![THERMOBILE C17 Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/thermobile/c17/c17_manual_1105471005.webp)
5
1
-
PRESENTATION AND OPERATION
This device is a mobile air conditioner for cooling demountable structures such as tents with a cooling capacity from 7
kW to 34 kW, depending of the model.
When the relative humidity of the air inlet is high, the air can be cooled below its dew point and humidity is then con-
densed to water. This process requires a certain amount of latent cooling but allows a dehumidification process, which is
an important factor in comfort for the user.
The operating range is between 20 and 45 ° C and is controlled by the HP / LP pressure. The drop in air temperature
depends on the conditions of entry (humidity).
The device are made with two compartment, isolated from each other. Its operation is based on a cooling circuit broken
down by two groups motorcycle fans.
The side of the device on which connect the ducts contain the evaporator. The fan sucks the warm indoor air, cool this
air through the exchanger and return it cold in the tent.
The opposite side contain the condenser. The fan draws in ambient outside air, it cross through the exchanger and re-
turns it outward.
The cooling system is filled with refrigerant R410a. This circuit is completely waterproof and allows the unit to operate in
areas with a maximum ambient temperature of +45 ° C.
At high ambient temperatures (above 45 ° C), the cooling of the condenser air flow is too low and a high pressure stops
the HP switch. The pressure switches HP / BP will reset automatically after a few minutes.
At an ambient temperature below 20 ° C, moisture in the airflow can form ice on the evaporator. To avoid this, the pres-
sure switch cuts the low pressure in the system. If the ambient temperature is too low, the BP activation causes frequent
starting and stopping of the compressor. This process can damage the compressor and should be avoided by always
using the product within the specified temperature range. See "Specifications".
Exchanger
(Condensor)
Exchanger
(Evaporator)
Temp. sensor
Evaporator
Temp. sensor
Condensor
Regulator
Liquid
phase
Gas
phase
Filter
Compressor
T
o o
utd
oo
r
T
o i
nd
oo
r
(Indoor)
(Outdoor)
Compressor: Used to circulate the fluid in the cooling circuit
Filter: Absorbs moisture and impurities in the cooling circuit
Condenser: Sends the heat generated in the tent or room outwards
Regulator: Sends the amount of liquid that is right in the evaporator
Evaporator: Absorbs heat of the tent or room by cooling the air circulating
High pressure switch / BP: To ensure that the compressor does not work at a temperature too low or too high
Содержание C17
Страница 9: ...9 Dimensions C8 Dimensions C17 CR17 ...
Страница 10: ...10 Dimensions CR34 ...
Страница 14: ...14 SCHEMA ELECTRIQUE ELECTRICAL WIRING C8 Cooling only ...
Страница 15: ...15 C8 Cooling only EC AXIAL FAN VERSION ...
Страница 16: ...16 SCHEMA ELECTRIQUE ELECTRICAL WIRING C17 Cooling only ...
Страница 17: ...17 CR17 Cooling and heating SCHEMA ELECTRIQUE ELECTRICAL WIRING ...
Страница 18: ...18 CR17 Cooling and heating ...