All installations and services must be performed by qualified service personnel.

 

 

24

CONFIRM IF EITHER BLOWER

WHEEL IS RUBBING AGAINST

HOUSING OR MOTOR SHAFT

IS SPINNING FREELY, REPAIR

OR REPLACE AS NECESSARY.

DOES BLOWER SPIN FREELY?

IS THERE 115V 

SUPPLIED TO MOTOR?

CHECK 115V SUPPLY, 
CONNECTION FUSES, 

SERVICE SWITCH AND 

DOOR SWITCH.

CHECK HARNESS 

CONNECTIONS

AND WIRE.

NO

YES

YES

YES

YES

NO

NO

NO

NO

NO

YES

YES

THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM

BLOWER MOTOR.  THE FOLLOWING SHOULD HELP ESTABLISH THE TYPE OF 

MALFUNCTION OR DEVIATION FROM THE NORMAL BLOWER OPERATION.

TO USE THIS DIAGRAM, YOU JUST NEED TO FOLLOW THE INSTRUCTIONS IN THE BOXES.

CHECK 24V SUPPLY 

TO INTEGRATED CONTROL.

IS THERE 24V 

ACROSS R & 

B/C ON THE

INTEGRATED

CONTROL?

REPLACE 

INTEGRATED 

CONTROL.

CHECK CONNECTIONS AND WIRES

AT INTEGRATED CONTROL, IF OK 

REPLACE INTEGRATED CONTROL.

CHECK CONNECTION ON HARNESS AND MOTOR, 

RECONNECT HARNESS TO MOTOR, IF 

CONNECTIONS ARE GOOD AND MOTOR STILL 

DOES NOT RUN REPLACE MOTOR.

REPLACE 16x4 BOX

NO

NO

YES

DISCONNECT 4 PIN COMMUNICATION

HARNESS FROM MOTOR.

IS THERE 30-35 VDC ACROSS PIN 1 & 4?

DISCONNECT 16 PIN 

HARNESS FROM 

16x4 BOX.  IS THERE 12VDC

ACROSS PIN12 & PIN1 

AND PIN12 & PIN3 

AT THE HARNESS PLUG?

DISCONNECT 16PIN 

HARNESS FROM 

INTEGRATED CONTROL.

IS THERE 12VDC ACROSS 

PIN6 & PIN1 

AT THE CONTROL?

TURN THERMOSTAT MANUAL FAN

SWITCH ON (IF AVAILABLE) OR JUMPER

BETWEEN R & G ON INTEGRATED CONTROL.  

IS THERE VOLTAGE GREATER THAN 

12VDC BETWEEN PIN15 & PIN1?

PERFECT SPEED 

Содержание OD6F/RA072DV5

Страница 1: ...SOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REFER...

Страница 2: ......

Страница 3: ...BEGINNING PAGE I BLOWER CONTROLLER INFORMATION 2 A TERMINAL DEFINITIONS FIELD WIRING 2 B WIRING SWITCHES 3 C INPUTS 6 D OUTPUTS 6 E OPERATING MODES 7 F CFM TABLES 9 II ECM TROUBLESHOOTING 19 A DIAGNOS...

Страница 4: ......

Страница 5: ...Thermostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for...

Страница 6: ...services must be performed by qualified service personnel 3 B WIRING SWITCHES TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring OH6 OH8 OD6 OL6 Single Stage F...

Страница 7: ...All installations and services must be performed by qualified service personnel 4 OH6 OD6 OL6 2 STAGE Figure 2 Blower Wiring...

Страница 8: ...All installations and services must be performed by qualified service personnel 5 Figure 3 Board Layout with Switches...

Страница 9: ...R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control operation Thermostat call for dehumidification DEHUM 24 V...

Страница 10: ...received or limit switch opens Fan Mode A call for fan G is received from the thermostat If no other mode is calling for blower operation the control will choose a Low speed value from the position o...

Страница 11: ...ard zero Table 1 ON and OFF Blower Delay Time Switch Settings Motor Blower Speed Three blower speed outputs are provided A G call for fan will provide the Low speed only A W heat call will provide the...

Страница 12: ...their respective air flow rates for the ECM blower motor To change air flow rates from that of the shipped settings use the respective SW1 dipswitch on the furnace s integrated control board see Figu...

Страница 13: ...1 Switch Settings Clg Tonage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 109 2 1 186 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 160 2 5 230 6 OFF 5 ON 4 OFF 3 1210 605 2 4 220 3 3 308 6 OFF 5 ON 4...

Страница 14: ...3 OFF 2 ON 1 OFF 883 706 79 883 75 706 94 883 94 3 OFF 2 ON 1 ON 968 744 72 968 69 774 86 968 86 3 ON 2 OFF 1 OFF 1054 843 66 1054 63 843 79 1054 79 3 ON 2 OFF 1 ON 1153 922 60 1153 58 922 72 1153 72...

Страница 15: ...e F0 02 05 3 OFF 2 OFF 1 OFF 1202 78o 1 6 146 2 5 233 3 OFF 2 OFF 1 ON 1315 71o 84o 1 9 174 2 7 252 3 OFF 2 ON 1 OFF 1429 65o 77o 2 3 206 3 2 294 3 OFF 2 ON 1 ON 1565 60o 70o 78o 2 6 242 3 6 337 Facto...

Страница 16: ...00 500 557 1 0 89 1 8 161 6 OFF 5 OFF 4 ON 2 5 1018 509 703 1 4 121 2 1 192 6 OFF 5 ON 4 OFF 3 1212 606 848 1 8 159 2 6 231 6 OFF 5 ON 4 ON 3 5 1406 703 994 2 3 203 3 1 290 Factory SW1 Switch Settings...

Страница 17: ...l SW 1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 1 3 114 1 9 173 3 OFF 2 OFF 1 ON 826 66 80 1 4 121 2 1 191 3 OFF 2 ON 1 OFF 898 61 74 1...

Страница 18: ...Air Flow Static Pressure Amps Watts Fan Control SW 1 Switch Settings Clg Tonage Cool Continous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 3 115 2 0 185 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 168 2 5 234 6 OFF 5...

Страница 19: ...898 92 3 OFF 2 ON 1 ON 983 786 64 983 67 786 84 983 84 3 ON 2 OFF 1 OFF 1068 854 59 1068 62 854 77 1068 77 3 ON 2 OFF 1 ON 1168 934 54 1168 57 934 71 1168 71 Factory SW1 Switch Settings 3 ON 2 ON 1 O...

Страница 20: ...1 Switch Settings Heating CFM Aprox Rise F 0 Aprox Rise F 0 Aprox Rise F 0 0 2 0 5 3 OFF 2 OFF 1 OFF 755 73 o 1 1 93 1 7 154 3 OFF 2 OFF 1 ON 826 66 o 80 o 1 2 105 1 9 168 3 OFF 2 ON 1 OFF 898 61 o 74...

Страница 21: ...essure in W C Fan Control SW 1 Sw itch Setting Clg Tonnage Cool Continuous 0 2 0 5 6 OFF 5 OFF 4 OFF 2 799 500 1 2 100 1 9 162 6 OFF 5 OFF 4 ON 2 5 1017 508 1 8 155 2 5 223 6 OFF 5 ON 4 OFF 3 1210 605...

Страница 22: ...are driven by the Y W G and DEHUM inputs and are located directly below those inputs They will light to indicate the presence of these signals The red Board Status LED has two functions 1 It will lig...

Страница 23: ...nt check Motor oscillates up down while being tested off of blower It is normal for motor to oscillate with no load on shaft Motor starts but runs erratically Varies up and down or intermittent Check...

Страница 24: ...Install drip loops Locate connectors above 7 and 4 o clock positions Use authorized motor and control model s for replacement Replace one motor or control model with another unless an authorized repla...

Страница 25: ...All installations and services must be performed by qualified service personnel 22 T stat in bad location Figure 4 ECM pin connectors...

Страница 26: ...RNESS TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLI...

Страница 27: ...THE INSTRUCTIONS IN THE BOXES CHECK 24V SUPPLY TO INTEGRATED CONTROL IS THERE 24V ACROSS R B C ON THE INTEGRATED CONTROL REPLACE INTEGRATED CONTROL CHECK CONNECTIONS AND WIRES AT INTEGRATED CONTROL IF...

Страница 28: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Страница 29: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables on...