Refrigeration Maintenance
112
Unit Evacuation
NOTE: The electrical system must be energized
throughout this procedure.
1. To prepare the unit for evacuation, recover
any refrigerant to 0 psi (0 kPa). (New Federal
Regulations may require your recovery
machine to pull the system’s pressures lower
then 0 psi [0 kPa]).
2. Close the isolation valve at the thermistor to
isolate the vacuum gauge. Turn the vacuum
gauge on to warm it up.
3. Open the compressor service valves and the
receiver outlet valve.
4. Replace and tighten the valve stem caps on all
three service valves.
5. Open the vacuum valve at the vacuum pump
and start the pump.
6. After evacuating the system for 5 minutes,
open the isolation valve at the thermistor to
access the vacuum gauge.
7. Evacuate the system to 500 microns. Back
seat the suction service valve and then
continue to evacuate the system for one
additional hour.
NOTE: The presence of refrigerant in the
compressor oil may prevent a low micron
reading from being achieved. The oil can
continue to “outgas” for long periods of
time. If the micron level appears to stall after
1/2 hour or 45 minutes between 1000 and
1500 microns, back seat the suction service
valve and observe the micron gauge. A sharp
drop in the micron reading (300 to 500
microns) indicates that refrigerant is in the
oil or a leak exists in the compressor area.
8. After the hour of additional evacuation time,
open the suction service valve. The vacuum
gauge reading will rise. Continue to evacuate
the system back down to 500 microns. When
the system reaches 500 microns, back seat the
suction service valve, close the vacuum valve
at the vacuum pump, and stop the pump.
9. Observe the reading on the vacuum gauge for
5 minutes. The pressure should not exceed
2000 microns. If the pressure exceeds 2000
microns in 5 minutes, a leak is present, or
additional evacuation time is required.
10. If the vacuum level is acceptable, start the
pump and open the vacuum valve. Evacuate
the system for 5 minutes to remove the
pressure rise. Close the vacuum valve and stop
the pump. Observe the vacuum gauge to
confirm that the system remains in a deep
vacuum.
11. Close the isolation valve at the thermistor. The
unit is now ready to charge.
CAUTION: Do not attempt to evacuate a
unit until you are sure that the unit is leak
free. A unit with less than a full
refrigerant charge should be thoroughly
leak checked and all leaks must be
repaired.
Содержание 920000
Страница 4: ......
Страница 10: ...Table of Contents 10...
Страница 22: ...Specifications 22...
Страница 41: ...Unit Description 41 Unit Photographs Figure 12 Front View Figure 13 Top View ARD026 AGA267...
Страница 42: ...Unit Description 42 Figure 14 Engine Side Door Open ARD041...
Страница 76: ...Electrical Maintenance 76...
Страница 132: ...Hilliard Clutch Maintenance 132...
Страница 134: ...Structural Maintenance 134...
Страница 146: ...Refrigeration Diagnosis 146...
Страница 148: ...Remote Evaporator Specifications 148...
Страница 150: ...Remote Evaporator Maintenance Inspection Schedule 150...
Страница 154: ...Remote Evaporator Unit Description 154...
Страница 158: ...Remote Evaporator Structural Maintenance 158...
Страница 160: ...Remote Evaporator System Diagnosis 160...
Страница 164: ...Wiring and Schematic Diagrams Index 164...
Страница 165: ...165 MD RD MT Model 30 w In Cab Schematic Diagram Page 1 of 2...
Страница 166: ...166 MD RD MT Model 30 w In Cab Schematic Diagram Page 2 of 2...
Страница 167: ...167 MD RD MT Model 30 w In Cab Wiring Diagram Page 1 of 3...
Страница 168: ...168 MD RD MT Model 30 w In Cab Wiring Diagram Page 2 of 3...
Страница 169: ...169 MD RD MT Model 30 w In Cab Wiring Diagram Page 3 of 3...
Страница 170: ...170 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Страница 171: ...171 MD RD MT Model 30 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Страница 172: ...172 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Страница 173: ...173 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Страница 174: ...174 MD RD MT Model 30 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Страница 175: ...175 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Страница 176: ...176 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Страница 177: ...177 MD RD MT Model 30 CYCLE SENTRY Wiring Diagram Page 3 of 3...
Страница 178: ...178 MD RD MT Model 50 w In Cab Schematic Diagram Page 1 of 2...
Страница 179: ...179 MD RD MT Model 50 w In Cab Schematic Diagram Page 2 of 2...
Страница 180: ...180 MD RD MT Model 50 w In Cab Wiring Diagram Page 1 of 3...
Страница 181: ...181 MD RD MT Model 50 w In Cab Wiring Diagram Page 2 of 3...
Страница 182: ...182 MD RD MT Model 50 w In Cab Wiring Diagram Page 3 of 3...
Страница 183: ...183 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 1 of 2...
Страница 184: ...184 MD RD MT Model 50 w In Cab CYCLE SENTRY Schematic Diagram Page 2 of 2...
Страница 185: ...185 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 1 of 3...
Страница 186: ...186 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 2 of 3...
Страница 187: ...187 MD RD MT Model 50 w In Cab CYCLE SENTRY Wiring Diagram Page 3 of 3...
Страница 188: ...188 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 1 of 3...
Страница 189: ...189 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 2 of 3...
Страница 190: ...190 MD RD MT Model 50 CYCLE SENTRY Wiring Diagram Page 3 of 3...