All installations and services must be performed by qualified service personnel.
16
EXAMPLE:
Heating output of furnace is 100,000 x 1.4
÷
100 = 1400 CFM. Air conditioning installed is 4 tons x
400 CFM = 1600 CFM or 48,000 BTU's.
NOTE:
The duct system must be sized for the larger CFM requirement for
cooling. If only 3 tons 36,000 BTU's of cooling x 400 CFM = 1200 CFM was installed, the duct would have to be
sized for the 1400 CFM heating requirement.
To insure obtaining the necessary air handling capacity of a duct system, each of the system components (trunk lines,
take offs, runs and register and grill-free areas) must be properly sized and matched together. A 12"x8" duct with a
400 CFM capacity for example will not flow 400 CFM if the register(s) to which it connects only flow a total of 200
CFM.
To achieve proper air movement, the main trunk lines, take offs, registers and grills of the supply return air duct
system must have an adequate square inch area to move the desired CFM. The chart shows the CFM air-handling
capability based on a 0.1" SP loss, in the supply duct system.
DUCT SIZES FOR HOMES, QUIET OFFICES OR SIMILAR INSTALLATIONS
Содержание PGL20-180
Страница 24: ...All installations and services must be performed by qualified service personnel 22...
Страница 25: ...All installations and services must be performed by qualified service personnel 23...
Страница 26: ...All installations and services must be performed by qualified service personnel 24...
Страница 27: ...All installations and services must be performed by qualified service personnel 25...
Страница 34: ...All installations and services must be performed by qualified service personnel 32 VII REPLACEMENT PARTS...
Страница 35: ...All installations and services must be performed by qualified service personnel 33...
Страница 36: ...All installations and services must be performed by qualified service personnel 34...
Страница 37: ...All installations and services must be performed by qualified service personnel 35...
Страница 38: ...All installations and services must be performed by qualified service personnel 36...