All installations and services must be performed by qualified service personnel.

 

 

26

Sequence of Operation Glossary 

Inputs:  LIMIT - 120vac power from the High Limit Switch used to power the burner. 
 

W- Switched 24vac indicating a Heat call from the thermostat. 

 

Y - Switched 24vac indicating a Cool call from the thermostat. 

 

G - Switched 24vac indicating a call for blower operation from the thermostat. 

 

DEHUM - Switched 24vac indicating a call for Dehumidification from a de-humidistat. 

 
 

2 Stage Control 

Inputs:  LIMIT - 120vac power from the High Limit Switch used to power the burner. 
 

W1- Switched 24vac indicating a Heat call from the thermostat. (Low fire) 

 

W2- Switched 24vac indicating a Heat call from the thermostat. (High fire) 

 

Y - Switched 24vac indicating a Cool call from the thermostat. 

 

G - Switched 24vac indicating a call for blower operation from the thermostat. 

 

DEHUM - Switched 24vac indicating a call for Dehumidification from a de-humidistat. 

 
NOTE:  2-Stage T-stat 

 

W1 – Low Fire 

 

W2 – High Fire 

 

Connect 2-Stage T-stat to both W1 and W2. 

 

Single Stage T-stat 

 

W2 

 

Connect single stage T-stat to W2 only.  

 
BLOWER Speeds: 

 

HEAT - The Heating Blower speed selected by positions 1, 2 & 3 of SW1 (CFM tables on page 

4) 
 

COOL - The Cooling Blower speed selected by positions 4, 5 & 6 of SW1  (CFM tables on page 

4) 
 

LOW - The LOW Blower speed selected by positions 4, 5 & 6 of SW1  (CFM tables on page 4) 

 
ECM – PSC Replacement 

In an emergency situation, a defective ECM motor can be replaced with a PSC motor to provide 
temporary circulating air flow for heating or cooling.  This is done by replacing the ECM motor in the 
motor mounting bracket with a PSC motor of similar Horsepower.  Wire the common lead (typically 
white) of the replacement PSC motor to the neutral (common) terminal on the fan control board (N - 1 
through 7).  Connect the high-speed replacement PSC motor lead (typically black) to the EAC terminal 
on the fan control board.  The EAC contact is energized with 115VAC any time the control board is 
calling for fan operation whether in heating or cooling mode.  This replacement should be only used in 
emergency situations and only until a replacement ECM motor can be obtained and reinstalled.

 

 

Содержание OD6F/RA072DV5

Страница 1: ...SOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REFER...

Страница 2: ......

Страница 3: ...BEGINNING PAGE I BLOWER CONTROLLER INFORMATION 2 A TERMINAL DEFINITIONS FIELD WIRING 2 B WIRING SWITCHES 3 C INPUTS 6 D OUTPUTS 6 E OPERATING MODES 7 F CFM TABLES 9 II ECM TROUBLESHOOTING 19 A DIAGNOS...

Страница 4: ......

Страница 5: ...Thermostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for...

Страница 6: ...services must be performed by qualified service personnel 3 B WIRING SWITCHES TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring OH6 OH8 OD6 OL6 Single Stage F...

Страница 7: ...All installations and services must be performed by qualified service personnel 4 OH6 OD6 OL6 2 STAGE Figure 2 Blower Wiring...

Страница 8: ...All installations and services must be performed by qualified service personnel 5 Figure 3 Board Layout with Switches...

Страница 9: ...R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control operation Thermostat call for dehumidification DEHUM 24 V...

Страница 10: ...received or limit switch opens Fan Mode A call for fan G is received from the thermostat If no other mode is calling for blower operation the control will choose a Low speed value from the position o...

Страница 11: ...ard zero Table 1 ON and OFF Blower Delay Time Switch Settings Motor Blower Speed Three blower speed outputs are provided A G call for fan will provide the Low speed only A W heat call will provide the...

Страница 12: ...their respective air flow rates for the ECM blower motor To change air flow rates from that of the shipped settings use the respective SW1 dipswitch on the furnace s integrated control board see Figu...

Страница 13: ...1 Switch Settings Clg Tonage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 109 2 1 186 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 160 2 5 230 6 OFF 5 ON 4 OFF 3 1210 605 2 4 220 3 3 308 6 OFF 5 ON 4...

Страница 14: ...3 OFF 2 ON 1 OFF 883 706 79 883 75 706 94 883 94 3 OFF 2 ON 1 ON 968 744 72 968 69 774 86 968 86 3 ON 2 OFF 1 OFF 1054 843 66 1054 63 843 79 1054 79 3 ON 2 OFF 1 ON 1153 922 60 1153 58 922 72 1153 72...

Страница 15: ...e F0 02 05 3 OFF 2 OFF 1 OFF 1202 78o 1 6 146 2 5 233 3 OFF 2 OFF 1 ON 1315 71o 84o 1 9 174 2 7 252 3 OFF 2 ON 1 OFF 1429 65o 77o 2 3 206 3 2 294 3 OFF 2 ON 1 ON 1565 60o 70o 78o 2 6 242 3 6 337 Facto...

Страница 16: ...00 500 557 1 0 89 1 8 161 6 OFF 5 OFF 4 ON 2 5 1018 509 703 1 4 121 2 1 192 6 OFF 5 ON 4 OFF 3 1212 606 848 1 8 159 2 6 231 6 OFF 5 ON 4 ON 3 5 1406 703 994 2 3 203 3 1 290 Factory SW1 Switch Settings...

Страница 17: ...l SW 1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 1 3 114 1 9 173 3 OFF 2 OFF 1 ON 826 66 80 1 4 121 2 1 191 3 OFF 2 ON 1 OFF 898 61 74 1...

Страница 18: ...Air Flow Static Pressure Amps Watts Fan Control SW 1 Switch Settings Clg Tonage Cool Continous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 3 115 2 0 185 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 168 2 5 234 6 OFF 5...

Страница 19: ...898 92 3 OFF 2 ON 1 ON 983 786 64 983 67 786 84 983 84 3 ON 2 OFF 1 OFF 1068 854 59 1068 62 854 77 1068 77 3 ON 2 OFF 1 ON 1168 934 54 1168 57 934 71 1168 71 Factory SW1 Switch Settings 3 ON 2 ON 1 O...

Страница 20: ...1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 o 1 1 93 1 7 154 3 OFF 2 OFF 1 ON 826 66 o 80 o 1 2 105 1 9 168 3 OFF 2 ON 1 OFF 898 61 o 74...

Страница 21: ...essure in W C Fan Control SW 1 Sw itch Setting Clg Tonnage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 100 1 9 162 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 155 2 5 223 6 OFF 5 ON 4 OFF 3 1210 605...

Страница 22: ...are driven by the Y W G and DEHUM inputs and are located directly below those inputs They will light to indicate the presence of these signals The red Board Status LED has two functions 1 It will lig...

Страница 23: ...nt check Motor oscillates up down while being tested off of blower It is normal for motor to oscillate with no load on shaft Motor starts but runs erratically Varies up and down or intermittent Check...

Страница 24: ...Install drip loops Locate connectors above 7 and 4 o clock positions Use authorized motor and control model s for replacement Replace one motor or control model with another unless an authorized repla...

Страница 25: ...All installations and services must be performed by qualified service personnel 22 T stat in bad location Figure 4 ECM pin connectors...

Страница 26: ...RNESS TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLI...

Страница 27: ...THE INSTRUCTIONS IN THE BOXES CHECK 24V SUPPLY TO INTEGRATED CONTROL IS THERE 24V ACROSS R B C ON THE INTEGRATED CONTROL REPLACE INTEGRATED CONTROL CHECK CONNECTIONS AND WIRES AT INTEGRATED CONTROL IF...

Страница 28: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Страница 29: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables on...

Отзывы: