Troubleshooting
FAULT
CAUSE
SOLUTION
The boiler does not reach its tempera-
ture setpoint
Boiler dirty
- Clean the flue gas pipes
Heat exchanger and burner mismatched - Check specifications and settings
Burner capacity insufficient
- Check and adjust the burner
Control thermostat faulty
- Check correct functioning
- Check the temperature setting
The boiler keeps shutting down, and
the control panel warning light comes
on
Control thermostat faulty
- Check correct functioning
- Check the temperature setting
- Check the electrical wiring
- Check the sensors
No water supply
Air in the circuit
- Check the circuit pressure
- Check the vent valve
The generator is at temperature but
the heating system is cold
Air in the circuit
- Bleed the circuit
Pump malfunctioning
- Check/unseize the pump
Problem with minimum temperature
thermostat (if present)
- Check the temperature setting
There is a smell of fumes
Fumes escaping into the air
- Clean the boiler body
- Clean the flue gas pipes
- Check that the boiler, flue pipes and
flue gas exhaust stack are all properly
sealed
The safety valve keeps opening
Incorrect circuit pressure
- Check the circuit pressure
- Check pressure reducer functioning
- Check pressure reducer setting
CH expansion vessel
- Check the efficiency of the expansion
vessel
There are traces of condensate on the
rear head
Flue gas box seals
- Check the seals between the rear head
and the flue gas box
Содержание THC 1000 GREY
Страница 1: ...THC 150 1450 GREY INSTALLATION OPERATION AND MAINTENANCE MANUAL ...
Страница 37: ...37 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Страница 38: ...38 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Страница 39: ...39 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...