VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised August 2017)
, Page
50.
4.10.2 EXTERNAL CONTACT MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the
BI-E
terminal’s electrical switch.
Display
BACnet
Variable
Description
Settings
Default
STPT Source
WP_STPTSourc
eAux
Selects the source used to control the set-point temperature.
External
means that the set-point will be determined by the auxiliary
boiler. The VOLTMAX boiler therefore has no set-point temperature and is
used only to activate the auxiliary boiler’s relay.
Internal
means that the set-point temperature will be determined by the
VOLTMAX boiler.
External or
internal
Internal
4.10.3 MANUAL MODE
Manual mode is used to select the system’s operating mode (Electric or auxiliary).
Display
BACnet Variable
Description
Selection
Default
Active Boiler
WP_ActiveBoiler
This option selects which boiler is in operation; either the VOLTMAX
boiler (electric) or the auxiliary boilder (auxiliary).
VOLTMAX ou
Auxiliary
0 = VOLTMAX
1 = Auxiliary
VOLTMAX
4.10.4 BI-ENERGY MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the
BI-E
terminal’s electrical switch. The benefit of this
mode is that the system can operate the back-up boiler when needed.
Display
BACnet variable
Description
Parameters
Default
STPT Source
WP_STPTSource
Aux
Selects the source used to control the set-point temperature.
Auxiliary
means that the set-point will be determined by the auxiliary
boiler. The VOLTMAX boiler has no set-point temperature and is only
used to activate the auxiliary boiler relay.
Voltmax
means that the set-point temperature will be determined by the
VOLTMAX boiler.
Auxiliary or
VOLTMAX
0 = Auxiliary
1 = VOLTMAX
VOLTMAX
Delta T. Start
Aux.
WP_DeltaTStartA
ux
This option adjusts the temperature differential (Set-point temperature
–
Water outlet temperature) used to activate the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
20
0
F
Delta T. Stop
Aux.
WP_DeltaTStopA
ux
This option configures the temperature differential (Set-point temperature
– Water outlet temperature) in the VOLTMAX boiler used to deactivate
the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
5
0
F
Delay Start Aux.
WP_DelayStartA
ux
This option adjusts the delay in minutes before activating the auxiliary
boiler.
Min
10