INSTALLER
INSTALLER
Hoses should also be fixed to the floor and suitably protected whenever possible
The flue gas exhaust and stack connection must be made in compliance with applicable laws and standards, using heat resist-
ant, condensate resistant and stress resistant rigid pipe and sealed joints.
The stack must be fitted with a condensate trap and drain and the flue gas exhaust pipe must be installed at a slope of at least
3° towards the boiler.
DIMENSIONS (mm)
THC GREY
150
210
270
350
450
600
800
1000
1250
1450
H - Height of flue gas outlet
515
515
545
545
645
645
680
680
720
805
mm
Ø i Diameter of flue gas fitting
200
200
250
250
300
300
350
350
400
450
mm
H
ø i
THERMITAL
THC
b
The stack must guarantee the minimum draught specified by applicable technical standards, assuming zero pressure at
the connection to the flue gas exhaust.
b
Inadequate or badly dimensioned stacks and flues can increase combustion noise and affect combustion parameters
b
Joints must be sealed using suitable materials (e.g. filler, mastic or silicon based sealant).
b
Uninsulated flues are potentially dangerous and can cause burns.
Installation in B23P configurationin
The B23P configuration may only be adopted with premix gas burners. The table below specifies maximum permissible flue
back-pressure. Make sure that flue pipes are of a suitable class for the values specified in the table.
BOILER model
PREMIXED BURNER model
Flue exhaust tube maximum
pressure (*) (Pa)
Boiler noise (**) (db(A))
THC 150 GREY
RX180S/PV
150
68
THC 210 GREY
RX250S/PV
150
68
THC/C 270 GREY
RX360S/PV
150
69
THC/C 350 GREY
RX500S/PV
180
67
THC/C 450 GREY
RX500S/PV
180 (***)
74 (***)
THC/C 600 GREY
RX850S/PV
180
74
THC 800 GREY
RX1000S/PV
200
76
THC 1000 GREY
RX1000S/PV
200
76
(*)
With B23P exhaust configuration (only with RX Series premix burners).
(**)
Noise level measured as continuous sound pressure weighted according to scale A, at 1 metre from the appliance.
(***) The values indicated are valid only in working conditions with CO2 ≥ 9.2 % and at less than 300 metres above sea level.
Содержание THC 1000 GREY
Страница 1: ...THC 150 1450 GREY INSTALLATION OPERATION AND MAINTENANCE MANUAL ...
Страница 37: ...37 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Страница 38: ...38 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...
Страница 39: ...39 ENGLISH TECHNICAL ASSISTANCE CENTRE TECHNICAL ASSISTANCE CENTRE ...