All installations and services must be performed by qualified service personnel.
22
:
When testing electrical equipment, always follow standard electrical procedures
and precautions.
1.
Electrical Branch Supply Circuit
Route all electrical wiring to the left side of the furnace. The power supply circuit to the
furnace must be installed and grounded in accordance with the provisions of the National
Electrical Code, ANSI/NFPA-70-1999, or latest edition, and all local codes having
jurisdiction. Electrical Branch Supply Circuit provisions of the Canadian Electrical Code Part
1 shall be observed and followed where applicable.
2.
Connection Of Power Supply Wires
a.
Remove the furnace control panel cover.
b.
Insert 120 VAC wires through the strain relief bushing (or conduit connection as
applicable) on the left side of the furnace junction box.
c.
Connect the “Hot” wire to the black wire marked “
L
1
”
.
d.
Connect the “Neutral” wire to the white wire marked “
L
2
”.
e.
Connect the “ground” wire to the ground lug.
3.
Connection Of Thermostat Wires
NOTE: Class 1 thermostat wire must be used inside the furnace burner compartment.
a.
Insert 24 VAC wires through the plastic grommet on the left side of the furnace casing.
b.
Connect the thermostat wires to “R” and “W” for heating.
c.
Connect the thermostat wires to the room thermostat.
IMPORTANT:
The room thermostat should be installed 4 to 5 feet above the floor on
interior wall which is relatively free from direct sources of heat (sunlight or supply airflow) or
exposure to cold (drafts from open windows and doors). The nominal anticipator setting is 0.2
amperes (refer to the thermostat literature for additional information).
Four-conductor thermostat wire is recommended for 24 VAC, low-voltage, control circuit
wiring. Only 2 wires are required for the furnace (a heating application only).
Electrical Wire Diameter
Maximum Recommended
Thermostat Wire Length
(AWG)
(feet)
24
55
22
90
20
140
18
225
Содержание OME-72D36
Страница 2: ......
Страница 7: ...All installations and services must be performed by qualified service personnel 4a...
Страница 21: ...All installations and services must be performed by qualified service personnel 18 Figure 6...
Страница 33: ...All installations and services must be performed by qualified service personnel 30 WIRING DIAGRAM...
Страница 34: ...All installations and services must be performed by qualified service personnel 31...
Страница 53: ...All installations and services must be performed by qualified service personnel 50...
Страница 54: ...All installations and services must be performed by qualified service personnel 51...
Страница 55: ......