VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised August 2017)
, Page
53.
4.14 BOOST MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Mode BOOST
WP_ActivateModeBoost
This option enables the BOOST functionality.
0 = Off
1 = On
Off
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Warm Weather
Shutdown
WP_ActivateWarmWeatherSD
Shuts down the boiler when the outside temperature
reaches a specific temperature. This temperature can
be set in the
Warm Weather Shutdown Temperature
box.
OFF / ON
0 = Off ; 1 = On
OFF
T. Ext Shutdown
WWSD
WP_WarmWeatherSDTemp
Sets the outside temperature that activates the
Warm
Weather Shutdown
, if it shuts down the boiler.
0 to 55 °C
0 to 99 °F
68 °F
Current Ext. T.
AV_OutdoorT
Shows the outside temperature in real time.
-46 to 107 °C
-50 to 250 °F
---