Operation
On call for heat the circulator comes on immediately, and the elements are energized in steps — two elements
per step spaced at approximately 60 second intervals. When the thermostat is satisfied, all elements and circu-
lator are de-energized at once. A high limit condition will instantly de-energize all elements and the circulator
will continue to run.
Ratings
ELECTRICAL CHARACTERISTICS — 120/240 VOLTS A.C. 3 WIRE SINGLE PHASE 60 HZ
*Net ratings are based on installed radiation of sufficient quantity to serve the requirements of the building and nothing need be added for normal
piping and pick up. Net rating is based on a piping and pick up allowance of 13%.
Dimensions
Equipment
Steel boiler, jacket, insulation, controls and
circulator
Factory Installed
– ASME relief valve,
temperature and pressure gauge, elements,
circulator, drain cock, completely wired.
Included but not installed
Air vent, thermostat.
Boiler
Size
TDE-10
TDE-15
TDE-20
TDE-25
TDE-30
KW
Rating
10
15
20
25
30
Input
34,000
51,000
68,000
85,000
102,000
Gross
Output
34,000
51,000
68,000
85,000
102,000
*Net
Output
30,000
44,000
59,000
74,000
89,000
1
43
43
43
43
43
2
–
21
42
42
42
3
–
–
–
21
42
Total
43
64
85
106
127
No. of 5KW
Heater
Elements
2
3
4
5
6
Watts
at
240V
10,000
15,000
20,000
25,000
30,000
Approx.
Shipping
Wgt. Lbs.
120
125
125
141
150
BTU/Hour
Amps
Circuit