Level Monitor Programming Instructions - Reverse Acting
1. Simultaneously press and hold the
↕
and
→
buttons, to enter
programming.
2. The display shows
PASSWORD,
then press the
→
button.
3. The display shows
0000
then press the
→
button four times.
4. The display shows
OK
then press the
→
button.
5. The display shows
CLR MAX/MIN
then press the
↕
button.
6. The display shows
SET UNITS,
then press the
→
button.
7. The display shows
5.000 PSI,
then press the
↕
button until the display
shows
138.5 “WC
.
8. Then press the
→
button.
9. The display shows
SET UNITS
then press the
↕
button.
10. The display shows
SW1
then press the
→
button.
11. If the display shows
OPEN/RISE
then press the
→
button; if not, then
press the
↕
button until the display shows
CLOSE/RISE
.
12. Then press the
→
button.
13. The display shows
SP
,
then press the
→
button.
14. The display shows
XXX.X “WC
.
15. Adjust the value of each digit using the
↕
button &
→
button until
the display shows the desired pump turn-on height in
WC INCHES
.
16. Then press the
→
button.
17. The display shows
DB
, then press the
→
button.
18. The display shows
XXX.X“WC
.
19. Adjust the value of each digit using the
↕
button &
→
button until
the display shows the desired pump turn-off height in
WC INCHES
.
20. Then press the
→
button.
2-5
Level Monitor
Thermo Scientific
Section 2
Programming