in disorder Reset the frequency cont...

Страница 11: ...nt and the amount of soot Dealer 26 The settings of the nozzle holder and or the forcer plate are incorrect or dirty Correct the settings of the nozzle holder and the forcer plate Clean the nozzle and...

Страница 12: ...es will not close Close the cock see fig 8 B User Contact your dealer Dealer The convector heater stops 35 An overheating problem has occurred in the convector heater Reduce the resistance at the outl...

Страница 13: ...ion Check the temperature resistance of the hose used Contact your dealer for information about the maximum length of the exhaust hoses bends manifolds and hose clamps The maximum static pressure in t...

Страница 14: ...14 40 020 950 rev 01 2019 IMAC 4000 OIL US English Date Description Maintenance or Failure Action by A...

Страница 15: ...15 40 020 950 rev 01 2019 English IMAC 4000 OIL US Date Description Maintenance or Failure Action by...

Страница 16: ...16 40 020 950 rev 01 2019 IMAC 4000 OIL US English IMAC 4000 A Fuel filter 41 520 031 B Nozzle C Electrodes block D Set of V belts 41 740 318 2xSPA 2240LW B...

Страница 17: ...18 000 24 000 24 000 CFM 10 595 14 715 14 715 Max pressure Pa 400 1000 700 Warm air T C 44 31 43 F 111 88 109 Current A 18 29 29 Nozzle SLW USG hr 6 00 60 S Fan thermostat C 35 F 95 Burner thermostat...

Страница 18: ...18 40 020 950 rev 01 2019 IMAC 4000 US...

Страница 19: ...care but Thermobile Industries B V cannot be held liable for possible errors in the information or the consequences thereof The information provided herein may not be reproduced and or published in an...

Страница 20: ...NDUSTRIES BV Konijnenberg 80 4825 BD Breda Nederland Postbus 3312 4800 DH Breda Nederland Bedrijfsnummer 3502 T 31 0 76 587 34 50 F 31 0 76 587 27 89 info thermobile com www thermobile com 40 020 950...

Отзывы: