12

ENGLISH

USER

If the boiler is not going to be used for an extended peri-
od of time, proceed as follows to prepare it for shutdown. 

 - Turn the function selector to OFF/RESET. 
 - Turn the mains power switch OFF. 
 - Close the fuel shut-off cock and the central heating and 

DHW circuit shut-off cocks.

Note that the frost protection and pump anti-block func-
tions are not active under these conditions. Drain the 
central heating circuit and domestic hot water circuit if 
there is any risk of freezing.

THE MAIN CONTROL PANEL

Green LED (4) 

Off = boiler in stand-by, burner out 
On = burning lit, boiler functioning normally.

Red LED (6) 

Safety shutdown:

 an error code flashes on the display.

Burner lockout:

 the red LED lights and an error code 

flashes on the display.
No error code is shown in OFF/RESET mode (

É

). To 

visualise any system errors, turn the function selector to 
"

Ç

" or "

Ö

". Error codes are displayed normally in combus-

tion analysis and frost protection modes.

To restore normal functioning, turn the function selector 
to “

É

” (OFF/RESET) then return it to its previous position: 

Summer "

Ç

", or Winter "

Ö

".

If the boiler does not restart after a number of resets, call 
your local Technical Assistance Centre. 

ON

OFF

20

40 60 80

100

4

3 2 1

0

0

120

4

6

CODE

DESCRIPTION OF ERROR

STATUS

AL10

Ignition attempts finished (no flame/condensate detected)

Lockout

AL20

Temperature threshold error

Lockout

AL21

Low temperature thermostat/condensate pump safety error

Lockout

AL29

Flue gas sensor overtemperature error

Lockout

AL71

CH flow temperature sensor error (open/short circuit)

Shutdown

AL73

CH return temperature sensor error (open/short circuit)

Shutdown

AL74

Overtemperature for no water circulation

Lockout

AL91

Primary heat exchanger needs cleaning (call Technical Assistance)

Signalling

AL28

CH flow/return sensors temperature differential error 

Lockout

AL26

CH return overtemperature

Lockout

AL79

CH flow overtemperature, or flow/return sensors temperature differential error

Lockout

AL41

Low CH water pressure 

Shutdown

AL40

Low CH water pressure (after 10 minutes)

Lockout

AL34

Fan speed error

Lockout

AL52

Generic electronic error

Lockout

AL55

Boiler configuration error (configuration jumper missing)

Lockout

WARNING LEDS AND ERRORS

Содержание SUNDAY 200 SOL

Страница 1: ...SUNDAY 200 SOL USER MANUAL...

Страница 2: ...1 Warning LEDs and errors 12 Cleaning 14 Maintenance 14 Useful information 15 CONTENTS This manual Code 20105339 Rev 1 04 17 is made up of 16 pages The following symbols are used in this manual b Iden...

Страница 3: ...be serviced regularly by Technical Assistance Service Their personnel are specially trained to keep your boiler efficient and cheap to run Technical Assistance Centres also stock any original spare pa...

Страница 4: ...ly from your local THERMITAL Technical Assistance Centre bThis boiler must be installed by a legally qualified heating engi neer in Italy heating engi neers are regulated by law 46 of the 5th March 19...

Страница 5: ...the factory The thermostatic mixer valve has to be adjusted to change this value see page 9 4 Green LED When lit shows that a flame is being detected 5 Two figure digital display Displays information...

Страница 6: ...ured by the sen sor over the last few hours is also shown If temperature sensor F2 is not installed the display reads out the message Not connected Storage cylinder top temperature sensor The display...

Страница 7: ...nating manner during automatic venting To interrupt automatic venting remove the central knob and press the combustion analysis button C ON OFF 20 40 60 80 100 4 3 2 1 0 0 120 START UP Have THERMITAL...

Страница 8: ...to the required temperature 20 C Turn the function selector 3 to SETTING CENTRAL HEATING WATER TEMPERATURE USING THE OUTDOOR TEMPERATURE SENSOR Since an outdoor temperature sensor is installed the sy...

Страница 9: ...and cold water inlet pressure 3 bar Knob position Min 1 2 3 4 5 6 7 Max Temperature C 27 32 38 44 49 53 58 63 67 Once you have set the required domestic hot water tem perature you can lock the adjust...

Страница 10: ...mer or room thermostat is installed these must be switched on and adjusted to a temperature higher than current room temperature before the boiler can start up The boiler will remain in stand by mode...

Страница 11: ...n analysis CO in being performed If you are going away for a short period of time like a weekend or a short holiday etc turn the function selector to OFF RESET The digital display reads out the messag...

Страница 12: ...OFF RESET then return it to its previous position Summer or Winter If the boiler does not restart after a number of resets call your local Technical Assistance Centre ON OFF 20 40 60 80 100 4 3 2 1 0...

Страница 13: ...elector to Remove the top front panel from the boiler by pulling it forwards Slowly refill the system opening the fill cock 2 until the pressure gauge reads between 1 and 1 2 bar Fit the top panel bac...

Страница 14: ...boiler without first dis connecting it from the mains electricity supply by turning the main power switch OFF In Italy Presidential Decree n 412 of the 26th August 1993 requires that THE PERSON RESPON...

Страница 15: ...N Seller Mr Address Tel Technical Assistance Service Mr Address Tel Fuel oil supplier Mr Address Tel Installer Mr Address Tel Date Work done Date Quantity supplied Date Quantity supplied Date Quantity...

Страница 16: ...o 7 37045 Legnago VR www thermital it As part of the company s ongoing commitment to perfecting its range of products the appearance dimensions technical data equipment and accessories may be subject...

Отзывы: