| Main Controller: 1x8 & 5x16 Segment Programmable
6-33
|
304243H02
Mini-mite Tube Furnace
Chapter 6
The 8-segment programmable 3216c controller consists of microprocessor based
three-mode PID (Proportional, Integral and Derivative) and appropriate output switching
devices to control the furnace. The programmable controller can be used as a single set
point controller or as a programmable controller. The 8-segment digital model enables
eight segments of programming. The controller is capable of varying temperature or
process value with time through programming. A program is stored as a series of
segments and can be run once, repeated a set number of times or run continuously.
Some of the commonly used parameters in operator Level 1 and Level 2 of 3216c
controller are:
Table 2
Parameter Description and Accessibility in 3216c
No
.
Parameter
Description
Level
Access
Value
Page
No.
1
T.STAT
Timer Status
Level 1 + 2
Read/Write
rES
6-31
2
T.REMN
Timer Remaining
Level 1 + 2*
Read Only*
-
6-32
3
T.ELAP
Elapsed Time
Level 1 + 2*
Read Only*
-
6-32
4
A1.DHI
Deviation High Alarm Set Point
Level 1
Read/Write
50
6-30
5
A2.HI
High Temperature Alarm Set Point
Level 2
Read Only
1125
6-30
6
SP.SEL
Set point Select
Level 1 + 2
Read/Write
SP1
6-23
7
SP1
Set point 1
Level 1 + 2
Read/Write
0-1100
6-23
8
SP2
Set point 2
Level 1 + 2
Read/Write
0-1100
6-23
9
RAMPU
Set point Ramp Units
Level 1 + 2
Read/Write
Mins
6-23
10
SP.RAT
Set point Rate Limit
Level 1 + 2
Read/Write
Off
6-24
11
A.TUNE
Auto Tune Enable
Level 1 + 2
Read/Write
Off
6-25
12
UNITS
Display Units
Level 1 + 2
Read/Write
Deg C
6-24
13
TM.CFG
Timer Configuration
Level 1 + 2
Read/Write
Prog(10)
6-37
14
SS.SP
Soft Start Setpoint
Level 1 + 2*
Read Only*
-
6-34
15
SS.PWR
Soft Start Power Limit
Level 1 + 2*
Read Only*
-
6-34
16
T.T
Requested Time Duration
Level 1 + 2*
Read Only*
-
6-35
17
THRES
Timer Start Threshold
Level 1 + 2
Read/Write
1
6-36
18
END.T
Timer End Type
Level 1 + 2
Read/Write
Dwell
6-37
19
Timer.TimeRes
Timer resolution
Level 1
Read Only
Mins
6-37
20
Level 2
Read/Write
6-37
21
TSP.1 to TSP.4
Target Set point 1 to Target Set point
4
Level 2
Read/Write
550
6-43
22
RMP.1 to RMP.4
Ramp Rate 1 to Ramp Rate 4
Level 2
Read/Write
OFF
6-43
23
DWEL.1 to DWEL.4 Dwell Time 1 to Dwell Time 4
Level 2
Read/Write
1 hour
6-44
24
PB
Proportional Band
Level 2
Read/Write
15
-
25
TI
Integral Time
Level 2
Read/Write
95
-
26
TD
Derivative Time
Level 2
Read/Write
16
-
27
LBT
Loop Break Time
Level 2
Read/Write
30 mins
6-30
28
PV.OFS
PV Offset
Level 2
Read/Write
0
6-29
Содержание Lindberg/Blue M Mini-Mite TF55030
Страница 11: ... Safety Precautions 1 9 304243H02 Mini mite Tube Furnace Chapter 1 ...
Страница 19: ... Installation 4 17 304243H02 Mini mite Tube Furnace Chapter 4 ...
Страница 21: ... Start Up 5 19 304243H02 Mini mite Tube Furnace Chapter 5 ...
Страница 57: ... Maintenance Cleaning 8 55 304243H02 Mini mite Tube Furnace Chapter 8 ...
Страница 61: ... Wiring Diagrams 10 59 304243H02 Mini mite Tube Furnace Chapter 10 ...
Страница 67: ... Contact Information Chapter 13 13 65 304243H02 Mini mite Tube Furnace ...
Страница 68: ...Find out more at thermofisher com ...